3.1 Environmental requirements

a. Ambient temperature: -10℃~+50℃ (recommended: 10℃~35℃ or 50℉~95℉).
b. Ambient humidity: 10-95%.
c. Altitude <2000m.
d. For outdoor installation
 Avoid direct sunlight
 Avoid rain and snow
 Avoid location susceptible to flooding
 Install under shed if possible
e. For indoor installation
 3 feet clearance from doors, windows, driveway or other batteries
 Keep away from heating device.
 Prevent from corrosive chemicals
 Prevent from water spillage
 Consider location equipped with ventilation fans, smoke, heat, or flammable gas
detector
HHS-1X5K/10K/15K/20K performance degrades when ambient temperature is below
10℃(50℉) or above 40℃(104℉) degrees.