Retrieving The Event Log; Behavior On Overload - Dell 1000W User Manual

Line-interactive rack ups 1000w, 1920/1500w, and 2700/2300w
Hide thumbs Also See for 1000W:
Table of Contents

Advertisement

Retrieving the Event Log

To retrieve the Event Log through the display:
1
Press the
button for one second to go to the main menu selection and scroll down to the
Event Log menu using the
2
Press the
button to enter the Event Log list.
3
Scroll through the listed events, notices, and alarms using either the
4
To return to the main menu, press the
5
Press the
button. The UPS status screen displays.

Behavior on Overload

See Table 8 for an explanation of how the UPS responds to an overload condition.
Table 8. Behavior on Overload
Overload Severity
Load Level
Level 1
100% to 101%
Level 2
102% to 110%
Level 3
> 110%
50
|
Operation
button.
button for one second. The Event Log displays.
On Utility Power
Overload alarm only and
support load indefinitely
Transfer to Fault mode in
2 minutes (±1 sec)
Transfer to Fault mode in
300 ms to 1 sec
button or the
On Battery
Overload alarm only, support load until
low battery shutdown level is reached
Transfer to Fault mode in 12 seconds
(±1 sec) or until low battery shutdown
level is reached
Transfer to Fault mode in 300 ms to
1 sec
button.