Sw1; Main/Sub Selection Switch; All/Zone Mode Selection Switch; Central Control/Remote Control Mode Selection Switch - Sanyo SHAKC64AGB Instruction Manual

Control system for spw air conditioner system's
Table of Contents

Advertisement

System Controller

SW1

Main/sub selection switch

OFF: System controller operates as main controller.
ON: System controller operates as sub-controller.

ALL/ZONE mode selection switch

ALL mode:
All indoor units can be controlled by system controller ZONE
1, 2, 3, 4 mode:
Indoor units in one of zone 1, 2, 3, or 4 can be controlled by
system controller. All indoor units cannot be set.
ALL mode
ZONE 1 mode
ZONE 2 mode
ZONE 3 mode
ZONE 4 mode

Central control/Remote control mode selection switch.

OFF: Central control mode
Individual setting by remote controller can be inhibited by
system controller.
ON: Remote control mode
Setting by system controller is inhibited by other central
control equipments.
Central control Main/Sub selection switch
(OFF: Main, ON: Sub)
1
When AMY adaptor etc. is used with system controller,
set the switch to ON position.
2
When only 1 system controller is used, set the switch
to OFF position.
3
Except
1
only 1 system controller to OFF position others to ON
position.
ALL mode system controller to be OFF position.
(recommended)
(Central control) button operation switch
OFF:
(Central control) button operation is permitted.
ON :
button operation is inhibited.
*All switches are in OFF position at shipment.
2
3
4
5
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
ON
ON
, when multiple system controllers are used, set
Fig. 3-60
.
SW1
ON
1
2 3 4
5 6 7 8
OFF
3