INSTALLATION MANUAL
AIR CONDITIONER (SPLIT TYPE)
Scan QR CODE to access installation and owner's manual on website.
https://www.toshiba-carrier.co.th/manuals/default.aspx
Manual are available in EN/FR/DE/IT/ES/PL/PT/NL/GR/CZ/CR/HU/
RO/BG/EE/LV/SK/SI/SV/NO/FI/DA/LT/RU.
Indoor unit
RAS-B10, 13, 18S4KVPG-E
Outdoor unit
RAS-10, 13, 18S4AVPG-E
R32
ENGLISH
1134050105A

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba RAS-B10S4KVPG-E

  • Page 1 INSTALLATION MANUAL ENGLISH AIR CONDITIONER (SPLIT TYPE) Scan QR CODE to access installation and owner’s manual on website. https://www.toshiba-carrier.co.th/manuals/default.aspx Manual are available in EN/FR/DE/IT/ES/PL/PT/NL/GR/CZ/CR/HU/ RO/BG/EE/LV/SK/SI/SV/NO/FI/DA/LT/RU. Indoor unit RAS-B10, 13, 18S4KVPG-E Outdoor unit RAS-10, 13, 18S4AVPG-E 1134050105A...
  • Page 2: Table Of Contents

    CONTENTS PRECAUTIONS FOR SAFETY ............................1 ACCESSORY AND INSTALLATION PARTS ........................5 INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS ...................6 Optional Installation Parts ..............................6 INDOOR UNIT ..................................7 Installation Place ................................7 Cutting a Hole and Mounting Installation Plate ........................7 Piping and Drain Hose Installation ...........................8 Indoor Unit Fixing ................................10 Drainage ..................................11 OUTDOOR UNIT ................................12...
  • Page 3: Precautions For Safety

    PRECAUTIONS FOR SAFETY Read the precautions in this manual carefully before This appliance is fi lled with R32. operating the unit. Warning indications on the air conditioner unit CAUTION CAUTION BURST HAZARD BURST HAZARD Open the service valves Open the service valves before the operation, before the operation, otherwise there might be the burst.
  • Page 4 DANGER • FOR USE BY QUALIFIED PERSONS ONLY. • TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK. • CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
  • Page 5 • Do not use any refrigerant different from the one specifi ed for complement or replacement. Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body.
  • Page 6 CAUTION • Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet basement or expose to rain or water. • After unpacking the unit, examine it carefully for possible damage. •...
  • Page 7: Accessory And Installation Parts

    ACCESSORY AND INSTALLATION PARTS Indoor Unit Part name Part name Installation plate × 1 Wireless remote controller × 1 Battery × 2 Remote controller holder × 1 Ultra pure fi lter × 2 Mounting screw × 8 Flat head wood screw × 2 Screw ×...
  • Page 8: Installation Diagram Of Indoor And Outdoor Units

    INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS For the rear left and bottom left piping Wall Hook Mounting screw Hook Installation plate Cut out a piece of SPACER from indoor unit packaging box, roll it and insert between the indoor unit and wall to tilt the indoor unit for better operation.
  • Page 9: Indoor Unit

    INDOOR UNIT Mounting the installation plate Installation Place Recommended mounting Indoor unit outline screw positions (Unit : mm) • A place which provides the spaces around the indoor unit as shown in the diagram. Hook • A place where there are no obstacles near the air inlet and outlet. •...
  • Page 10: Piping And Drain Hose Installation

    • Rear right • Rear left When the installation plate is directly mounted on the wall Drain hose 1. Securely fi t the installation plate onto the wall by screwing it in the upper and lower parts to hook up the indoor unit. 2.
  • Page 11 How to fi x the drain hose • Cut off the pipe exist from inside of Front panel using a coping saw or an equivalent tool. • To install the drain hose, insert the drain hose fi rmly until the connection •...
  • Page 12: Indoor Unit Fixing

    Left-hand connection with piping Indoor Unit Fixing • Bend the connecting pipe so that it is laid within 43 mm above the wall surface. If the connecting pipe is laid exceeding 43 mm above the wall 1. Remove the air inlet grille. surface, the indoor unit may unstably be set on the wall.
  • Page 13: Drainage

    How to remove the air inlet grille Drainage 1. Be careful open the air inlet grille until arm touch the stopper of the front panel. 2. Push arms on left and right side to outward direction then pull toward you 1.
  • Page 14: Outdoor Unit

    OUTDOOR UNIT Installation Place Precautions about Installation in Regions with Snowfall and Cold Temperatures • A place which provides the spaces around the outdoor unit as shown in the diagram. • Do not use the supplied drain nipple for draining water. Drain the water •...
  • Page 15: Draining The Water

    Draining the Water Refrigerant Piping Connection • Holes are provided on the base plate of the outdoor unit to ensure that the Flaring defrost water produced during heating operations is drained off effi ciently. If a centralized drain is required when installing the unit on a balcony or 1.
  • Page 16: Evacuating

    Packed valve handling precautions Evacuating • Open the valve stem all the way out, but do not try to open it beyond the stopper. After the piping has been connected to the indoor unit, you can perform the air purge together at once. Pipe size of Packed Valve Size of Hexagon wrench AIR PURGE...
  • Page 17: Electrical Works

    ELECTRICAL WORKS Model RAS-B10S4KVPG-E RAS-B13S4KVPG-E RAS-B18S4KVPG-E Power source 50 Hz, 220 – 240 V Single phase Maximum running current 8.50 A 9.95 A 12.00 A Circuit breaker rating 15 A 15 A 20 A Power supply cable H07RN-F or 60245 IEC66...
  • Page 18: In Case Of Indoor Unit Connect With 1:1 Outdoor Unit

    In Case of Indoor Unit Connect With 1:1 Outdoor Unit The power supply can be selected to connect to indoor unit or outdoor unit. Choose proper way and connect the power supply and connecting cable by follow the instruction as following. Power Supply Input at Indoor Unit Terminal Block (Recommend) Indoor Unit Outdoor Unit...
  • Page 19: Power Supply Input Wiring Diagram For 1:1 Outdoor Unit

    Power supply input Wiring Diagram for 1:1 Outdoor Unit Power supply input at Indoor Terminal Block (Recommend) Indoor Terminal Block Power supply input Outdoor Terminal Block Power supply input at Outdoor Terminal Block (Optional) Indoor Terminal Block Outdoor Terminal Block Power supply input CAUTION 1.
  • Page 20: In Case Of Indoor Unit Connect With Inverter Multi System (Ims)

    In Case of Indoor Unit Connect With Inverter Multi System (IMS) Power Supply Input at Outdoor Unit Terminal Block Indoor Unit Outdoor Unit Stripping length of the Connecting cable Connecting cable connecting cable connect to Earth line Terminal block (L N 1 2 3) 50 mm 10 mm Earth line...
  • Page 21: Others

    OTHERS Gas Leak Test Test Operation To switch the TEST RUN (COOL) mode, press [RESET] button for 10 seconds. (The beeper will make a short beep.) Check places for the indoor unit. OPERATION / Check places for RESET Button the outdoor unit. Auto Restart Function Setting •...
  • Page 23: Installation Check List

    INSTALLATION CHECK LIST Model name After finishing installation work, please check items below and hand this sheet to user to keep it in a safe place together with Owner and Installation Manuals Check date Checked by Note : Please put a mark " "...