Exhaust System Requirements - Frigidaire GCET1031FS4 Installation Instructions Manual

27" (69 cm) wide laundry center washer- dryer
Hide thumbs Also See for GCET1031FS4:
Table of Contents

Advertisement

Available languages

Available languages

EXHAUST
SYSTEM
REQ UIREMENTS
Use only 4 inch (10.2 cm) diameter (minimum) rigid or flexible
metal duct and approved vent hood which has a swing-out
damper(s) that open when the dryer is in operation. When the
dryer stops, the dampers automatically close to prevent drafts
and the entrance of insects and rodents. To avoid restricting the
outlet, maintain a minimum of 12 inches (30.5 cm) clearance
between the vent hood and the ground or any other obstruction.
The following
are specific requirements
for
proper and safe operation
of your dryer. Failure to follow
these instructions
can create excessive drying
times and
fire hazards.
Do not install a clothes dryer with flexible
plastic venting materials.
If your present system is made up
of plastic duct or metal foil duct, replace it with a rigid or flexible
metal duct. In Canada and the United States if metal (foil type)
duct is installed, it must be of a specific type identified by the
appliance manufacturer as suitable for use with clothes dryers
and in the United States must also comply with the Outline for
Clothes Dryer Transition Duct, UL standard 2158A.
Flexible
venting materials are known to collapse, be easily crushed and
trap lint. These conditions will obstruct clothes dryer airflow and
increase the risk of fire.
Ensure the present duct is free of
any lint prior to installing
dryer duct.
Do not allow
combustible
materials
(for
example:
clothing,
draperies/curtains,
paper) to come in
contact
with
exhaust
system.
The dryer MUST NOT be
exhausted into a chimney, a wall, a ceiling, or any concealed
space of a building which can accumulate lint, resulting in a fire
hazard.
Exceeding the length of duct pipe or number
of elbows allowed
in the "MAXIMUM
LENGTH" charts can
cause an accumulation of lint in the exhaust system. Plugging
the system could create a fire hazard, as well as increase drying
times.
Do not screen the exhaust ends of the vent
system, nor use any screws, rivets or other fastening means
that extend into the duct and catch lint to assemble the
exhaust system. Lint can become caught in the screen, on the
screws or rivets, clogging the duct work and creating a fire hazard
as well as increasing drying times. Use an approved vent hood
to terminate the duct outdoors, and seal all joints with duct
tape. All male duct pipe fittings MUSTbe installed downstream
with the flow of air.
Explosion hazard. Do not install the dryer
where gasoline or other flammables
are kept or stored. If
the dryer is installed in a garage, it must be a minimum of 18
inches (45.7 cm) above the floor. Failure to do so can result in
death, explosion, fire or burns. The exhaust system back pressure
MUST not exceed 0.6 inches (1.52 cm) of water column,
measured with an inclined manometer at the point the exhaust
connects to the dryer. The exhaust system should be inspected
and cleaned a minimum of every 18 months
with normal
usage. The more the dryer is used, the more often you should
check the exhaust system and vent hood for proper operation.
7
- Risk of Fire - A clothes
dr ,or must
be
exhausted
outdoors.
Do not exhaust dryer into a chimney, a
wall, a ceilinq, an attic, a crawl space or any concealed space
of a building
A clothes dryer produces combustible lint. If the
dryer is not exhausted outdoors, some fine lint will be expelled
into the laundry area. An accumulation of lint in any area of the
home can create a health and fire hazard. The dryermust
be
connected
to an exhaust
outdoors.
Regularly inspect the
outdoor exhaust opening and remove any accumulation of lint
around the outdoor exhaust opening and in the surrounding
area.
4
The maximum length of the exhaust system depends upon the
type of duct used, number of elbows and type of exhaust hood.
The maximum length for both rigid and flexible duct is shown in
the chart below.
EXHAUST DUCT LENGTHS
EXHAUST HOOD TYPE
Number
b-.
of 90°
',
"-,,
Turns
_--
j>
4"
10.2C
4)
o
I
2
3
o
I
2
3
Louvered
_25"
(6.
MAXIMUM
LENGTH OF 4-INCH (10.2 CM)
DIAMETER RIGID METAL DUCT
56 ft. (17.07 m)
46 ft. (14.02 m)
34ft. (10.36 m)
32 ft. (9.75 m)
42 ft. (12.8 m)
36 ft. (10.97
m)
28ft.
(8.53 m)
18ft.
(5.48 m)
MAXIMUM
LENGTH OF 4-INCH (10.2 CM)
DIAMETER
FLEXIBLE METAL DUCT
30ft. (9.14 m)
22 ft. (6.7 m)
16 ft. (4.88 m)
10 ft. (3.05 m)
22 ft. (6.7 m)
14ft. (4.27 m)
10 ft. (3.05 m)
5 ft. (1.5 m)