L300P Supplement

1. Added functions

RUN Permissive input signal for FW/REV [ROK]
・Assign function 49 (ROK) to an intelligent input terminal.
・When inverter is in the STOP mode, and the RUN Permissive
input signal [ROK] is "ON," the inverter can enter RUN mode via FW or RV signals
・When inverter is in the STOP mode, and the RUN Permissive input signal [ROK]
is "OFF," the FW and RV terminals are disabled, and the inverter cannot enter the RUN mode.
・When inverter is in the RUN mode and Permissive input signal [ROK] transitions from "ON" to "OFF," the
inverter will decelerate to a stop.
RUN Permissive (ROK)
FW / RV
Output frequency
Required Parameter Settings: parameter C001 to C005 (intelligent inputs 1 to 5)
Option Code Setting: RUN Permissive input signal for FW/REV = 49 [ROK]
Output signal for RUN Command Source [RMD]
・Assign function 27 [RMD] to an intelligent input terminal.
・ When the RUN command source is set to Remote operator,
(meaning A002 = 02), the RUN Command Source Output Signal [RMD] is "ON".
・When the RUN Command Source is NOT the Remote operator,
(A002 is NOT = 02) the RUN Command Source Output Signal [RMD] is "OFF".
Required Parameter Settings: parameter C021, C022, or C026 (Intelligent outputs 11 or 12, or
alarm relay)
Option Code Setting: RUN Command Source output signal = 27 [RMD]
OFF
ON
OFF
ON
1
Explanation of functions
Related Functions
C001-C005 : Intelligent input setting
Related Functions
C021-C022 : Intelligent output setting
C026
: Alarm relay output setting
A002
: RUN command source