Mitsubishi Electric EHSD-MEC.UK Service Manual page 49

R410a hydrobox
Hide thumbs Also See for EHSD-MEC.UK:
Table of Contents

Advertisement

No.
Fault symptom
4
LED2 on FTC is off.
<FTC powered on independent source>
(See 6. WIRING
1. FTC is not supplied with 220 to 240V AC.
DIAGRAM)
2. There are problems in the method of
connecting the connectors.
3. FTC failure
When LED1 on FTC is lit.
Incorrect setting of refrigerant address for
outdoor unit.
(None of the refrigerant address is set to "0".)
5
LED2 on FTC is
When LED1 is also blinking on FTC .
blinking.
Faulty wiring between FTC and outdoor unit
(See 6. WIRING
When LED1 on FTC is lit.
DIAGRAM)
1. Faulty wiring in main controller
Multiple indoor units have been wired to a
single outdoor unit.
2. Short-circuited wiring in main controller
3. Main controller failure
6
LED4 on FTC is off.
1. SD memory card is NOT inserted into the
(See 6. WIRING
memory card slot with correct orientation.
DIAGRAM)
2. Not an SD standards compliant memory card.
LED4 on FTC is
1. Full of data.
blinking.
2. Write-protected.
(See 6. WIRING
3. NOT formatted.
DIAGRAM)
4. Formatted in NTFS file system.
7
No water at hot tap.
1. Cold main off
2. Strainer (local supply) blocked.
8
Cold water at tap.
1. Hot water run out.
2. Prohibit, schedule timer or holiday mode se-
lected.
3. Heat pump not working.
4. Booster heater cut-out tripped.
5. The earth leakage circuit breaker for booster
heater breaker (ECB1) tripped.
6. The booster heater thermal cut-out has
tripped and cannot be reset using the manual
reset button.
7. Immersion heater cut-out tripped.
8. Immersion heater breaker (ECB2) tripped.
9. 3-way valve fault
OCH571
Possible cause
Check for faulty wiring between FTC and outdoor unit.
2.,3. Remove main controller wires and check LED2 on FTC. (See Figure 5.2.1. in
49
Explanation - Solution
1. Check the voltage across the L and N terminals on the indoor power supply
terminal block. (See 7. FIELD WIRING)
• When the voltage is not 220 to 240V AC, check for faulty wiring to power
supply.
• When the voltage is 220 to 240V AC, go to 2. below.
2.
Check for faulty wiring between the connectors.
• When the connectors are wired incorrectly re-wire them correctly referring
to below. (See 7. FIELD WIRING and a wiring diagram on the control and
electrical box cover.)
L
N
Modified settings
White
CN01
(Separate power
Hydrobox
S1
supply to
control board
the hydrobox)
S2
S3
• If no problem found with the wiring, go to 3. below.
3. Check the FTC control board.
• Check the fuse on FTC control board.
• Check for faulty wiring.
• If no problem found with the wiring, the FTC control board is faulty.
Recheck the refrigerant address setting on the outdoor unit.
Set the refrigerant address to "0".
(Set refrigerant address using SW1(3 - 6) on outdoor controller circuit board.)
1. Check for faulty wiring in main controller.
The number of indoor units that can be wired to a single outdoor unit is one.
Additional indoor units must be wired individually to a single outdoor unit.
installation manual)
• If LED2 is blinking check for short circuits in the main controller wiring .
• If LED2 is lit, wire the main controller again and:
- if LED2 is blinking, the main controller is faulty;
- if LED2 is lit, faulty wiring of the main controller has been corrected.
1. Correctly insert SD memory card in place until a click is heard.
2. Use an SD standards compliant memory card. (Refer to section 5.8. in instal-
lation manual)
1. Move or delete data, or replace SD memory card with a new one.
2. Release the write-protect switch.
3. Refer to "5.8 Using SD memory card" in installation manual.
4. FTC is Not compatible with NTFS file system. Use an SD memory card for-
matted in FAT file system.
1. Check and open stop cock.
2. Isolate water supply and clean strainer.
1. Ensure DHW mode is operating and wait for DHW tank to re-heat.
2. Check settings and change as appropriate.
3. Check heat pump – consult outdoor unit service manual.
4. Check booster heater thermostat and press reset button if safe.
Reset button is located on the side of booster heater, covered with white rub-
ber cap. See 4. PART NAMES AND FUNCTIONS to find out its position.
5. Check the cause and reset if safe.
6. Check resistance across the thermal cut-out, if open then the connection is
broken and the booster heater will have to be replaced.
Contact your Mitsubishi Electric dealer.
7. Check immersion heater thermostat and press reset button, located on im-
mersion heater boss, if safe. If the heater has been operated with no water
inside it may have failed, so please replace it with a new one.
8. Check the cause and reset if safe.
9. Check plumbing/wiring to 3-way valve.
(i) Manually override 3-way valve using the main controller. (Refer to <Man-
ual operation> in section 9-4.) If the valve does not still function, go to (ii)
below.
(ii) Replace 3-way valve.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents