Toshiba RAV-SM402MUT-E Service Manual

Split type digital inverter indoor unit
Hide thumbs Also See for RAV-SM402MUT-E:

Advertisement

Quick Links

SERVICE MANUAL

AIR-CONDITIONER
RAV-SM402MUT-E
RAV-SM452MUT-E
RAV-SM562MUT-E
This Service Manual describes contents of the new indoor unit.
For the outdoor unit, refer to the Service Manual with FILE NO. A05-001 and A07-003.
R410A
SPLIT TYPE
<DIGITAL INVERTER>
INDOOR UNIT
PRINTED IN JAPAN, Jun, 2008 ToMo
FILE NO. A06-005
Revised: Jun, 2008

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba RAV-SM402MUT-E

  • Page 1: Service Manual

    Revised: Jun, 2008 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE <DIGITAL INVERTER> INDOOR UNIT RAV-SM402MUT-E RAV-SM452MUT-E RAV-SM562MUT-E This Service Manual describes contents of the new indoor unit. For the outdoor unit, refer to the Service Manual with FILE NO. A05-001 and A07-003. R410A...
  • Page 2: Table Of Contents

    Adoption of New Refrigerant This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer. WARNING Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to have a service person do it.
  • Page 3 7. CONTROL BLOCK DIAGRAM ..............38 7-1. Indoor Control Circuit ..................38 7-2. Control Specifications ..................39 7-3. Indoor Print Circuit Board ................46 8. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS... 47 8-1. Indoor Control Circuit ..................47 9. TROUBLESHOOTING ................49 9-1.
  • Page 4: Specifications

    1. SPECIFICATIONS 1-1. Indoor Unit 1-1-1. 4-Way Air Discharge Cassette Type <Single type> Indoor unit RAV- SM402MUT-E SM452MUT-E SM562MUT-E Model Outdoor unit RAV- SP404AT(Z, ZG)-E SP454AT(Z, ZG)-E SP562AT(Z, ZG)-E Cooling capacity (kW) Heating capacity (kW) Power supply 1 phase 230V (220 – 240V) 50Hz Running current 5.05 –...
  • Page 5 <Single type> Indoor unit RAV- SM562MUT-E SM562MUT-E Model Outdoor unit RAV- SM562AT-E SM563AT-E Cooling capacity (kW) Heating capacity (kW) Power supply 1 phase 230V (220 – 240V) 50Hz Running current 7.02 – 7.75 7.02 – 7.75 Power consumption (kW) 1.61 1.61 Power factor Cooling...
  • Page 6 <Twin type> Indoor unit 1 RAV- SM562MUT-E SM562MUT-E Model Indoor unit 2 RAV- SM562MUT-E SM562MUT-E Outdoor unit RAV- SP1102AT(Z, ZG)-E SP1104AT(Z, ZG)-E Cooling capacity (kW) 10.0 10.0 Heating capacity (kW) 11.2 11.2 Indoor unit Power supply 1 phase 230V (220 – 240V) 50Hz Running current 10.31 –...
  • Page 7 <Twin type> Indoor unit 1 RAV- SM562MUT-E SM562MUT-E Model Indoor unit 2 RAV- SM562MUT-E SM562MUT-E Outdoor unit RAV- SM1102AT-E SM1103AT-E Cooling capacity (kW) 10.0 10.0 Heating capacity (kW) 11.2 11.2 Indoor unit Power supply 1 phase 230V (220 – 240V) 50Hz Running current 14.96 –...
  • Page 8 <Triple type> Indoor unit 1 RAV-SM562MUT-E Indoor unit 2 RAV-SM562MUT-E Model Indoor unit 3 RAV-SM562MUT-E Outdoor unit RAV-SM1603AT-E Cooling capacity (kW) 14.0 Heating capacity (kW) 16.0 Indoor unit Power supply 1 phase 230V (220 – 240V) 50Hz Running current 23.88 – 21.89 Power consumption (kW) 4.99...
  • Page 9: Outdoor Unit

    1-2. Outdoor Unit <Super Digital Inverter> Model name Outdoor unit RAV-SP 562AT(Z)(ZG)-E 802AT(Z)(ZG)-E 1104AT(Z)(ZG)-E 1404AT(Z)(ZG)-E 1 phase 230V (220 – 240V) 50Hz Power supply (Power exclusive to outdoor is required.) Type Hermetic compressor Compressor Motor (kW) 3.75 3.75 Pole Refrigerant charged (kg) Refrigerant control Pulse motor valve...
  • Page 10 Model name Outdoor unit RAV-SP404AT(Z)(ZG)-E RAV-SP454AT(Z)(ZG)-E 1 phase 230V (220 – 240V) 50Hz Power supply (Power exclusive to outdoor is required.) Type Hermetic compressor Compressor Motor (kW) Pole Refrigerant charged (kg) Refrigerant control Pulse motor valve Standard length Max. total length Inter Additional refrigerant charge 20g/m (21m to 30m)
  • Page 11: Operation Characteristic Curve

    1-3. Operation Characteristic Curve <Digital Inverter> RAV-SM562MUT-E / RAV-SM562AT-E <Cooling> <Heating> • Conditions • Conditions Indoor : DB27˚C/WB19˚C Indoor : DB20˚C Outdoor : DB35˚C Outdoor : DB7˚C/WB6˚C Air flow : High Air flow : High Pipe length : 7.5m Pipe length : 7.5m 230V 230V 60 70 80...
  • Page 12 <Super Digital Inverter> RAV-SP404AT-E, RAV-SP404ATZ-E, RAV-SP404ATZG-E RAV-SP454AT-E, RAV-SP454ATZ-E, RAV-SP454ATZG-E <Cooling> <Heating> SP45 SP45 SP45 SP45 SP45 SP45 SP40 SP40 SP40 SP40 SP40 SP40 • Conditions • Conditions Indoor : DB27˚C/WB19˚C Indoor : DB20˚C Outdoor : DB35˚C Outdoor : DB7˚C/WB6˚C Air flow : High Air flow : High Pipe length : 7.5m Pipe length : 7.5m...
  • Page 13: Capacity Variation Ratio According To Temperature

    1-4. Capacity Variation Ratio According to Temperature RAV-SP404AT-E, RAV-SP404ATZ-E, RAV-SP404ATZG-E RAV-SP454AT-E, RAV-SP454ATZ-E, RAV-SP454ATZG-E <Cooling> <Heating> • Conditions • Conditions Indoor : DB27˚C/WB19˚C Indoor : DB20˚C Indoor air flow : High Indoor air flow : High Pipe length : 7.5m Pipe length : 7.5m 32 33 34 35 36 37 38 39 40 41 42 43 -12 -10 -8 -6 -4 -2 0 2 4 8 10...
  • Page 14: Construction Views (External Views)

    2. CONSTRUCTION VIEWS (EXTERNAL VIEWS) 2-1. Indoor Unit 595 to 660 Ceiling open dimension 1000 or more Check port 450) Check port 450) Check port 450) Obustacle Drain-up standing-up size Indoor unit 1000 or more Bottom face of ceiling Note) As ABS is used for the drain discharge port of the main unit, the vinyl chlor paste cannot be used.
  • Page 15 RBC-TWP30E2, RBC-TWP50E2 (Simultaneous Twin) Inner diameter Ø C Inner Inner diameter Ø D diameter Ø D Model (RBC-) Liquid side Ø9.5 Ø6.4 TWP30E2 Gas side Ø15.9 Ø12.7 Liquid side Ø9.5 Ø9.5 TWP50E2 Gas side Ø15.9 Ø15.9 – 15 –...
  • Page 16 RBC-TRP100E (Simultaneous Triple) <Gas side> Header assembly Inner diameter Ø15.9 <Liquid side> Branch pipe assembly Inner diameter Ø9.52 Insulator Gas side socket Liquid side socket Ø15.9 Ø12.7 Ø9.5 Ø6.4 Ø15.9 Ø25.4 Ø9.5 Ø12.7 (External (External (External (External diameter) diameter) diameter) diameter) 3 pcs.
  • Page 17: Systematic Refrigerating Cycle Diagram

    3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM 3-1. Indoor Unit • Single type Distributor Indoor unit (Combination of one indoor unit and (Strainer TCJ sensor one outdoor unit) incorporated) Air heat exchanger TC sensor Refrigerant pipe Refrigerant pipe at liquid side at gas side Outer diameter Ø6.4 Outer diameter Ø12.7 Heating time...
  • Page 18: Outdoor Unit

    3-2. Outdoor Unit RAV-SM562MUT-E / RAV-SP562AT-E Packed valve Packed valve Outer dia. Ø12.7 Outer dia. Ø6.4 Modulating Strainer TS sensor (PMV) (SKV-18D26) TO sensor TD sensor Strainer 4-way valve Capillary Muffler (STF-0213Z) sensor Accumulator Ø3×Ø2× (1500cc) Ø25 × L210 L530 Heat exchangerØ8 Ø25 ×...
  • Page 19 RAV-SM562MUT-E / RAV-SM562AT-E Packed valve Packed valve Outer dia. Ø12.7 Outer dia. Ø6.4 TS sensor (Pulse Motor Valve) (CAM-B30YGTF-1) TO sensor 2-step muffler Ø19 .05 × 200L TD sensor Strainer 4-way valve sensor (STF-0108Z) Muffler Heat exchanger Ø8 ripple, Ø19 × L160 2 rows, 14 steps FP1.3 flat fin Distributor...
  • Page 20 RAV-SM402MUT-E / RAV-SP404AT-E RAV-SM454MUT-E / RAV-SP454AT-E Packed valve Packed valve Outer dia. Ø12.7 Outer dia. Ø6.4 TS sensor (Pulse Motor Valve) (CAM-B30YGTF-2) TO sensor 2-step muffler Ø19.05 × 200L TD sensor Strainer 4-way valve (STF-0108Z) sensor Muffler Heat exchanger Ø8 ripple, Ø19 ×...
  • Page 21: Wiring Diagram

    4. WIRING DIAGRAM 4-1. Indoor Unit 4-1-1. Compact 4-way Cassette Type Connection interface (option) (EXCT) 1 2 3 CN50 CN51 CN34 (WHI) (RED) (RED) CN104 CN102 CN101 CN80 CN73 CN70 (YEL) (RED) (BLK) (GRN) (RED) (WHI) P.C. Board MCC-1402 CN40 (BLU) CN33 CN60...
  • Page 22 • Single type • Twin type Power supply 220-240V Power supply 220-240V Single phase 50Hz Single phase 50Hz Outdoor unit Outdoor unit 1 2 3 1 2 3 1 2 3 Indoor unit 1 2 3 1 2 3 Indoor unit Indoor unit Earth No.1 (Master)
  • Page 23: Specifications Of Electrical Parts

    5. SPECIFICATIONS OF ELECTRICAL PARTS 5-1. Indoor Unit Parts name Type Specifications Fan motor (for indoor) SWF-230-60-1R Output (Rated) 60 W, 220–240 V Thermo. sensor (TA-sensor) 155 mm 10 kΩ at 25°C Heat exchanger sensor (TCJ-sensor) Ø6 mm, 1200 mm 10 kΩ...
  • Page 24: Refrigerant R410A

    6. REFRIGERANT R410A This air conditioner adopts the new refrigerant HFC 6) When an air conditioning system charged with a (R410A) which does not damage the ozone layer. large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, The working pressure of the new refrigerant R410A even when refrigerant leaks, its concentration is 1.6 times higher than conventional refrigerant...
  • Page 25 Table 6-2-1 Thicknesses of annealed copper pipes Thickness (mm) Nominal diameter Outer diameter (mm) R410A 6.35 0.80 0.80 9.52 0.80 0.80 12.70 0.80 0.80 15.88 1.00 1.00 2) Joints For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm.
  • Page 26 c) Insertion of Flare Nut Flare processing dimensions differ according to the type of flare tool. When using a conven- d) Flare Processing tional flare tool, be sure to secure “dimension Make certain that a clamp bar and copper A” by using a gauge for size adjustment. pipe have been cleaned.
  • Page 27 Table 6-2-6 Flare and flare nut dimensions for R22 Dimension (mm) Nominal Outer diameter Thickness Flare nut width diameter (mm) (mm) (mm) 6.35 9.52 13.0 13.5 12.70 16.2 16.0 12.9 15.88 19.4 19.0 16.0 19.05 23.3 24.0 19.2 Fig. 6-2-2 Relations between flare nut and flare seal surface 2) Flare Connecting Procedures and Precautions a) Make sure that the flare and union portions do not have any scar or dust, etc.
  • Page 28: Tools

    6-3. Tools 6-3-1. Required Tools The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened. The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc.
  • Page 29: Recharging Of Refrigerant

    6-4. Recharging of Refrigerant When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps. Recover the refrigerant, and check no refrigerant remains in the equipment. When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s Connect the charge hose to packed valve service...
  • Page 30: Brazing Of Pipes

     Be sure to make setting so that liquid can be charged. ‚ When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down. It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
  • Page 31 2) Characteristics required for flux 6-5-3. Brazing • Activated temperature of flux coincides with the As brazing work requires sophisticated techniques, brazing temperature. experiences based upon a theoretical knowledge, it must be performed by a person qualified. • Due to a wide effective temperature range, flux is hard to carbonize.
  • Page 32: Tolerance Of Pipe Length And Pipe Head

    6-6. Tolerance of Pipe Length and Pipe Head n Twin system Total length (L + a or L + b) 50 m Pipe length Branch pipe length (a, b) 15 m (one way) Maximum difference between indoor units 10 m Refrigerant pipe (b –...
  • Page 33 n Triple system Total length (L + a, L +b, L+c) 50 m Pipe length Branch pipe length (a, b, c) 15 m (one way) Maximum difference between indoor units 10 m Refrigerant pipe (|a – b|, |b – c|, |c – d|) specification Between indoor units ( ∆...
  • Page 34: Additional Refrigerant Amount

    6-7. Additional Refrigerant Amount n Twin system <Formula for Calculating Additional Refrigerant Amount> Do not remove the refrigerant even if the additional refrigerant amount becomes minus result as a result of calculations by the following formula and operate the air conditioner as it is. Additional refrigerant amount (kg) = Main piping additional refrigerant amount (kg) + Branch piping additional refrigerant amount (kg) α...
  • Page 35 n Triple system <Formula for Calculating Additional Refrigerant Amount> Do not remove the refrigerant even if the additional refrigerant amount becomes minus result as a result of calculations by the following formula and operate the air conditioner as it is. Additional refrigerant amount (kg) = Main piping additional refrigerant amount (kg) + Branch piping additional refrigerant amount (kg) α...
  • Page 36: Piping Materials And Sizes

    6-8. Piping Materials and Sizes n Twin system Use copper tube of Copper and copper alloy seamless pipes and tubes, with 40mg/10m or less in the amount of oil stuck on inner walls of pipe and 0.8mm in pipe wall thickness for diameters for diameters 6.4, 9.5 and 12.7mm and 1.0mm, for diameter 15.9mm.
  • Page 37: Branch Pipe

    6-9. Branch Pipe n Twin system Now the refrigerant pipe is installed using branch pipes supplied as accessories. • Bend and adjust the refrigerant piping so that the branch pipes and pipe after branching become horizontal. • Fix the branch pipes onto a wall in a ceiling or onto a column. •...
  • Page 38: Control Block Diagram

    7. CONTROL BLOCK DIAGRAM 7-1. Indoor Control Circuit Main (Sub) master remote controller Weekly timer *1 Connection Interface is attached to master unit. Display Function setup Function setup (In case of group control operation) driver *2 Weekly timer is not connectable to Display Display the sub remote controller.
  • Page 39: Control Specifications

    7-2. Control Specifications Item Outline of specifications Remarks When power 1) Distinction of outdoor units supply is reset When the power supply is reset, the outdoors are distinguished, and control is exchanged according to the distinguished result. 2) Setting of speed of the indoor fan/setting whether to adjust air direction or not.
  • Page 40 Item Outline of specifications Remarks Room 1) Adjustment range Remote controller setup tem- temperature perature (°C) control COOL/ Heating Auto operation operation Wired type 18 to 29 18 to 29 18 to 29 Wireless type 18 to 30 16 to 30 17 to 27 2) Using the item code 06, the setup temperature in Shift of suction tempera-...
  • Page 41 Item Outline of specifications Remarks <HEAT> Air speed Ta (˚C) selection (Continued) L(L) (-0.5) –1.0 L(H) H(H) (+0.5) +1.0 (HH) (+1.0) +2.0 (+1.5) +3.0 (HH) (+2.0) +4.0 Value in the parentheses indicates one when thermostat of the remote controller works. Value without parentheses indicates one when thermostat of the body works.
  • Page 42 Item Outline of specifications Remarks Cool air 1) In heating operation, the indoor fan is controlled based In D or E zone, the priority discharge on the detected temperature of Tc sensor or Tcj sensor. is given to setup of air preventive As shown below, the volume exchange.
  • Page 43 Item Outline of specifications Remarks Drain pump control 1) In cooling operation (including Dry operation), the drain pump is usually operated. 2) If the float switch operates while drain pump operates, the compressor stops, the drain pump continues the operation, and a check code is output.
  • Page 44 Item Outline of specifications Remarks <In case of wired remote controller> Frequency fixed operation 1. When pushing [CHECK] button for 4 seconds or more, (Test run) [TEST] is displayed on the display screen and the mode enters in Test run mode. 2.
  • Page 45 Item Outline of specifications Remarks Central control 1) Setting at the central controller side enables to select mode selection the contents which can be operated on the remote controller at indoor unit side. 2) RBC-AMT31E, RBC-AMT32E [Last push priority] : (No display) The operation contents can be selected from both remote controller and central controller of the indoor...
  • Page 46: Indoor Print Circuit Board

    Microcomputer operation LED Filter/Option error input EEPROM Connection interface DC fan output Indoor/Outdoor inter-unit cable Optional power supply Remote controller power supply LED DC fan return Drain pump output Float SW Fan output TCJ sensor EXCT HA (T10) TA sensor Remote controller inter-unit cable Used for DISP...
  • Page 47: Circuit Configuration And Control Specifications

    8. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS 8-1. Indoor Control Circuit 8-1-1. Outline of Main Controls 1. Pulse Motor Valve (P.M.V.) control 1) PMV is controlled with 50 to 500 pulses during operation, respectively. 2) In cooling operation, PMV is controlled with the temperature difference between TS sensor and TC sensor. 3) In heating operation, PMV is controlled with the temperature difference between TS sensor and TE sensor.
  • Page 48 8-1-2. Indoor P.C. Board Optional Connector Specifications Connector Function Specifications Remarks Option output CN60 DC12V (COM) Defrost output ON during defrost operation of outdoor unit Thermo. ON output ON during Real thermo-ON (Comp ON) Cooling output ON when operation mode is in cooling system (COOL, DRY, COOL in AUTO cooling/heating) Heating output ON when operation mode is in heating system...
  • Page 49: Troubleshooting

    9. TROUBLESHOOTING 9-1. Summary of Troubleshooting <Wired remote controller type> 1. Before troubleshooting 1) Required tools/instruments – • screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch • Tester, thermometer, pressure gauge, etc. 2) Confirmation points before check a) The following operations are normal.
  • Page 50 <Wireless remote controller type> 1. Before troubleshooting 1) Required tools/instruments – • screwdrivers, spanners, radio cutting pliers, nippers, etc. • Tester, thermometer, pressure gauge, etc. 2) Confirmation points before check a) The following operations are normal. 1. Compressor does not operate. •...
  • Page 51: Check Code List

    9-2. Check Code List Error mode detected by indoor and outdoor units ¥ ¡ : Flash, : Go on, : Go off Wireless sensor Wired remote Diagnostic function lamp display controller Judgment and measures Status of Cause of operation Condition Operation Timer Ready...
  • Page 52 ¥ ¡ : Flash, : Go on, : Go off Wireless sensor Wired remote Diagnostic function lamp display controller Judgment and measures Status of Cause of operation Condition Operation Timer Ready Check code air conditioner ¥ ¥ Unset indoor capacity Displayed when 1.
  • Page 53 Error mode detected by remote controller ¥ ¡ : Flash, : Go on, : Go off Wireless sensor Wired remote Diagnostic function lamp display controller Judgment and measures Status of Cause of operation Condition Operation Timer Ready Check code air conditioner No communication with master indoor unit Remote controller power error, Defective indoor EEPROM •...
  • Page 54: Error Mode Detected By Led On Outdoor P.c. Board

    9-3. Error Mode Detected by LED on Outdoor P.C. Board RAV-SP562AT-E only <SW801: LED display in bit 1, bit 2 OFF> • When multiple errors are detected, the latest error is displayed. ¡ • When LED display is (Go on), there is the main cause of trouble on the objective part of control at CDB side and the unit stops.
  • Page 55: Troubleshooting Procedure For Each Check Code

    9-4. Troubleshooting Procedure for Each Check Code 9-4-1. Check Code [E01 error] Correct inter-unit cable of remote controller. Is inter-unit cable of A and B normal? Is there no disconnection Correct connection of connector. or contact error of connector on harness Check circuit cables.
  • Page 56 [E04 error] Does outdoor unit operate? Is setup of group address correct? Check item code [14]. Are 1, 2, 3 inter-unit cables normal? Correct inter-unit cable. Are connections from connectors of inter-terminal blocks (1, 2, 3) Correct connection of connector. of indoor/outdoor units normal? Check indoor P.C.
  • Page 57 [E10 error] Check indoor control P.C. board (MCC-1402). Defect → Replace [E18 error] Correct inter-unit cable of remote controller. Is inter-unit cable of A and B normal? Is there no disconnection Correct connection of connector. or contact error of connector on harness Check circuit cables.
  • Page 58 [L20 error] Correct cable connection Are cable connections to communication line U3, U4 normal? Are not multiple same central Correct central control network address. control network addresses connected? Check central controller (including connection interface) indoor P.C. board. Defect → Replace. [L30 error] Check indoor P.C.
  • Page 59 [P12 error] <Only for 4-way air discharge cassette type models> Turn off the power. Are not there connections errors or Correct connection of connector. disconnection on connectors CN333 and CN334 of indoor unit P.C. board (MCC-1402)? Remove connectors CN333 and CN334 of indoor unit P.C.
  • Page 60 [P22 error] Are connections of CN301 and CN300 of P.C. board correct? ∗ CN301, CN303 Does the fan rotate without trouble when handling the fan with hands under condition of removing CN301 and CN300 from P.C. board? The status that the resistance values between leads below are 50 to 80Ω...
  • Page 61 [P19 error] Is voltage applied Is operation of to 4-way valve coil terminal 4-way valve normal? in heating operation? Is flow of refrigerant Check 4-way valve by electron expansion Defect → Replace valve normal? Check and replace electron expansion valve. Is circuit cable normal? Are characteristics of TC sensor resistance...
  • Page 62 [F01 error] Is connection of TCJ sensor connector Correct connection of connector. (Indoor P.C. board CN102) normal? Are characteristics of Replace TCJ sensor. TCJ sensor resistance value normal? ∗ Refer to Characteristics-2. Check indoor P.C. board (MCC-1402). Defect → Replace [P26 error] Improve the power supply line.
  • Page 63 [P29 error] Check and correct circuit cabling Are connections of cable/connector normal? such as cabling to compressor. Is compressor normal? Compressor error → Replace Is not earthed? Is not winding shorted? Compressor error → Replace (Is resistance between windings 0.6 to 1.2Ω?) Compressor error →...
  • Page 64 [F06 error] Are connections of Correct connection of connector. TE/TS sensor connectors of CDB CN604/CN605 normal? ∗ (For RAV-SM562AT-E, RAV-SM563AT-E, RAV-SP404AT-E, RAV-SP454AT-E, CN600 TE sensor and CN603 TS sensor) Are characteristics of TE/TS sensor Replace TE and TS sensors. resistance values normal? Check CDB.
  • Page 65 [L29 error] In the case of SUPER DIGITAL INVERTER Are connections of CDB CN800 and CDB IPDU CN06 Correct connection of connector. connectors normal? Check cabling between IPDU Was the error just after Are cabling/connector normal? power ON determined? and CDB and connector. IPDU P.C.
  • Page 66 [P03 error] Is protective control such as Are connections of Correct the cabling and discharge temprelease control normal? cable/connector normal? connection of connector. Check parts. Defect → Replace Check and correct the charged Is charged refrigerant amount normal? refrigerant amount. Improve and delete the cause Is not abnormal overload? Are characteristics of...
  • Page 67 [P04 error] Is high-voltage protective operation by TE sensor normal? Is connection of Correct connection of cabling connector. cabling connector normal? Check TE sensor. Defect → Replace Does cooling outdoor fan normally operate? Correct connection Is connection of of connector. connector normal? Is fan motor normal? Replace fan motor.
  • Page 68 [C06 error] (Central controller) Is U3, U4 communication line normal? Correct communication line. Are connections between connectors CN51 of connection interface P.C. board and Correct connection of connector. connectors CN51 of indoor P.C. board normal? Check connections of A, B terminal blocks. Is A, B communication line normal? Correct communication line of remote controller.
  • Page 69 [E03 error] (Master indoor unit) [E03 error] is detected when the indoor unit cannot receive a signal sent from the main remote controller (and central controller). In this case, check the communication cables of the remote controllers A and B, the central control system X and Y.
  • Page 70 9-4-2. Relational Graph of Temperature Sensor Resistance Value and Temperature TA sensor TC, TCJ sensor Caracteristics-2 Caracteristics-1 Resistance Resistance –10 Temperature [˚C] Temperature [˚C] TE, TO, TS sensor Caracteristics-3 Resistance Resistance (10˚C or higher) (10˚C or lower) Temperature [˚C] TD sensor Caracteristics-4 Resistance Resistance...
  • Page 71: Replacement Of Service Indoor P.c. Board

    10. REPLACEMENT OF SERVICE INDOOR P.C. BOARD [Requirement when replacing the service indoor P.C. board assembly] In the non-volatile memory (Hereinafter said EEPROM, IC10) installed on the indoor P .C. board before replace- ment, the type and capacity code exclusive to the corresponding model have been stored at shipment from the factory and the important setup data such as system/indoor/group address set in (AUTO/MANUAL) mode or setting of high ceiling selection have been stored at installation time.
  • Page 72 H1 Readout of the setup data from EEPROM (Data in EEPROM contents, which have been changed at the local site, are read out together with data in EEPROM set at shipment from the factory.) TEST 1. Push , and buttons of the remote controller at the same time for 4 seconds or more. (Corresponded with No.
  • Page 73 r3 Writing of the setup contents to EEPROM (The contents of EEPROM installed on the service P .C. board have been set up at shipment from the factory.) TEST 1. Push , and buttons of the remote controller at the same time for 4 seconds or more. (Corresponded with No.
  • Page 74 * Initial setup value of EEPROM installed on the service P .C. board Indoor unit capacity Item code [11] Setup data Type Abbreviated name 0006 RAV-SM402MUT-E 0007 Compact 4-way cassette RAV-SM452MUT-E 0009 RAV-SM562MUT-E * Initial setup value of EEPROM installed on the service P .C. board...
  • Page 75: Setup At Local Site And Others

    11. SETUP AT LOCAL SITE AND OTHERS 11-1. Indoor Unit 11-1-1. Test Run Setup on Remote Controller <Wired remote controller> TEST 1. When pushing button on the remote controller for 4 seconds or more, “TEST” is displayed on LC display. ON / OFF Then push button.
  • Page 76 <In case of wireless remote controller> Procedure Description Turn on power of the air conditioner. The operation is not accepted for 5 minutes when power has been turned on at first time after installation, and 1 minute when power has been turned on at the next time and after. After the specified time has passed, perform a test operation.
  • Page 77 Item No. (DN) table (Selection of function) Item Description At shipment Filter sign lighting time 0000 : None 0002 for D.I. and S.D.I. 0002 : 2500H (4-Way/Duct/Ceiling Type) models Dirty state of filter 0000 : Standard 0000 : Standard 0001 : High degree of dirt (Half of standard time) Central control address 0001 : No.1 unit 0064 : No.64 unit...
  • Page 78 11-1-2. Wiring and Setting of Remote Controller Control 2-remote controller control <Wired remote controller> (Controlled by 2 remote controllers) How to set wired remote controller as sub remote controller This control is to operate 1 or multiple indoor units are operated by 2 remote controllers. Change DIP switch inside of the rear side of the (Max.
  • Page 79 11-1-3. Monitor Function of Remote Controller Switch n Calling of sensor temperature display <Contents> Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service monitor mode from the remote controller. <Procedure> TEST Push buttons simultaneously for 4 seconds to call the service monitor mode.
  • Page 80 n Calling of error history <Contents> The error contents in the past can be called. <Procedure> TEST Push buttons simultaneously for 4 seconds or more to call the service check mode. TEMP. ON / OFF Service Check goes on, the item code 01 is displayed, and then the content of the latest alarm is displayed.
  • Page 81 n Indoor unit power-ON sequence Power ON • The unit without power feed waits entirely → Waiting status is released by system start • Reboot when power is fed on the way <By feed unit> <Automatic address judgment> Not normal 3 minutes elapse Gr construction check Normal...
  • Page 82: Setup At Local Site / Others

    11-2. Setup at Local Site / Others Model name: TCB-PCNT30TLE2 and TCB-PX30MUE 11-2-1. TCC-LINK Adapter (For TCC-LINK Central Control) 1. Function This model is an optional P .C. board to connect the indoor unit to TCC-LINK (Central controller). 2. Microprocessor Block Diagram Indoor unit Central controller...
  • Page 83 3) Install the spacers and P .C. board that are attached to TCB-PCNT30TLE2, on the Connection Interface Kit. Spacers (Attached to the TCB-PCNT30TLE2) P .C. board (Attached to the TCB-PCNT30TLE2) 4) Remove the 2P terminal block for the communication cable of the electric parts box on the unit, and then replace with the attached 4P terminal block for the communication wires.
  • Page 84 6) Setting for Central Control For Central Control setting, refer to the Installation Manual of the TCB-PCNT30TLE2. 7) After the installation work has been completed, install the Connection Interface Kit cover to the Connec- tion Interface Kit tightened with the two screws (4 ×10). Screw (4 ×10) Connection Hook of...
  • Page 85: Wiring Specifications

    5. Wiring Specifications • Use 2-core with no polar wire. No. of wires Size • Match the length of wire to wire length of the central Up to 1000m: twisted wire 1.25mm control system. Up to 2000m: twisted wire 2.0mm If mixed in the system, the wire length is lengthened with all indoor/outdoor inter-unit wire length at side.
  • Page 86: How To Set Up Central Control Address Number

    7. External view of P.C. board assembly Terminator (SW01) 8. Address setup In addition to set up the central control address, it is necessary to change the indoor unit number. (Line/Indoor/Group address). For details, refer to TCC-LINK Adapter Installation Manual. 11-3.
  • Page 87: Address Setup

    12. ADDRESS SETUP 12-1. Address Setup Procedure When an outdoor unit and an indoor unit are connected, or when an outdoor unit is connected to each indoor unit respectively in the group operation even if multiple refrigerant lines are provided, the automatic address setup completes with power-ON of the outdoor unit.
  • Page 88: Address Setup & Group Control

    12-2. Address Setup & Group Control <Terminology> Indoor unit No. : N - n = Outdoor unit line address N (Max. 30) - Indoor unit address n (Max. 64) Group address : 0 = Single (Not group control) 1 = Master unit in group control 2 = Sub unit in group control Master unit (= 1) : The representative of multiple indoor units in group operation sends/receives signals to/from the remote controllers and sub indoor units.
  • Page 89 4. Single group operation • Each indoor unit controls the outdoor unit individually. Sub/Header Sub/Header Master/Header Sub/Header Sub/Header 5. Multiple groups operation (Manual address setting) Sub/Header Sub/Header Sub/Follower Master/Header Sub/Follower Sub/Follower • Header unit: The header unit receives the indoor unit data (thermo status) of the follower (Without identical line address &...
  • Page 90 12-2-2. Automatic Address Example from Unset Address (No miswiring) 1. Standard (One outdoor unit) 1) Single 2) Twin 3) Triple (1-1) (1-2) (1-1) (1-2) (1-3) Individual Master/Header Sub/Follower Sub/Header Master/Follower Sub/Follower (Master/Header) Only turning on source power supply (Automatic completion) 2.
  • Page 91: Address Setup (Manual Setting From Remote Controller)

    12-3. Address Setup (Manual Setting from Remote Controller) In case that addresses of the indoor units will be (Example of 2-lines cabling) (Real line: Cabling, Broken line: Refrigerant pipe) determined prior to piping work after cabling work Outdoor Outdoor • Set an indoor unit per a remote controller. 1 2 3 1 2 3 •...
  • Page 92: Confirmation Of Indoor Unit No. Position

    12-4. Confirmation of Indoor Unit No. Position 1. To know the indoor unit addresses though position of the indoor unit body is recognized • In case of individual operation (Wired remote controller : indoor unit = 1 : 1) (Follow to the procedure during operation) <Procedure>...
  • Page 93: Detachments

    13. DETACHMENTS 13-1. Indoor Unit Ceiling panel: RBC-UM11PG(W)E Preparing work: 1. Before work, be sure to stop the power supply of the air conditioner and turn off switch of the power supply breaker. (Otherwise an electric shock may be caused.) 2.
  • Page 94 Part name Procedure Remarks 1. Detachment Adjust corner cover 1) Perform work of procedure of 2) Turn clockwise screws (4 positions) at the suction port corner until adjust corner cover rises up. NOTE) When you work, keep the torque at below 12N•m. Do not use an electric screwdriver;...
  • Page 95 Part name Procedure Remarks 1. Detachment Control P.C. board 1) Perform works of procedure -1- and 2) Remove the connectors connected from the control P.C. board to other parts. CN33 : Flap motor (5P, White) CN34 : Float switch (3P, Red) CN41 : Terminal block of remote controller (3P, Blue) CN40 : Terminal block of crossover between inside and outside (5P, Black) CN68 : Drain pump (3P, Blue)
  • Page 96 Part name Procedure Remarks 1. Detachment Electric parts box 1) Perform works of procedure -1-and 2) Remove connectors of the lead wire connected to the following connectors of the control P.C. board. CN33 : Flap motor (5P, White) CN34 : Float switch (3P, Red) CN68 : Drain pump (3P, Blue) CN101 : TC2 sensor (2P, Black) CN102 : TCJ sensor (2P, Red)
  • Page 97 Part name Procedure Remarks 1. Detachment Bell mouth 1) Perform work of procedure Fixing claws 2) Take off the lead wires of the drain pump, float for lead wires Bell mouth switch, and fan motor from the bell mouth. 3) Take off fixing screws of the bell mouth. (Ø4 ×...
  • Page 98 Part name Procedure Remarks 1. Detachment Fan motor Fixing nut for fan motor 1) Perform work of procedure 2) Take off screws fixed with lead holding bracket of the fan motor. (Ø4 × 10, 2 pcs.) 3) Open wiring holding part of the fan motor lead holding bracket and then take off the fan motor lead wire from the bracket.
  • Page 99 Part name Procedure Remarks 1. Detachment Drain pan 2 screws 1) Perform works of procedure -1 and 2) Remove the drain cap and extract drain water accumulated in the drain pan. NOTE) Socket of dr Socket of drain pan et of drain pan ain pan When removing the drain cap, be sure to receive drain water with a bucket, etc.
  • Page 100 Part name Procedure Remarks 1. Detachment Heat exchanger 1) Recover refrigerant gas. 2) Remove the refrigerant pipe at indoor unit side. 3) Perform work of procedure Piping cover Piping cover 4) Take off screws (Ø4 × 10, 3 pcs.) fixing the piping cover to remove the piping cover.
  • Page 101: Exploded Views And Parts List

    14. EXPLODED VIEWS AND PARTS LIST 14-1. Ceiling Panel RBC-UM11PG(W)E Location Location Part No. Description Part No. Description 43109414 Grille, Air Inlet 43122091 Joint, Kit (A) 4302C059 Motor, Louver 43122092 Joint, Kit (B) 43180332 Air Filter 43122093 Louver 43497012 Screw 43107261 Outlet, Air Form 43100322...
  • Page 102: Compact 4-Way Air Discharge Cassette Type

    14-2. Compact 4-way Air Discharge Cassette Type 242, 249 238, 239, 240, 248 219 216 217 – 102 –...
  • Page 103 Model name RAV-SM Location Part No. Description 402MUT-E 452MUT-E 562MUT-E 43120225 Fan Ass’y, Turbo 43122094 Bell Mouth 43172185 Pan Ass’y, Drain 43121738 Motor, Fan, SWF-230-60-1R 4314J329 Refrigeration, Cycle Ass’y 4314Q034 Distributor Ass’y 43047685 Nut, Flare, 1/4 IN 43149351 Socket, 1/4 IN 43047688 Nut, Flare, 1/2 IN 43149353...
  • Page 104 Location Part No. Description 43160565 Terminal Block, 3P , AC250V, 20A, 43050425 Sensor Ass’y, Service TC (F6) 43050426 Sensor, Service, TA 43160568 Terminal, 2P , AC30V/DC42V, 1A 4316V323 P .C. Board Ass’y, MMC-1402 (220V – 240V) – 104 –...
  • Page 105 WARNINGS ON REFRIGERANT LEAKAGE Important Check of Concentration Limit NOTE 2 : The room in which the air conditioner is to be installed requires a design that in the event of The standards for minimum room volume are as follows. refrigerant gas leaking out, its concentration will not (1) No partition (shaded portion) exceed a set limit.
  • Page 106 TOSHIBA CARRIER CORPORATION 23-17, TAKANAWA 3 CHOME, MINATOKU, TOKYO, 108-8580, JAPAN Copyright © 1999 to 2007 TOSHIBA CARRIER CORPORATION, ALL Rights Reserved.

This manual is also suitable for:

Rav-sm452mut-eRav-sm562mut-e

Table of Contents