Panasonic CS-MRE7MKE Service Manual page 68

Indoor unit outdoor unit
Hide thumbs Also See for CS-MRE7MKE:
Table of Contents

Advertisement

17.4.16. F11 (4-way valve Abnormality)
Malfunction Decision Conditions
• When heating operation, when indoor pipe temperature is below 10 C
• When cooling operation, when indoor pipe temperature is above 45 C
Malfunction Caused
• Connector in poor contact
• Faulty sensor
• Faulty outdoor unit PCB
• 4-way valve defective
Troubleshooting
68

Hide quick links: