Download Print this page
Siemens FC922 Installation Instructions Manual
Siemens FC922 Installation Instructions Manual

Siemens FC922 Installation Instructions Manual

Fire alarm control panel
Hide thumbs Also See for FC922:

Advertisement

Quick Links

FC922 / FC924 / FT924
FV922 / FV924 / VR2005
Fire Alarm Control Panel
Installation Instructions
MP-UL 3.1
Siemens Industry, Inc.
A6V10356958_en--_n
Smart Infrastructure

Advertisement

loading

Summary of Contents for Siemens FC922

  • Page 1 FC922 / FC924 / FT924 FV922 / FV924 / VR2005 Fire Alarm Control Panel Installation Instructions MP-UL 3.1 Siemens Industry, Inc. A6V10356958_en--_n Smart Infrastructure...
  • Page 2: Legal Notice

    Legal Notice Technical specifications and availability subject to change without notice. © 2020 Copyright by Siemens Industry, Inc. Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited.
  • Page 3 In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art security concept. Siemens’ portfolio only forms one element of such a concept. You are responsible for preventing unauthorized access to your plants, systems,...
  • Page 4 Non-Silenceable . BACnet client Supervision timeout Ability for the BACnet supervision Acceptable Range must be between to delay reporting network timeout to be configured from 1s to 10 1 sec and 85 sec. supervision. minutes. Siemens Industry, Inc. A6V10356958_en--_n Smart Infrastructure...
  • Page 5 Ground fault supervision for the power Ground fault supervision must be supply can be activated or turned off “on” and activated Signal Silence Inhibit Feature Signal Silence Inhibit range 0-30 UL minimum is 3 minutes minutes Siemens Industry, Inc. A6V10356958_en--_ n Smart Infrastructure...
  • Page 6 1s, 2s, 3s, 5s, 10s, 20s. FDCIO422 Input Type can be Ability to set the FDCIO422 device Not Allowed to Normally Closed inputs for configured to Normally Closed Class A & Class B wiring Siemens Industry, Inc. A6V10356958_en--_n Smart Infrastructure...
  • Page 7 Ground fault supervision for the power Ground fault supervision must be supply can be activated or turned off “on” and activated Signal Silence Inhibit Feature Signal Silence Inhibit range 0-30 ULC minimum is 5 minutes minutes Siemens Industry, Inc. A6V10356958_en--_ n Smart Infrastructure...
  • Page 8 Computer with high speed internet connection Microsoft Explorer 7.0 or higher Adobe Reader (http://www.adobe.com/) If you cannot meet these requirements, please contact Siemens Technical Support at 1-800-248-7976 to request hard copy of the installation guidelines. Location of the FS920 User Documentation To access the FS920 documentations, go to https://extranet.w3.siemens.com/buildingtechnologies/partner/FSUSENV3/Pages/default.aspx.
  • Page 9 Provide the list of compatible devices that can be connected to the Notification Appliance Circuit. FS920 Fire System CM10013en0F Describes the FS20 Protection Integration including the Integration Guide configuration steps of FC20 fire alarm control panels. Siemens Industry, Inc. A6V10356958_en--_ n Smart Infrastructure...
  • Page 10 Fiber Optic cables are used to network the panels together. The FC922 is capable of supporting up to 252 devices and FC924 is capable of supporting up to 504 devices. Both panels have a PMI with optional LED module, 2 Class B or 1 Class A NAC (expandable to 4 Class B, 2 Class A NACs), 4 control relays, Battery Charger, Aux Power connection and optional capability for connection to Leased Line or City Tie.
  • Page 11: Installation

    The FV922 and FV924 panels use 3-Height enclosure units; the FC922 and FC924 panel use 2-Height enclosure units and the FT924 and VR2005 use 1-Height enclosure units. All the modules are installed inside the enclosure backbox and inner doors (refer to Figure 3).
  • Page 12 UL (option) (FCM2025/2050-A1) and VCNET connection of the FV922/2050 Fire voice control panel. For inter- connection between FC922/FC924 and FV922/FV924, the Ethernet switch (modular) (FN2012-A1, S54400-B152-A1) must be used. The Ethernet connections can be configured as Class B or X and is supervised. For proper wiring connection, refer to the FN2012-A1 Installation Instructions, Document ID A6V10407862.
  • Page 13 Knockouts: 4, 7, 8, 9, 10, 11 are for Power Limited only Notes: Refer to Table 5 to locate each module wiring diagram. Figure 1: Module Location in 2HU Enclosure and Recommended Wire Routing Siemens Industry, Inc. A6V10356958_en--_ n Smart Infrastructure...
  • Page 14 Recommended Wiring Routes: 7 – FN2006-U1 /FN2007-U1 - Knockouts: 1, 2, 3, 4 are for Power Limited wiring only 11- FHA2031-U1 Notes: Refer to Table 5 to locate each module wiring diagram. 12 – FTI2001-U1 Siemens Industry, Inc. A6V10356958_en--_n Smart Infrastructure...
  • Page 15 - Knockouts 2, 7, 10, 11, 12 are for 4. FHA2031-U1 10. Battery set power limited wiring. 5. FCI2020-U1 11. VTO2001-U2/U3 6. FCI2016/FCI2017-U1 12. FCM2022-U2/U3 7. FCI2011-U1 or XCI2001 -U1 13. VTO2004-U2/U3 14. FCA2032-U1 Siemens Industry, Inc. A6V10356958_en--_ n Smart Infrastructure...
  • Page 16: Module Locations

    Figure 4: Module Location in 1HU Remote Microphone Station and Recommended Wire Routing Module Locations: Recommended Wiring Routes: VTO2004-U2/U3 Any knockouts may be used for the power-limited wiring VTO2001-U2/U3 associated with the Remote Microphone. VTA2001- A1 FHA2031-U1 (optional) Siemens Industry, Inc. A6V10356958_en--_n Smart Infrastructure...
  • Page 17 / VN2003-A1 As indicated in Figure 5, FTI2001-U1 and VTA2001-A1 are VTO2004-U2/U3 stacked on top of one another using the standoff provided with VTO2002-U2/U3 VTA2001-A1. It is shown flat for ease of layout. Siemens Industry, Inc. A6V10356958_en--_ n Smart Infrastructure...
  • Page 18 Figure 6: Module Location in MXL-IQ MSE-3L Enclosure and Recommended Wire Routing Module Locations in MSE-3L Enclosure Notes: using Adapter Plate (P/N A5Q00075220): To install an FCL2004-U1 module in a MSE-3L enclosure, install a FCL2004-U1 FHA-MIQKIT-04 (Black) or FHA-MIQKIT-05 (Red). FCL2004-U1 (optional) FCI2016/FC2017-U1 FCM2018/FCM2019-U2/-U3 Siemens Industry, Inc. A6V10356958_en--_n Smart Infrastructure...
  • Page 19 Module Locations in 2HU Enclosure using Notes: Adapter Plate (P/N A5Q00079811): For mounting the FCL2004-U1 module(s) in a 2HU enclosure, FCL2004-U1 refer to the FCL-MXLPLATE Installation Instructions, Document FCL2004-U1 (optional) ID A6V11877890. FCI2016/FC2017-U1 FCM2018/FCM2019-U2/-U3 Siemens Industry, Inc. A6V10356958_en--_ n Smart Infrastructure...
  • Page 20 Section 12.4 of NFPA 72, 2010 edition. All wiring between the releasing device and any other interconnected product shall be monitored for integrity in accordance with the Common Performance and Monitoring for Integrity – Protected Premises Units/Systems. Siemens Industry, Inc. A6V10356958_en--_n Smart Infrastructure...
  • Page 21 Siemens Industry, Inc. A6V10356958_en--_ n Smart Infrastructure...
  • Page 22 A6V10350024 FHA2036-R1 S54400-B42-A2 Trim Kit 2HU Red A6V10350024 FT2003-U1 S54400-C136-A1 Graphic driver (I/O) A6V10384377 FCA2032-U1 S54400-B145-A1 Battery disconnect module A6V10385200 FHD2012-U1 S54400-C135-A1 Inner Door RDT (black) A6V10385202 FCL2004-U1 S54400-A68-A1 MXL Device Interface Module A6V11415283 Siemens Industry, Inc. A6V10356958_en--_n Smart Infrastructure...
  • Page 23 Tabular annunciator (32 z, bl) A6V10456397 FT2009-R1 S54400-A146-A1 Tabular annunciator (32 z, red) A6V10456397 PAD-5 S54339-A5-A1 Power Expander Main Board A6V101030358 PAD-5-CLSA S54339-A6-A1 Class A/B Expansion Board w/ A6V101030359 Releasing PAD-5-CDC S54339-A7-A1 Conventional Detector Expansion A6V101030366 Board Siemens Industry, Inc. A6V10356958_en--_ n Smart Infrastructure...
  • Page 24 0.000 200 mA (stanby) 210mA(alarm) per module 196 mA(standby) 2.42A @ 25V (alarm) per VCI2001-U1 Voice ampl. Card (25V/70V) 0.000 0.000 module VN2001-A1 Ethernet module (electric) 0.000 0.000 7 mA(standby) 7mA (active) per module Siemens Industry, Inc. A6V10356958_en--_n Smart Infrastructure...
  • Page 25 1.0 mA per device ILED /8726 Intelligent LED 0.00000 1.4 mA per device PAD-5 Power Expander Main Board 0.00000 0.75 mA per expander Conventional Detector PAD-5-CDC Expansion Board 0.00000 0.75 mA per board Siemens Industry, Inc. A6V10356958_en--_ n Smart Infrastructure...
  • Page 26: Battery Calculation

    10. Calculate the Battery Reserve (AH) = (Battery Reserve (%) / 100%) x (System Alarm Req + System Standby Req) 11. Calculate the minimum battery Requirement = Battery Reserve + System Alarm Req + System Standby Req. Select the battery that meets or exceeds the final calculated amp hour rating. Siemens Industry, Inc. A6V10356958_en--_n Smart Infrastructure...
  • Page 27 This page has been left intentionally blank. Siemens Industry, Inc. A6V10356958_en--_ n Smart Infrastructure...
  • Page 28 Issued by © 2020 Siemens Industry, Inc. Siemens Industry, Inc. Technical specifications and availability subject to change without notice. Smart Infrastructure 8 Fernwood Road Florham Park, NJ 07932 Tel. +1 973-593-2600 www.downloads.siemens.com/dlc Document ID A6V10356958_ en--_n SAP order no.: A5Q00051308...

This manual is also suitable for:

Fc924Ft924Fv922Fv924Vr2005Fc924-us ... Show all