Operation Panel - Mitsubishi Electric FR-A800 Safety Stop Function Instruction Manual

Safety stop function
Hide thumbs Also See for FR-A800:

Advertisement

Internal
Input terminal
Input
safety
power
circuit
status
OFF
Normal
ON
Normal
ON
Normal
OFF
Normal
OFF
ON
Fault
ON
Fault
ON
Fault
OFF
Fault
OFF
 ON: The transistor is conducted. OFF: The transistor is not conducted.
 When not using the safety stop function, short across terminals S1 and PC, S2 and PC, and SIC and SD to use the inverter.
(In the initial status, terminals S1 and PC, S2 and PC, and SIC and SD are respectively shorted with shorting wires.)
 If any of the protective functions shown in the following table is activated, the terminal SO turns OFF.
Error definition
Option fault.
Communication option fault
Parameter storage device fault
Retry count excess
Parameter storage device fault
Operation panel power supply short circuit/
RS-485 terminals power supply short
circuit
 If the internal safety circuit is operated normally, the terminal SO remains ON until E.SAF is displayed, and the terminal SO
turns OFF when E.SAF is displayed.
 SA is displayed when the terminals S1 and S2 are identified as OFF due to the internal safety circuit failure.
 If another fault occurs at the same time as E.SAF, the other fault can be displayed.
 If another warning occurs at the same time as SA, the other warning can be displayed.
NOTE
• The response time from safety stop signal input to drive shutoff (safe state) is faster than 8ms.
• Hold the ON or OFF status for 2ms or longer to input signal to terminal S1 or S2.
Signal input shorter than 2ms is not recognized.
Table.3 Truth table of safety related signals
Output
,


terminal
S1
S2
SO
OFF
ON
ON

OFF
OFF
ON
OFF
OFF
ON

ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
Operation panel indication
E.OPT
E.OP1
E.PE
E.RET
E.PE2
E.CTE
Inverter running status
Output shutoff (Safe state)
Drive enabled
Output shutoff (Safe state)

Output shutoff (Safe state)

Output shutoff (Safe state)
Output shutoff (Safe state)
Output shutoff (Safe state)
Output shutoff (Safe state)
Output shutoff (Safe state)
Error definition
24 VDC power fault
Safety circuit fault
Overspeed occurrence
CPU fault
Internal circuit fault
INSTALLATION AND WIRING

Operation panel

indication
E.SAF
SA


Not
Not
displayed
displayed
Not
Not
displayed
displayed
Displayed
Displayed
Displayed
Displayed
Not
Displayed
displayed
Not
Displayed
displayed
Displayed
Displayed
Displayed
Displayed
Displayed
Displayed
Operation panel indication
E.P24
E.SAF
E.OS
E.CPU
E.5 to E.7
E.13

5