Mitsubishi Electric REMOTE STATUS ALARM PANEL Instruction Manual page 14

Remote status alarm panel
Table of Contents

Advertisement

1
2
External Terminal
A
Strip in UPS
Output Overload
18
Common
17
Output Overload
Battery Low
16
Common
15
Battery Low
UPS Failure
B
Common
UPS Failure
Converter Operation
14
Common
13
Converter Operation
Battery Operation
12
Common
11
Battery Operation
Load on Inverter
Common
C
Load on Inverter
Load on Bypass
10
Common
Load on Bypass
D
10/13/04
3
6
5
8
7
9
16 awg twisted pair recommended
0
4
5
Mitsubishi Electric
Automation, Inc.
Date
Tom Kobayashi
Drawn by
U-23C012
Dwg No.
93120-MAN07
6
7
Terminal Strip TB1 in
Remote Status Alarm Panel
Output Overload
16
Common
15
Output Overload
Low Battery
14
Common
13
Low Battery
UPS Failure
12
Common
11
UPS Failure
Rectifier On
10
Common
9
Rectifier On
On Batteries
8
Common
7
On Batteries
Load on Inverter
6
Common
5
Load on Inverter
Load on Bypass
4
Common
3
Load on Bypass
Remote Status Alarm Panel
(RSAP) Interconnect Diagram
02-15-00
8
9
Dwg No.
U-23C012
Page
2033 C
1/1