Hitachi WJ200 Series Quick Reference Manual page 73

Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Func.
Name
Code
Logic output 2 operator
C147
Logic output 3 operand A
C148
Logic output 3 operand B
C149
Logic output 3 operator
C150
Input [1] response time
C160
Input [2] response time
C161
Input [3] response time
C162
Input [4] response time
C163
Input [5] response time
C164
Input [6] response time
C165
Input [7] response time
C166
Multistage speed/position
C169
determination time
Input Function Summary Table – This table shows all thirty-one intelligent input functions
at a glance. Detailed description of these functions, related parameters and settings, and
example wiring diagrams are in "Using Intelligent Input Terminals" on page 4-8.
Option
Terminal
Code
Symbol
00
FW
FORWARD Run/Stop
01
RV
Reverse Run/Stop
Multi-speed Select,
02
CF1 *1
Bit 0 (LSB)
Multi-speed Select,
03
CF2
Bit 1
Multi-speed Select,
04
CF3
Bit 2
Multi-speed Select,
05
CF4
Bit 3 (MSB)
06
JG
Jogging
07
DB
External DC braking
Set (select) 2nd Motor
08
SET
Data
"C" Function
Description
Applies a logic function to calculate
[LOG] output state,
Three options:
00...[LOG] = A AND B
01...[LOG] = A OR B
02...[LOG] = A XOR B
All the programmable functions
available for logic (discrete) outputs
except LOG1 to LOG3, OPO, no
Applies a logic function to calculate
[LOG] output state,
Three options:
00...[LOG] = A AND B
01...[LOG] = A OR B
02...[LOG] = A XOR B
Sets response time of each input
terminal, set range:
0 (x 2 [ms]) to 200 (x 2 [ms])
(0 to 400 [ms])
Set range is 0. to 200. (x 10ms)
Input Function Summary Table
Function Name
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Description
Inverter is in Run Mode, motor runs forward
Inverter is in Stop Mode, motor stops
Inverter is in Run Mode, motor runs reverse
Inverter is in Stop Mode, motor stops
Binary encoded speed select, Bit 0, logical 1
Binary encoded speed select, Bit 0, logical 0
Binary encoded speed select, Bit 1, logical 1
Binary encoded speed select, Bit 1, logical 0
Binary encoded speed select, Bit 2, logical 1
Binary encoded speed select, Bit 2, logical 0
Binary encoded speed select, Bit 3, logical 1
Binary encoded speed select, Bit 3, logical 0
Inverter is in Run Mode, output to motor runs at
jog parameter frequency
Inverter is in Stop Mode
DC braking will be applied during deceleration
DC braking will not be applied
The inverter uses 2nd motor parameters for
generating frequency output to motor
The inverter uses 1st (main) motor parameters
for generating frequency output to motor
71
Run
Defaults
Mode
Lnitial data
Units
Edit
00
00
01
00
1.
1.
1.
1.
1.
1.
1.
0.
ms

Advertisement

Table of Contents
loading

Table of Contents