When using with the Weekly-Timer, all switch settings except S41-1 must be OFF.
About the Setting Switches
● Complete the switch settings before turning ON the schedule timer power.
S41
Function selector switch (1) settings
• In the case of using the Schedule-Timer:
1
(U1-U2 network) set to OFF
2
• In the case of using the Weekly-Timer:
(4-core lead to remote) set to ON *
3
4
Timer Group Settings (2, 3)
5
Function
2
3
6
1 timer group – fixed
OFF
OFF
7
4 timer group – fixed
OFF
ON
8
8 timer group – fixed
ON
OFF
Manual group setting
ON
ON
OFF
ON
For details of the timer groups, refer to the Creating
* These switches are all
Timer Groups when using the Schedule Timer as
OFF at the time of
described in below.
delivery.
Central Control Main/Sub
Sub: OFF
Switching (4)
Main: ON
(Central Control Devices center/ Terminal switching)
(1) Set to "sub" (OFF) when using together with the 64 system
central remote controller. (Factory setting: Sub)
(2) Set to "main" (ON) when using together with an ON-OFF
controller, wired remote controller or wireless remote
controller.
* When using with multiple schedule timer units, set only
1 unit to "main" (ON) and set the remainder to "sub"
(OFF).
Schedule Timer Address Settings (5, 6, 7)
A maximum of 8 schedule timer units can be connected to the inter-unit
control wiring (central control wiring). If multiple units are connected, use the
setting switches and allocate the addresses, taking care to avoid duplication.
Address
5
6
7
Address 1
OFF
OFF
OFF
Address 2
OFF
OFF
ON
Address 3
OFF
ON
OFF
Address 4
OFF
ON
ON
Address 5
ON
OFF
OFF
Address 6
ON
OFF
ON
Address 7
ON
ON
OFF
Address 8
ON
ON
ON
Holiday and Operation Disable Settings for Each Group (8).
When this switch is set to OFF, units are all controlled together. When this switch is ON, the
units are controlled by the settings for each timer group.
(For details of the timer groups, refer to the Creating Timer Groups when using the Schedule
Timer as described in below.)
S42
1
2
Simultaneous time
Disabled: OFF
3
communications (5)
Enabled: ON
When multiple schedule timers are installed, set this
4
switch to ON to perform time settings for multiple units
5
simultaneously. One minute after the time is set, the time
6
at the other schedule timers will change to match the set
time. (Ordinarily this switch is set to OFF.)
7
8
Spare (6, 7, 8)
Be sure that these switches are OFF when the system is
OFF
ON
used.
* These switches are all OFF
at the time of delivery.
● The following switch setting is required when selecting remote controller enable/disable
button to enable with the schedule timer.
Remote controller disabled item Switch (2, 3, 4)
When remote controller enable/disable is used with the schedule timer, set the remote controller item switches 2,
2: Temperature setting
3 and 4 to the specific item according to the following items.
3: Operation mode
OFF: No setting
ON: Setting
64 system central
Remote controller disabled items
remote controller
2
indication
Mode 0 Remote controller enable/disable not used
No indication
OFF
OFF
Mode 1 Start/stop
Central 1
OFF
OFF
Mode 2 Operation mode
Central 4
OFF
Mode 3 Operation mode + Start/stop
Central
OFF
Mode 4 Temperature setting
Central
ON
OFF
Mode 5 Temperature setting + Start/stop
Central
ON
OFF
Mode 6 Temperature setting + Start/stop
Central 3
ON
Mode 7 Temperature setting + Operation mode + Start/stop
Central
ON
• All switch settings should be set to OFF when enable/disable is not used.
• Central 1 – 4 are the designations for the remote-controller disable modes for the 64 system central remote
controller.
• After the above setting is completed, perform the enable/disable setting using the
remote controller
button with schedule timer. For more information, refer to
[Setting Up Programmed Operations] in the Operation Manual of the Schedule Timer.
::: Continue from the previous section :::
Remote Controller Enable Items Switch (1) (Substitute/Addition Selector)
OFF:
(Substitute mode)
All setting contents will be substituted to setting contents using the remote controller disabled item
switches 2, 3 and 4 as opposed to the remote controller enable/disable items in setting presently.
Example: In the case of setting to [Mode 5] during remote controller disabled item (Temperature
setting+ Start/stop mode)
Use to remote controller
: Setting changeable
: Setting cannot be changed
Set to central 4 with the
Set to remote controller
Set to remote controller
64 system central
disabled item via the
enabled item via the
controller
timer
timer
Temperature setting
Temperature setting
Operation mode
Operation mode
Start/Stop
Start/Stop
Change to all of the setting items
Enable all items independently of
with switches
determined by setting switches
ON:
(Addition mode)
Items set to ON using the remote controller disabled item switches 2, 3 and 4 will be added to the
remote controller enable/disable items in the current setting.
Example: In the case of setting to [Mode 5] during remote controller disabled item (Temperature
setting+ Start/stop mode)
Use to remote controller
: Setting changeable
: Setting cannot be changed
Set to central 4 with the
Set to remote controller
Set to remote controller
64 system central
disabled item via the
enabled item via the
controller
timer
timer
Temperature setting
Temperature setting
Operation mode
Operation mode
Start/Stop
Start/Stop
Disabled addition with switch
Enabled addition with switch
setting items only (Temperature
setting items only (Temperature
setting + Start/stop)
setting + Start/stop)
Setting Central Control Addresses when using with the Schedule
Timer
● When using the schedule timer, central control addresses setting of the indoor
unit is required.
(If central control address of the indoor unit has not been set, the schedule timer cannot be
used to start and stop these units normally. Therefore, be sure to set the central control
addresses of the indoor unit before turning on the power of the schedule timer.)
(1) Turn on the power of all the indoor units.
(2) Confirm the setting for the system addresses, indoor addresses and group addresses
of all indoor units. If a wrong setting is found, reset the system addresses, indoor
addresses and group addresses correctly.
(3) Perform the address settings that turn off the power of the indoor units.
• Central control address setting using the wired remote controller
<Perform the following procedures, 1 to 5, to all the indoor units>
1. Press and hold the wired remote controller
button and
seconds.
2. Assign the item code (DN) to
using the temperature setting button
3. Set the desired control address (1 to 64) using the timer button
4. Press the
button.
(Confirm the remote controller indication changes from flashing to fully lit.)
5. After setting is completed, press the
button and then return the unit to general off status.
(In this case, it will take about 1 minute for normal remote controller operation to resume.)
<Central control address setting using the 64 system central remote controller>
Refer to the [Address switch setting] in the [Installation manual of 64 system central remote
controller] that is supplied to the 64 system central remote controller.
Creating Timer Groups when using the Schedule Timer
● The schedule timer can be used to create up to 8 timer groups (8 zones).
<Setting fixed timer groups (zones)>
Fig. 12
1 fixed timer group (1 setting zone) (64 units together)
Schedule
4 fixed timer group (4 setting zone) (16 units together)
timer
8 fixed timer group (8 setting zone) (8 units together)
Central control address 1
64 (Group (Zone) 1)
1
2
8
9
10
Central control address 1
8
Central control address 9
4: Start/stop
(Group (Zone) 2)
(Group (Zone) 1)
Central control address 1
16 (Group (Zone) 1)
3
4
18
24
25
26
17
OFF
ON
Central control address 17
24
Central control address 25
(Group (Zone) 3)
(Group (Zone) 4)
ON
OFF
Central control address 17
32 (Group (Zone) 2)
ON
ON
OFF
33
34
40
41
42
ON
ON
OFF
Central control address 33
40
Central control address 41
(Group (Zone) 5)
(Group (Zone) 6)
ON
ON
Central control address 33
48 (Group (Zone) 3)
49
50
56
57
58
Central control address 49
56
Central control address 57
(Group (Zone) 7)
(Group (Zone) 8)
Central control address 49
64 (Group (Zone) 4)
● Procedure for making fixed timer group settings (zone)
(1) First, use a 64 system central remote controller or the wired remote controllers to set
the central control addresses, as assigned in the figure above, to the indoor units that
will be subject to group timer control.
(2) Next, use S41 switches 2 and 3 to set the number of timer groups (zones) you wish to
create.
(For setting of switches 2 and 3, refer to the [About the Setting Switches] item above.
(3) Finally, turn on the schedule timer power. Initial communications are performed.
(
flashes in the display.) The normal display appears after several minutes, and
the timer group settings are confirmed.
<Procedure for making manual timer group settings (zone)>
Manual timer group settings allow central control addresses to be assigned freely within the timer
groups such as the setting example below.
Temperature setting
Fig. 13
Operation mode
Start/Stop
Setting example
Schedule timer
(Group (Zone) 1)
1
2
17
18
33
34
(Group (Zone) 4)
Temperature setting
Operation mode
Start/Stop
49
50
(Group (Zone) 7)
● Procedure for making manual timer group settings (zone)
(1) Turn on (manual settings) S41 setting switches 2 and 3, then turn on the power.
Restart and initial communications are performed. (
normal display appears after several minutes.
(2) When the normal display appears, press and hold the schedule timer
button, and the
button
flashing, in the present time display. (
address number.)
(3) Use the
button
2
in the Setting buttons area to select the timer group for
programmed operation. Then use the
select the central control address to assign and register for that timer group. Press the
4
button
to register the selected central control address. (Registered central
control address appears on the [Timer program] display area of the schedule timer.)
(4) To continue registering addresses, repeat step (3). Central control address numbers
will be added to the right side on the [Timer program] display area of the schedule
timer. To cancel a registered central control address, use the
Setting buttons area to select the timer group, then use the
button for at least 4
Setting buttons area to select the central control address and press the
(5) When registration is completed, press the
/
.
automatically and performs initial communications. (
/
.
normal display appears after several minutes, and the manually assigned timer group
settings are confirmed.
Fig. 14
16
16
5
1
4
32
• During manual timer group settings, the schedule timer can be used to create up to 8 groups (8
zones), and the central control addresses can be registered up to 64 units in 1 group (1
32
zone).In addition, one of the central control addresses can be set in multiple timer groups.
(Indoor units of the central control address 33-40 are performed to start/stop and enable/
disable operation according to the programmed operation for both timer group (zone) 1 and 4
to illustrate with reference to the thick frame marking as shown in above setting example of
48
Fig. 13)
48
64
64
Checking the Central Control Addresses and Operating the Units
that are Controlled by the Schedule Timer
● The schedule timer communicates with the indoor units to check which central control
addresses can be controlled with the current timer control.
The schedule timer can then be used to start and stop these units.
(1) Press and hold the schedule timer
for 4 seconds or longer. "
(2) Use the
button in the
in sequential order. In this way, it is possible to check which central control addresses
in the displayed timer group can be operated by the timer.
(3) With the selected timer group displayed, press the timer
button is pressed the indoor units in the displayed timer group start or stop. Pressing
the
button in this mode permits all items (operation start/stop, operation
mode, temperature setting items) at the indoor units in the displayed timer group where
remote controller prohibit is in effect.
(4) After checking the addresses and operating the units, press and hold the
button for 2 seconds or longer. The schedule timer display returns to the normal
display and all controllable indoor units stop.
Installation Work Plan
8
9
10
16
● Use the wired remote controller to check the unit No. of the indoor units.
(Group (Zone) 3)
(Start the A/C unit with the wired remote controller, then press the remote controller
UNIT SELECT button once to display the unit No. of the master unit.)
24
25
26
32
Schedule timer
Fixed timer group
(Group
(Zone))
1
4
8
40
41
42
48
(Group
(Group
1
(Zone) 5)
(Zone) 6)
56
57
58
64
1
(Group (Zone) 8)
2
flashes in the display.) The
button, the
1
for 4 seconds or longer. "
" appears,
indicates "address" and
is the central
3
button
3
in the Setting buttons area to
2
button
2
in the
4
3
button
in the
5
button
.
6
1 At the
button
. The schedule timer restarts
time of
flashes in the display.) The
shipment
5
3
Timer program display
area
6
2
3
6
7
4
8
button,
button, and
button
(central control address)" appears in sequence, blinking.
area to display the blinking central control addresses
button. Each time the
Central
Indoor unit Unit No.
control
Room name
System - Indoor
addresses
1
,
2
,
3
,
4
,
5
,
6
,
7
,
8
,
9
,
10
,
11
,
12
,
13
,
14
,
15
,
16
,
17
,
18
,
19
,
20
,
21
,
22
,
23
,
24
,
25
,
26
,
27
,
28
,
29
,
30
,
31
,
32
,
33
,
34
,
35
,
36
,
37
,
38
,
39
,
40
,
41
,
42
,
43
,
44
,
45
,
46
,
47
,
48
,
49
,
50
,
51
,
52
,
53
,
54
,
55
,
56
,
57
,
58
,
59
,
60
,
61
,
62
,
63
,
64
,
85464369073002 (E)

Advertisement

loading