IM_D0X7205001-01_EN.book Page 1 Friday, May 19, 2023 9:06 PM
AIR CONDITIONER (SPLIT TYPE)
Installation Manual
Indoor Unit
Model name:
<Slim Duct Type>
RAV-HM301SDTY-E
RAV-HM401SDTY-E
RAV-HM561SDTY-E
RAV-HM801SDTY-E
D 0 X 7 2 0 5 0 0 1 -
0 1
R32
For commercial use
English

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba RAV-HM301SDTY-E

  • Page 1 IM_D0X7205001-01_EN.book Page 1 Friday, May 19, 2023 9:06 PM D 0 X 7 2 0 5 0 0 1 - AIR CONDITIONER (SPLIT TYPE) Installation Manual For commercial use Indoor Unit Model name: <Slim Duct Type> RAV-HM301SDTY-E RAV-HM401SDTY-E RAV-HM561SDTY-E RAV-HM801SDTY-E English...
  • Page 2: Table Of Contents

    IM_D0X7205001-01_EN.book Page 1 Friday, May 19, 2023 9:06 PM – 1 – Contents Original instruction Please read this Installation Manual carefully before installing the Air Conditioner. • This Manual describes the installation method of the indoor unit. Precautions for Safety ..........3 •...
  • Page 3 Encontrará más información en el MANUAL DEL PROPIETARIO, el MANUAL DE INSTALACIÓN y otros formación relativa a la realización de trabajos en altura con los aparatos de aire acondicionado fabricados por Toshiba Carrier Corporation, o, de otro modo, habrá sido instruida en dichas tareas por documentos similares.
  • Page 4 IM_D0X7205001-01_EN.book Page 54 Friday, May 19, 2023 9:06 PM Precauciones de seguridad  Indicaciones de advertencia en la unidad de aire acondicionado El fabricante no se hará responsable de ningún daño producido por no seguir las descripciones de este manual. Indicación de advertencia Descripción ADVERTENCIA...
  • Page 5 IM_D0X7205001-01_EN.book Page 55 Friday, May 19, 2023 9:06 PM – 55 – • Sólo un instalador cualificado(*1) o una persona de servicio • Este aparato está destinado a ser utilizado por usuarios expertos o cualificada(*1) tiene permiso para realizar trabajos en lugares altos formados en tiendas, industria ligera o para uso comercial por usando una base de 50 cm o más o para quitar la rejilla de parte de personas no expertas.
  • Page 6 IM_D0X7205001-01_EN.book Page 56 Friday, May 19, 2023 9:06 PM Instalación Tubería del refrigerante • La longitud del conducto de succión debe ser mayor de 850 mm. • Instale firmemente el tubo del refrigerante durante los trabajos de • Cuando la unidad interior vaya a instalarse suspendida deberán instalación antes de poner en funcionamiento el aparato de aire usarse los pernos para colgar (M10 ó...
  • Page 7 IM_D0X7205001-01_EN.book Page 57 Friday, May 19, 2023 9:06 PM – 57 – • Use cables que cumplan con las especificaciones del manual de • Si surge cualquier problema (por ejemplo, ha aparecido un instalación y las estipulaciones de las normas y leyes locales. El indicador de código de comprobación, olor a quemado, sonidos uso de cables que no cumplen con las especificaciones puede dar anómalos, el aire acondicionado no enfría ni calienta o hay fugas...
  • Page 8 IM_D0X7205001-01_EN.book Page 58 Friday, May 19, 2023 9:06 PM Recolocación Para desconectar el dispositivo de la fuente de alimentación. • Sólo un instalador cualificado (*1) o una persona de servicio • Este dispositivo debe conectarse a la fuente de alimentación cualificada (*1) tiene permiso para recolocar el aparato de aire mediante un interruptor cuya separación de contacto sea como acondicionado.
  • Page 9 IM_D0X7205001-01_EN.book Page 59 Friday, May 19, 2023 9:06 PM – 59 – • La conexiones mecánicas deben ser accesibles para propósitos de PRECAUCIÓN mantenimiento. Cuando se utiliza un refrigerante inflamable, todos los • En los casos que requieren ventilación mecánica, las aberturas de electrodomésticos deben cargarse con refrigerante en el lugar de ventilación deben mantenerse sin obstrucciones.
  • Page 10 IM_D0X7205001-01_EN.book Page 60 Friday, May 19, 2023 9:06 PM • Las válvulas de solenoide se colocarán correctamente en la • Al conectar a una unidad exterior de refrigerante R32 y usar un tubería para evitar descargas hidráulicas. detector de fugas, encienda siempre la alimentación de la unidad •...
  • Page 11 IM_D0X7205001-01_EN.book Page 61 Friday, May 19, 2023 9:06 PM – 61 – 4. Comprobación de la presencia de refrigerante • Debe continuar habiendo un grado de ventilación durante el período en que se realiza el trabajo. • Se debe comprobar el área con un detector de refrigerante •...
  • Page 12 IM_D0X7205001-01_EN.book Page 62 Friday, May 19, 2023 9:06 PM 9. Comprobaciones a dispositivos eléctricos • Asegúrese de que el aparato está montado con seguridad. • La reparación y el mantenimiento de componentes eléctricos debe • Asegúrese de que los sellos o materiales de sellado no se hayan incluir comprobaciones de seguridad iniciales y procedimientos de degradado hasta el punto de que ya no sirvan para evitar la inspección de componentes.
  • Page 13 IM_D0X7205001-01_EN.book Page 63 Friday, May 19, 2023 9:06 PM – 63 – de ignición en la búsqueda o detección de fugas de refrigerante. refrigerante empleado y el porcentaje apropiado de gas (25% • No se utilizará una antorcha de haluro (o ningún otro detector que máximo) está...
  • Page 14 IM_D0X7205001-01_EN.book Page 64 Friday, May 19, 2023 9:06 PM • El enjuague se debe lograr rompiendo el vacío en el sistema con 17. Desmantelamiento OFN y continuando llenando hasta que se alcance la presión de • Antes de llevar a cabo este procedimiento, es esencial que el trabajo, después ventilándola a la atmósfera y finalmente tirando técnico esté...
  • Page 15 IM_D0X7205001-01_EN.book Page 65 Friday, May 19, 2023 9:06 PM – 65 – j) Cuando los cilindros se hayan llenado correctamente y se haya recuperación de todos los refrigerantes apropiados. completado el proceso, asegúrese de que los cilindros y el • Además, debe haber disponible un conjunto de balanzas equipo se retiren rápidamente del sitio y que todas las válvulas calibradas y en buen estado de funcionamiento.
  • Page 16: Accessory Parts

    IM_D0X7205001-01_EN.book Page 122 Friday, May 19, 2023 9:06 PM Accessory parts Selection of installation place Q’ty WARNING Part name Model type Shape Usage 301 401 • Install the air conditioner securely in a location where the base can sustain the weight adequately. If the strength is not enough, the unit may fall down resulting in injury.
  • Page 17 IM_D0X7205001-01_EN.book Page 123 Friday, May 19, 2023 9:06 PM – 123 –  Installation space • Locations where there is anything under the unit installed that would be exposed to wet risk. (If the drain has become blocked or when the humidity is over 80 %, condensation from the indoor unit will drip, possibly causing damage to anything underneath.) (Unit: mm) •...
  • Page 18: Installation

    01_IM_D0X7205001-01_EN-2.fm Page 124 Friday, June 9, 2023 2:03 PM Installation CAUTION CAUTION Strictly comply with the following rules to prevent damage of the indoor units and human injury. • Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged) •...
  • Page 19 IM_D0X7205001-01_EN.book Page 125 Friday, May 19, 2023 9:06 PM – 125 –  Installation of hanging bolt  Installation of indoor unit REQUIREMENT • Consider the piping / wiring after the unit is hung to Treatment of ceiling determine the location of the indoor unit installation •...
  • Page 20: Drain Piping

    IM_D0X7205001-01_EN.book Page 126 Friday, May 19, 2023 9:06 PM Drain piping  Installation of remote controller (sold separately) CAUTION CAUTION For installation of the wired remote controller, follow the Installation Manual attached with the remote controller. Following the Installation Manual, perform the drain piping work so that water is properly drained. Apply a heat insulation so •...
  • Page 21 IM_D0X7205001-01_EN.book Page 127 Friday, May 19, 2023 9:06 PM – 127 –  Pipe material, size and insulator  Drain up The following materials for piping work and insulating process are procured locally. When a down-gradient cannot be secured for the drain pipe, drain-up For drain pipes that will be piping is possible.
  • Page 22 IM_D0X7205001-01_EN.book Page 128 Friday, May 19, 2023 9:06 PM  Heat insulating process • As shown in the figure, cover the flexible hose and hose band with the attached heat insulator up to the bottom of the indoor unit without gap. •...
  • Page 23: Duct Design

    IM_D0X7205001-01_EN.book Page 129 Friday, May 19, 2023 9:06 PM – 129 – Duct design  Arrangement Referring to the following dimensions, manufacture duct at the local site. (Unit: mm) 301, 401 <Under air intake> <Under air intake> <Under air intake> 658.8 858.8 1058.8...
  • Page 24 IM_D0X7205001-01_EN.book Page 130 Friday, May 19, 2023 9:06 PM  Fan characteristics 301 type 401 type Standard air volume: 570 (m Standard air volume: 600 (m Upper limit of external static pressure (50Pa) High (50Pa) High (50Pa) Upper limit of external static pressure (50Pa) Lower limit of Lower limit of...
  • Page 25 IM_D0X7205001-01_EN.book Page 131 Friday, May 19, 2023 9:06 PM – 131 –  Installation of filter rail and filter Insert the filter into the rail in the direction of the arrow as shown in the figure below until it reaches the filter stopper. Under air intake •...
  • Page 26: Refrigerant Piping

    IM_D0X7205001-01_EN.book Page 132 Friday, May 19, 2023 9:06 PM Refrigerant piping  Connecting method of the duct Projection margin in flaring: B (Unit: mm) Connect a duct to the outside of the flange. In CAUTION CAUTION addition, the duct must be Outer dia.
  • Page 27: Electrical Connection

    IM_D0X7205001-01_EN.book Page 133 Friday, May 19, 2023 9:06 PM – 133 – Electrical connection • Use the tightening torque levels as listed in the table below. REQUIREMENT Outer dia. of connecting • Apply the heat insulation to the pipe connecting Tightening torque (N•m) WARNING pipe...
  • Page 28 IM_D0X7205001-01_EN.book Page 134 Friday, May 19, 2023 9:06 PM Remote controller wiring Indoor unit Indoor unit Indoor unit Indoor unit Remote controller wiring, remote controller inter-unit wiring Wire size: 2 × 0.5 to 2.0 mm Remote controller In case of wired type only Up to 500 m wiring Total wire length of remote controller wiring and remote...
  • Page 29: Applicable Controls

    IM_D0X7205001-01_EN.book Page 135 Friday, May 19, 2023 9:06 PM – 135 – Applicable controls  Wire connection REQUIREMENT REQUIREMENT • Connect the wires matching the terminal numbers. Incorrect connection causes a trouble. When the air conditioner is used for the first time, it will •...
  • Page 30 IM_D0X7205001-01_EN.book Page 136 Friday, May 19, 2023 9:06 PM [5d] Push the menu button to make Code No. [  To secure better effect of  Remote controller sensor • Specify for the Code No. in procedure flash. Change Code No. [ ] with [ •...
  • Page 31: Test Run

    IM_D0X7205001-01_EN.book Page 137 Friday, May 19, 2023 9:06 PM – 137 – Test run Wired remote controller  Before test run Wired remote controller <Overview of test run operations using the wireless Be sure to stop the air conditioner before making •...
  • Page 32: Maintenance

    IM_D0X7205001-01_EN.book Page 138 Friday, May 19, 2023 9:06 PM Maintenance Periodic Maintenance For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air conditioner in use be cleaned and maintained regularly to ensure efficient operation of the air conditioner. CAUTION CAUTION When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended.
  • Page 33: Troubleshooting

    IM_D0X7205001-01_EN.book Page 139 Friday, May 19, 2023 9:06 PM – 139 – Troubleshooting  Check codes and parts to be checked Wired Wireless remote controller remote Sensor block display of  Confirmation and check controller receiving unit Judging display Main defective parts Parts to be checked / trouble description conditioner device...
  • Page 34 IM_D0X7205001-01_EN.book Page 140 Friday, May 19, 2023 9:06 PM Wired Wired Wireless remote controller Wireless remote controller remote remote Sensor block display of Sensor block display of controller controller receiving unit receiving unit display Judging display Judging Main defective parts Parts to be checked / trouble description conditioner Main defective parts...
  • Page 35 IM_D0X7205001-01_EN.book Page 141 Friday, May 19, 2023 9:06 PM – 141 – Trouble detected by central control device Check code Wireless remote controller Outdoor unit 7-segment display Sensor block display of receiving unit Check code name Judging device Central control device indication Auxiliary code Operation...
  • Page 36: Specifications

    Heating to check your units with the spanner mark (Notice code mark) on the wired remote controller or central controller display. RAV-HM301SDTY-E • Even while the notice code mark is displayed, the air conditioner can operate normally. RAV-HM401SDTY-E • A maximum of 5 notice codes can be issued simultaneously in one system (line).
  • Page 37 – 143 – Declaration of Conformity Declaration of Conformity Manufacturer: Toshiba Carrier Air Conditioning (China) Co., Ltd. Manufacturer: Toshiba Carrier Air Conditioning (China) Co., Ltd. No.181, Weiken Street, Baiyang Block, Hangzhou Qiantang New Area, No.181, Weiken Street, Baiyang Block, Hangzhou Qiantang New Area,...
  • Page 38 IM_D0X7205001-01_EN.book Page 144 Friday, May 19, 2023 9:06 PM 71-EN – 144 – 72-EN...
  • Page 39 IM_D0X7205001-01_EN.book Page 145 Friday, May 19, 2023 9:06 PM – 145 – MEMO...
  • Page 40 IM_D0X7205001-01_EN.book Page 146 Friday, May 19, 2023 9:06 PM MEMO – 146 –...
  • Page 41 IM_D0X7205001-01_EN.book Page 147 Friday, May 19, 2023 9:06 PM Toshiba Carrier Air Conditioning (China) Co., Ltd. D0X7205001-01...