Installatiehandleiding INBOUW UNITS HSP duct / LHT serie Buitenunit AOYG 72 LRLA AOYG 90 LRTLA Voor gebruik door de professional. Te bewaren door de gebruiker voor toekomstig gebruik.
INSTALLATION MANUAL To avoid getting an electric shock, never touch the electrical components soon after the OUTDOOR UNIT [Original instructions] power supply has been turned off . After turning off the power, always wait 10 minutes or PART No. 9380545231-03 English more before you touch the electrical components.
2. ABOUT THE UNIT 2.3. Accessories WARNING 2.1. Precautions for using R410A refrigerant For installation purposes, be sure to use the parts supplied by the manufacturer or other prescribed parts. The use of non-prescribed parts can cause serious accidents WARNING such as the unit falling, water leakage, electric shock, or fi...
CAUTION Unit: mm Do not install the outdoor unit in the following areas: • Area with high salt content, such as at the seaside. It will deteriorate metal parts, causing the parts to fail or the unit to leak water. •...
When an obstruction is present also in the upward area (Unit : mm) 3.4. Transporting the unit (2) Obstacles at rear, sides, and above (1) Obstacles at rear and above WARNING Do not touch the fi ns. Otherwise, personal injury could result. Max.
• Do not install directly on the ground, this may result in equipment failure. 4.3.2. Simultaneous operation multi type installation • The drain water is discharged from the bottom of the equipment. Construct a drain ditch around the base and discharge the drain water properly. CAUTION •...
5.3.4. Pipe connection 5.2. Brazing CAUTION CAUTION Seal the pipe route hole with putty (locally purchased) such that there are no gaps. Small insects or animals that are trapped in the outdoor unit may cause a short circuit in If air or another type of refrigerant enters the refrigeration cycle, the internal pressure in the electrical component box.
Single type CAUTION Do not block the walls and the ceiling until the sealing test and the charging of the Outdoor unit Pressure regulating valve refrigerant gas have been completed. For maintenance purposes, do not bury the piping of the outdoor unit. •...
Page 10
5.6.1. If additional refrigerant is required (Example 2) • When the piping is longer than chargeless piping length, additional charging is neces- Indoor unit sary. (30,000 Btu) L2 : 5 m 1) Remove the charging port cap from the liquid pipe. 2) Attach a charging hose to the refrigerant cylinder, and connect it to the charging Liquid pipe [mm] 9.52...
CAUTION 6. ELECTRICAL WIRING The primary power supply capacity is for the air conditioner itself, and does not include the concurrent use of other devices. Cable Cable size [mm²] Type Remarks Connect the power cables in positive phase sequence. If there is a missing phase con- 4 Cable + Ground Power Supply Cable Type60245 IEC66...
6.4.3. Wiring procedure 6.3. Knock out holes for wiring (1) Remove the service panel, the terminal cover and connect the wires to the terminal CAUTION in accordance with the terminal nameplate. (Fig. A, Fig. B) (2) Secure the cables using the cable clamps under the terminal blocks. (Fig. B) Be careful not to deform or scratch the panel while opening the knockout holes.
7. PIPE INSTALLATION-2 7.1. Installing insulation • Install insulation material after conducting the “5.4. Sealing test”. • To prevent condensation and water droplets, install insulation material on the refrigerant pipe. • Refer to the table to determine the thickness of the insulation material. •...
9.1. Function settings • Various functions can be set. Follow the setting methods described in 9.1.1. or 9.1.2. to set as per the requirement. Perform these settings after the indoor unit stops. Table. Settings List LED display PUMP Factory Setting Item LOW NOISE PEAK CUT Content...
10.1.3. Peak cut mode (CN132) 10. EXTERNAL INPUT AND OUTPUT • Operation that suppressed the current value can be performed by means of the connected unit. The air conditioner is set to the Peak cut mode by applying the contact Outdoor unit PC board input of a commercial On/Off...
11.2.1. Setting method on outdoor unit board 11. TEST RUN Turn on the power of the outdoor unit and enter standby mode. “POWER/MODE” Lamp lights up. 11.1. Pre-test run check items PUMP PEAK POWER/ Before the test operation, refer to the fi gure and check the following items. ERROR DOWN NOISE...
12. ERROR CODES 12.1. Error display mode Display when an error occurs. You can determine the operating status by the lighting up and blinking of the LED lamp. PUMP PEAK POWER/ ERROR DOWN NOISE MODE LED display part (L1) (L2) (L3) (L4) (L5)
(5) When LED display changes as shown in the below fi gure, close the 3-way valve on 13. PUMP DOWN the gas pipe side tightly. PUMP PEAK POWER/ WARNING ERROR DOWN NOISE MODE Never touch electrical components such as the terminal blocks except the button on (L1) (L2) (L3)