Hitachi Vector Control with the SJ300 Inverter Application Note page 15

Vector control with the sj300 inverter

Advertisement

(3-2) Example of positioning under speed control mode (ASR) on SJ300 with SJ-FB
(3-2-1) Example of wiring
SJ300
f*
O
L
P24
ORT
SW
Material
M
Fig 4. Example of wiring
(3-2-2) Example of parameter settings
No.
Code
1
A044
Control method
2
P011
ppr of the encoder
3
P012
Control mode
4
P013
Mode of the pulse train input
5
P014
Stop position while orientation
6
P015
Speed while orientation
7
P016
Direction of orientation
8
P017
Orientation completion range
9
A001
Frequency command from;
10
A002
RUN command from;
11
F002
Acceleration time
F003
Deceleration time
Above are the main parameters to get position control. You have to adjust other parameters ([H***] parameters)
to get good performance.
© 2002 Hitachi America, Ltd.
M
EP5
Encoder
EG5
EAP
EAN
Example of 1024ppr line driver type encoder.
EBP
EBN
EZP
EZP
EZN
EZN
SW
Œ • Ž
n (Pulses)
Allowable
Required stop
deviation
position
n
(pulses)
0
Contents
In case of using external Z pulse
A
Belt is stopped at a certain position after passing a switch "SWZ".
Œ
Material M passes "SWO" point.
("SWO" turns ON which means an inverter is going into an
orientation mode.)
Belt speed will be an orientation speed (set in
[P015]), which means it is ready for positioning
Ž
After passing
SWZ
and stops at a certain position (set in [P017]).
Inverter gives out a "positioning completion signal ; POK" from
an intelligent output terminal.
Set value
05
V2 (closed loop control)
1024
Depends on the encoder
00
ASR (Speed command base on speed)
-
No need to care because this is ASR mode
*
When you want to stop at n pulses after
catching zero-pulse (after AZP/N is given);
[P014] = 4096 * n / [P011]
<Regardless the ppr of an encoder>
Stop at 300 pulses after Z pulse is given
for example;
[P014] = 4096 * 300 / 1024 = 1200
2.0
In case of 2.0Hz for orientation speed.
00
In case of FW rotation
*
Allowable deviation of positioning.
[P017] = n
01
Terminal (O-L input)
02
"RUN" key of the operator
3.0
As short as the system allows.
3.0
15
and wait for a Z pulse.
point, inverter starts counting the pulses
Remarks
* 4
o

Advertisement

loading