Type Designation Label - ABB FOCH Hardware Manual

Table of Contents

Advertisement

10 Operation principle
the nominal line-to-line voltage ( U n). To calculate the actual peak voltage value in volts
and d u /d t value in volts per microsecond, multiply the values of the graph by the
supply voltage ( U
).
n
The values in the first graph are measured with an ABB d u /d t filter while the second
graph without any output filtering. The values in the second graph are only
representative. The actual unfiltered d u /d t values depend on the drive type, and are
usually in the range of 1 to 5 kV/microsecond.
The voltage rise time can be calculated as follows: t = 0.8 · Û
3.0
2.5
2.0
1.5
1.0
0.5
0.0
100
A
Drive with d u /d t filter
Drive without d u /d t filter
B
I
Motor cable length
Û
/ U
Relative peak line-to-line voltage
LL
n
(d u /d t )/ U
Relative d u /d t value
n
Note: Û
and d u /d t values are approximately 20% higher with resistor braking.
LL

Type designation label

The type designation label includes IEC and UL (NEC) ratings, appropriate markings
and the type designation and serial number, which allow identification of each filter.
An example label is shown below.
A
Û
/U
LL
n
d
u
/
d
t
-
-- - -
-- -
- - - - (1/ µs)
-
U n
200
300
l (m)
/(d u /d t ).
LL
5.5
5.0
du/dt
-------------(1/ µs)
U n
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
100
B
Û
/U
LL
n
200
300
l (m)

Advertisement

Table of Contents
loading

Table of Contents