TOSHIBA
6.0
Troubleshooting Procedures
6.4
AC Output Voltage Not Present
6.4
Is the AC
line LED indicator
YES
Is the inverter
LED indicator
YES
Is the fault
LED indicator
NO
Is the UPS unit
a 1500 or 2000 VA
Contact your Toshiba
service representative.
NO
lit?
NO
lit?
YES
lit?
YES
model?
NO
NO
Go to
6.1
Go to
6.2
Go to
6.3
Replace the output fuses.
(See note 2 page 5-4)
Is AC output
voltage present?
YES
Continue normal operations.
6 - 4