5.5

Front Panel Settings

Listed below are the default settings of the primary UPS parameters.
Settings
1) O/P VOLT SET
100/110/115/120/127
(output voltage
208/220/230/240 Vac
set)
2) I/P FREQ SET
+/- 2%
(input frequency
+/- 5%
setting)
+/- 7%
3) I/P BYPASS
+/- 10%
SET
+10% -15%
(input bypass
+15% -20%
setting)
4) FREE RUN
ON/OFF
SET
5) HE MODE SET
ON/OFF
6) MANUAL
ON/OFF
BYPASS
Options
16
Default
120 V
120 V (FOR LV series)
230 V
230 V (FOR HV series)
+/- 5%
Input Frequency range in
Free Run mode
+10%
Input Voltage range when
-15%
Bypass mode is on
ON
If ON, enable UPS runs on
Asynchronous mode.
For example:
If input freq 55Hz
output freq stays at 60Hz.
If OFF, disable UPS runs on
synchronous mode.
For example:
If input freq 55Hz,
UPS will go to battery mode.
OFF
If ON, enable UPS runs in
High efficiency mode. The
unit will be in bypass mode
with 95% or higher
efficiency.
If OFF, the unit will be in the
online mode with 85%
efficiency.
OFF
If ON, enable UPS switch to
Bypass mode immediately.
Remarks