1-14. Optional Solenoid Valve Kit - Panasonic U-72MF1U9 Installation Instructions Manual

3way vrf system air conditioner
Hide thumbs Also See for U-72MF1U9:
Table of Contents

Advertisement

1-14. Optional Solenoid Valve Kit

Precautions on Installation of Solenoid Valve Kit
(1) Clean base metals thoroughly.
(2) Use proper ventilation to carry fumes away from the work area.
(3) Use a high quality silver based solder of at least 15 % silver.
(4) Heat the base materials broadly and uniformly.
(5) Take precautions not to overheat the device which could damage sensitive internal components.
(6) Insure compliance with all local codes!
CZ-P56HR1U
Part
Types and specifi cations of
Number
tubing connections
1
Gas tube: ID1/2"
2
Liquid tube: ID1/4"
3
Suspension hook
4
Liquid tube: ID3/8"
5
Suction tube: ID5/8"
6
Discharge tube: ID1/2"
7
Service panel
8
Base of control box
9
Terminal for power line
0
Terminal for communication line
!
Earth (M5 with washer)
@
Cover of control box
#
Relay kit
$
Cover of relay kit
5-25/32
7
9-13/32
• Specifications
7.500 ≤ Total capacity of indoor units (BTU/h) < 19.000
Compatibility
Power source
Single-phase AC 208–230V 60Hz (supplied by indoor unit)
Power input
33 W max.
Net weight
151.7 oz.
Accessories
Washer x 2
Hanging hook
M4 screw x 4
Tapping screw x 4
Wire holder
3-WAY connect wire
ACC-3WAY-AAB (Solenoid Valve Relay Kit)