Shut Down And Restart - Beko Bekoblizz LC 12-355 Instructions For Installation And Operation Manual

Compressed air refrigeration chiller
Table of Contents

Advertisement

Note!
LC 12-35 - A dew point included in the green operating area of the electronic control unit is considered to
be correct according to the possible operating conditions (flow rate, air inlet temperature, ambient
temperature etc.).
LC 55-355 - A dew point between 0°C and +10°C displayed on the electronic control unit is considered to
be correct according to the possible operating conditions (flow rate, air inlet temperature, ambient
temperature etc.).
During the operation, the refrigerating compressor runs continuously. The chiller needs to be switched on during the
entire compressed-air usage time, even if the compressed-air compressor works periodically.
9.3

Shut down and restart

Shut down (see Section 11.1 "Control panel")
Ensure that the dew point temperature indicated on the electronic control unit is stable.
Interrupt the compressed-air supply.
After a few minutes, stop the chiller by switching off the main switch on the control panel (pos. 1).
Restart (see Section 11.1 "Control panel")
Make sure that the condenser is clean (air-cooled).
Ensure that the cooling-water flow and the temperature are in accordance with the provisions (water-cooled).
Check whether or not voltage is applied at the chiller.
Start the chiller by switching on the main switch on the control panel (pos. 1).
Ensure that the electronic control unit is switched on.
Wait a few minutes and then check, whether or not the dew point temperature indicated on the
electronic control unit is stable and whether or not the condensate is drained off at regular intervals.
Establish the compressed-air supply.
During the operation, the refrigerating compressor runs continuously. The chiller needs to be switched on during the
entire compressed-air usage time, even if the compressed-air compressor works periodically.
Note!
LC 12-35 - A dew point included in the green operating area of the electronic control unit is considered to
be correct according to the possible operating conditions (flow rate, air inlet temperature, ambient
temperature etc.).
LC 55-355 - A dew point between 0°C and +10°C displayed on the electronic control unit is considered to
be correct according to the possible operating conditions (flow rate, air inlet temperature, ambient
temperature etc.).
Note!
The chiller must not be started up more than six times an hour. Wait at least five minutes prior to
every restart. The user is responsible for the compliance with these provisions. Irreparable damage can
be caused when starting up the device too often.
BEKOBLIZZ® LC 12-355