Cisco Network Convergence System 6000 Series Routers Site Planning Guide January 2014 Cisco Systems, Inc. www.cisco.com Cisco has more than 200 offices worldwide. Addresses, phone numbers, and fax numbers are listed on the Cisco website at www.cisco.com/go/offices. Text Part Number: OL-29236-02...
Page 2
OR ITS SUPPLIERS HAVE BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. Cisco and the Cisco logo are trademarks or registered trademarks of Cisco and/or its affiliates in the U.S. and other countries. To view a list of Cisco trademarks, go to this URL: www.cisco.com/go/trademarks.
C H A P T E R Basic Site and Installation Planning Aisle Spacing and Maintenance Access Floor Plan Drill Hole Template Power and Cooling Requirements System Console Cable Management Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
Page 4
A P P E N D I X System Product IDs A P P E N D I X Component Product IDs Line Card Product IDs Cosmetic Product IDs Accessory Product IDs Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
This document also describes the chassis, its components, site facilities requirements (such as floor space, weight requirements, receiving and staging), and installation to help you plan the site where the system will be installed. The Cisco product IDs (PIDs) are listed in Appendix B.
Page 6
SAVE THESE INSTRUCTIONS Statements using this symbol are provided for additional information and to comply with regulatory Warning and customer requirements. Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
Cisco technical documentation: http://www.cisco.com/en/US/docs/general/whatsnew/whatsnew.html Subscribe to the What’s New in Cisco Product Documentation as a Really Simple Syndication (RSS) feed and set content to be delivered directly to your desktop using a reader application. The RSS feeds are a free service, and Cisco currently supports RSS version 2.0.
Page 8
Cisco Network Convergence System 6000 Series Routers Site Planning Guide viii OL-29236-02...
Fabric Cards (FCs). The Cisco NCS 6008 chassis has an integrated rack and does not require an external rack. It is bolted to the facility floor. It contains its own power system consisting of six AC or DC power trays holding up to 18 AC Power Modules (PMs) or up to 24 DC PMs.
Chapter 1 Cisco NCS 6008 Chassis The Cisco NCS 6008 chassis is a highly scalable routing system with redundancy and reliability features that allow for nonstop operation even during service upgrades of equipment, with no single points of failure in hardware or software. The routing system has the potential to expand from a single-chassis to a multichassis configuration for even greater routing capacity.
Page 11
Rear View of the Cisco NCS 6008 Chassis 1 Power input feeds (AC or DC) 3 Card cage with slots for FCs and RP cards 2 Air exhaust plenum Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
Chassis Components Chassis Components Table 1-1 lists the main components of the Cisco NCS 6008 chassis. It identifies the components that are considered field replaceable units (FRUs), but where additional detail is useful, it identifies subassemblies that are not field replaceable.
The upper three AC power trays (0-2) are contained within power shelf 0 (PS0) and the lower three AC power trays (3-5) are contained within power shelf 1 (PS1). Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
Page 14
Six FC slots (left to right: 0, 1, 2, 3, 4, 5). The FC slots can be populated with FCs for standalone • chassis operation. See the “Component Product IDs” section on page B-1. Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
Chapter 1 Cisco NCS 6008 Chassis Overview of Site Planning Steps Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
Each AC PM requires its own single-phase AC input power feed. If you have 3-phase AC-Delta or AC-Wye at your equipment, a Cisco NCS 3-Phase AC PDU is required to convert a 3-phase AC input power feed to three single-phase AC input power feeds.
2-1). The grounding points are also referred to as Network Equipment Building System (NEBS) bonding and grounding points. Note These bonding and grounding receptacles satisfy the Telcordia NEBS requirements for bonding and grounding connections. Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
Page 19
Cisco; it is available from any commercial cable vendor. The cable should be sized according to local and national installation requirements. The DC Return of the Cisco NCS 6008 chassis should remain isolated from the system frame and chassis Caution (DC-I: Isolated DC Return).
An “allpole” separation of the power source is not required. The DC PM is an isolated DC/DC converter with no galvanic connection between “L+” and the chassis. In addition, the “L+” potentials of each PM are isolated from each other. Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
0.62 inches (15.75 mm). The terminal posts are centered 0.63 inches (16 mm) apart and are 1/4-20 thread. We recommend that you use a 90-degree angle, industry-standard, dual-hole, standard barrel compression lug (Figure 2-3). Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
Page 22
1.45 1.05±.04 Beveled wire entry .28±.01 Color coded .38±.01 barrel markings 1.74 REF Use local electrical codes for clearance requirements when using power lugs to ensure safe operation. Note Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
2-1, AC input power requirements are as follows: • Two separate and independent AC power sources are required to provide N+N power redundancy in case a power source fails. Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
The AC power system requires single-phase AC input power to each PM. If you have 3-phase AC Delta or AC Wye at your equipment, a Cisco NCS 3-phase AC PDU is required to convert 3-phase AC input power to single-phase AC input power (Cisco PID NCS-PDU-DELTA or NCS-PDU-WYE).
Page 25
Chapter 2 Power and Cooling AC Power Systems Figure 2-5 North America—AC Input Power Cord Figure 2-6 Europe—AC Input Power Cord Figure 2-7 United Kingdom—AC Input Power Cord Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
Page 26
The AS 3112 standard rates cord sets up to a maximum of 15 A, 250 VAC for the C21 plug. Therefore the building circuit breaker must be 15-A maximum. Installation of the Cisco NCS 6008 chassis must follow national and local electrical codes.
Page 27
Chapter 2 Power and Cooling AC Power Systems Figure 2-10 Japan—AC Input Power Cord Figure 2-11 Switzerland—AC Input Power Cord Figure 2-12 South Africa—AC Input Power Cord Cisco Network Convergence System 6000 Series Routers Site Planning Guide 2-11 OL-29236-02...
Page 28
Chapter 2 Power and Cooling AC Power Systems Figure 2-13 Israel—AC Input Power Cord Figure 2-14 China—AC Input Power Cord Figure 2-15 Brazil—AC Input Power Cord Cisco Network Convergence System 6000 Series Routers Site Planning Guide 2-12 OL-29236-02...
Converting 3-Phase AC to Single-Phase AC If you have 3-phase AC Delta or AC Wye input power at your equipment, a Cisco NCS 3-phase AC PDU is required to convert 3-phase AC Delta or AC Wye input power to single-phase AC input power that connects directly to the rear of each PM.
Page 30
AC Delta and Wye PDUs. Figure 2-17 AC Delta Power Cord Plug To AC outlet Figure 2-18 AC Wye Power Cord Plug To AC outlet Cisco Network Convergence System 6000 Series Routers Site Planning Guide 2-14 OL-29236-02...
Page 31
AC Delta PDU. The single AC Wye PDU is similar. Figure 2-19 Single AC PDU—Front and Rear 1 3-phase AC input cord 2 Single-phase AC output cords Cisco Network Convergence System 6000 Series Routers Site Planning Guide 2-15 OL-29236-02...
Chassis Cooling System The Cisco NCS 6008 chassis has two fan trays, with six variable-speed fans each, that cool the chassis card cages. Cool air flows in at the bottom front of the chassis, up through the chassis card cages, through the fans in the fan trays, and exhausts out the top rear of the chassis.
Chapter 2 Power and Cooling Facility Cooling Requirements The airflow volumes for a fully loaded Cisco NCS 6008 chassis are as follows: Chassis airflow: Up to 2500 cubic feet (70,792 liters) per minute • DC power system airflow: Up to 240 cubic feet (6796 liters) per minute •...
Page 34
Chapter 2 Power and Cooling Facility Cooling Requirements Cisco Network Convergence System 6000 Series Routers Site Planning Guide 2-18 OL-29236-02...
C H A P T E R System Specifications This appendix contains tables that list the specifications for the main components of the Cisco NCS 6008 chassis. Chassis Specifications, page 3-1 • Power Specifications, page 3-2 • Environmental Specifications, page 3-3 •...
–48 VDC or –60 VDC (tolerance range: –40 to –72 VDC) Input current 50 A max at –48 VDC 40 A max at –60 VDC 60 A at –40 VDC (maximum) Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
1. Short-term refers to a period of not more than 96 consecutive hours and a total of not more than 15 days in 1 year. This refers to a total of 360 hours in any given year, but no more than 15 occurrences during that 1-year period. Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
Page 38
System Specifications Regulatory, Compliance, and Safety Specifications Regulatory, Compliance, and Safety Specifications For information about the regulatory, compliance, and safety standards to which the Cisco NCS 6008 chassis conforms, see: Regulatory Compliance and Safety Information for the Cisco Network Convergence System 6000 Series Routers.
Page 39
Chapter 3 System Specifications Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
Page 40
Chapter 3 System Specifications Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
C H A P T E R Site Planning Considerations This chapter describes the general considerations for planning the installation of the Cisco NCS 6008 chassis. For complete instructions on mounting and securing the chassis, see the Cisco Network Convergence System 6000 Series Routers Unpacking, Moving, and Securing Guide.
Only the Cisco chassis lift dolly (“jumbo jack”) is recommended to move the chassis. The dolly • supplied by Cisco in support of the Cisco NCS 6008 chassis is the NCS 6008 Lift Dolly (PID NCS-LIFT). If you already have a CRS dolly, you can order PID NCS-LIFT-BRKT, which is the CRS Lift upgrade to NCS 6008.
Aisle Spacing and Maintenance Access Floor Plan The floor plan for the Cisco NCS 6008 chassis must include enough space to install the chassis and allow sufficient airflow for the system. The floor plan must also provide enough room to access chassis components for maintenance (for example, to remove fan trays, power components, cables, and air filters).
Excessive bending can damage interface cables. You must provide the LC cables from the Cisco NCS 6008 chassis to your facility interconnect. Because the type and number of components vary with each routing system site, plan these data cable runs in advance of the system installation.
Page 45
IEEE 1588 time RJ-45 port for STP cable Cat5 or better. synchronization port USB 2.0 port for external — storage Alarm port Shielded 15-pin D-SUB cable with male connector. Cisco Network Convergence System 6000 Series Routers Site Planning Guide OL-29236-02...
Site Planning Considerations Cisco Installation Services Cisco Installation Services Cisco or a Cisco partner can provide complete installation services, from planning to power up. For information about Cisco or Cisco partner installation services, consult Cisco Customer Advocacy. System Testing, Certification, and Warranties After the routing system has been installed, it must be tested and certified.
Estimated shipping date: Site ready date: Installation date: Site Location and Address Company name: Site address: Shipping address: Building or computer room access: Special instructions: Hours and days of operation: Cisco Network Convergence System 6000 Series Routers Hardware Installation Guide OL-29236-02...
Page 48
Is there someone on site during working hours to accept delivery of the materials? If not, list the times this person would be available. Cisco Network Convergence System 6000 Series Routers Hardware Installation Guide OL-29236-02...
Page 49
If so, describe them. Are there special requirements for power or power cables (for example, a different wire gauge)? If so, describe them. Cisco Network Convergence System 6000 Series Routers Hardware Installation Guide OL-29236-02...
Page 50
Will fiber jumpers be provided? What length of fiber jumper is required to complete the installation? What type of fiber connector is used at the site? If attenuation is required, will attenuators be provided? Cisco Network Convergence System 6000 Series Routers Hardware Installation Guide OL-29236-02...
A P P E N D I X System Product IDs This appendix provides information about the PIDs for the Cisco NCS 6008 chassis and its components. Component Product IDs, page B-1 • Line Card Product IDs, page B-3 •...
Page 52
Cisco NCS 100x10GE patch panel short reach NCS-PP-100X10-SR= (spare) 1. The PCM can be serviced in the field by Cisco personnel or with proper guidance from Cisco technical support. Cisco Network Convergence System 6000 Series Routers Hardware Installation Guide OL-29236-02...
Page 53
Front bottom grille NC6-GRILLE-FB= Front bottom grille Rear left and right doors NC6-DOOR-R= Rear left and right doors Exhaust air deflector NC6-GRILLE-R= Exhaust air deflector, rear of the chassis Cisco Network Convergence System 6000 Series Routers Hardware Installation Guide OL-29236-02...