950 W AC-Input and DC-Input Power Supplies
Table A-3
Item
Branch circuit requirement (AC-input)
Power supply output capacity
DC-input voltage
DC-input current
Power supply output (AC supply)
Power supply output (DC supply)
Output holdup time
Heat Dissipation
Catalyst 6500 Series Switches Installation Guide
A-6
950 W AC-Input and DC-Input Power Supplies Specifications (continued)
Appendix A
Specification
Each chassis power supply should have its own
dedicated, fused-branch circuit:
For North America—15 A
•
For International—Circuits sized to local and
•
national codes
All Catalyst 6500 series AC-input power supplies
•
require single-phase source AC.
All AC power supply inputs are fully isolated.
•
Source AC can be out of phase between
–
multiple power supplies in the same chassis,
which means that PS1 can be operating from
phase A and PS2 can be operating from
phase B.
Source AC can be out of phase between AC
–
inputs on power supplies that are equipped
with multiple AC inputs, which means that
power cord 1 can be plugged into phase A and
power cord 2 can be plugged into phase B.
950 W maximum (100–240 VAC)
–48 VDC to –60 VDC continuous
38 A @ –48 VDC
•
30 A @ –60 VDC
•
•
15 A @ +1.5 V
2.5 A @ +3.3 V
•
19.15 A @ +50 V
•
15 A @ +1.5 V
•
2.5 A @ +3.3 V
•
19.15 A @ +50 V
•
•
20 ms minimum (AC-input power supply)
4 ms (DC-input power supply)
•
4441 BTU/hour (approx.) AC-input power supply
•
4632 BTU/hour (approx.) DC-input power supply
•
Power Supply Specifications