Table 1 1 Compute enclosure PDU power options
Source voltage
Source/Circuit type
(nominal)
3–phase 60A
200–220 VAC
line-to-line
(phase-to-phase),
3–phase
50Hz/60Hz
3–phase 32A
220 VAC to 240 VAC
line-to-neutral 3–phase
50Hz/60Hz
Single-phase 63A
200V to 240V ac
50Hz/60Hz
Single-phase 30A
200–240 VAC
50Hz/60Hz
Table 12 IOX ac power specifications
Requirements
Nominal input voltage
Frequency range (minimum - maximum)
Number of phases
Rated line current
Maximum inrush current
Power factor correction
Ground leakage current
Table 13 IOX PDU power options
Source voltage
Source/Circuit type
(nominal)
Single-phase 30A
200-240 VAC
50Hz/60Hz
Single-phase 32A
200-240 VAC
50Hz/60Hz
Power receptacle
Plug or connector type
required
IEC 309 60A 3-Pole,
IEC 309 60A 3-Pole,
4 wire, Blue, 3.6m
4 wire, Blue
(1 1.8ft) power cord
IEC 309 32A 4-Pole,
IEC 309 32A 4-Pole,
5 wire, Red, 3.6m
5 wire, Red
(1 1.8ft) power cord
IEC 309 63A Single
IEC 309 63A Single
Phase Blue , 3.6m
Phase, Blue
(1 1.8ft) power cord
NEMA L6-30P Single
NEMA L6-30R Single
Phase, 3.6m (1 1.8ft)
Phase
power cord
Value
200–240 VAC
50–60 Hz
Single-phase
3 A
30 A for 20ms
0.97
1 mA
Power receptacle
Plug or connector type
required
NEMA L6-30P Single
NEMA L6-30R Single
Phase, 3.6m (1 1.8ft)
Phase
power cord
IEC 309 32A Single
IEC 309 32A Single
Phase Red, 3.6m
Phase, Red
(1 1.8ft) power cord
Number of power
cords required (per
enclosure leaving the
rack)
2
2
4
6
Number of power
cords required (per
enclosure leaving the
rack)
2
2
Electrical specifications