Bosch Plena Voice Alarm System Installation And Operation Manual page 137

Hide thumbs Also See for Plena Voice Alarm System:
Table of Contents

Advertisement

Plena Voice Alarm System
11 Interface to external control device(s) (option with the requirements)
Clause / Requirement
The VACIE may have provision for interfacing to
external control device(s) such as standardized
user interfaces required by local regulations. In
this case, the following shall apply:
a
b
c
NOTE - The external control devices should
comply with available local or national standards.
Bosch Security Systems B.V.
the interface shall allow only access level 1
and 2 functions;
the mandatory functions of the VACIE shall
not be overridden;
any short-circuit, interruption or earth fault in
the transmission path to the external
device(s) shall
not prevent the mandatory function of
the VACIE, and
be indicated on the VACIE, at least by
means of the general fault warning
indicator.
Installation and Operation manual
Compliance
Plena Voice Alarm System does not
support the Interface to external control
device(s) option.
9922 141 1037x (V2.16) | V0.6 | 2011.09
| en 137
Signature