Mitsubishi Electric PUHY-P200 Service Handbook

Mitsubishi Electric PUHY-P200 Service Handbook

Hide thumbs Also See for PUHY-P200:
Table of Contents

Advertisement

2010
AIR CONDITIONER
Service Handbook
Service Handbook
Model
PUHY-P200, P250, P300, P350, P400, P450YJM-A
PUHY-P500, P550, P600, P650, P700, P750, P800, P850, P900YSJM-A(1)
PUHY-P950, P1000, P1050, P1100, P1150, P1200, P1250YSJM-A
PUHY-EP200, EP250, EP300YJM-A
PUHY-EP400, EP450, EP500, EP550, EP600YSJM-A(1)
PUHY-EP650, EP700, EP750, EP800, EP850, EP900YSJM-A(1)

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric PUHY-P200

  • Page 1 2010 AIR CONDITIONER Service Handbook Service Handbook Model PUHY-P200, P250, P300, P350, P400, P450YJM-A PUHY-P500, P550, P600, P650, P700, P750, P800, P850, P900YSJM-A(1) PUHY-P950, P1000, P1050, P1100, P1150, P1200, P1250YSJM-A PUHY-EP200, EP250, EP300YJM-A PUHY-EP400, EP450, EP500, EP550, EP600YSJM-A(1) PUHY-EP650, EP700, EP750, EP800, EP850, EP900YSJM-A(1)
  • Page 2: Safety Precautions

    Safety Precautions Before installing the unit, thoroughly read the following safety precautions. Observe these safety precautions for your safety. WARNING This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid the risk of serious injury or death.
  • Page 3 WARNING Securely attach the terminal block cover (panel) to the After completing the service work, check for a gas unit. leak. If the terminal block cover (panel) is not installed properly, If leaked refrigerant is exposed to a heat source, such as a dust and/or water may infiltrate and pose a risk of electric fan heater, stove, or electric grill, poisonous gases may be shock, smoke, and/or fire.
  • Page 4 Precautions for handling units for use with R410A CAUTION Do not use the existing refrigerant piping. Use a vacuum pump with a reverse-flow check valve. A large amount of chlorine that may be contained in the re- If a vacuum pump that is not equipped with a reverse-flow sidual refrigerant and refrigerating machine oil in the exist- check valve is used, the vacuum pump oil may flow into the ing piping may cause the refrigerating machine oil in the...
  • Page 5: Before Installing The Unit

    Before installing the unit WARNING Do not install the unit where a gas leak may occur. When installing the unit in a hospital, take appropriate measures to reduce noise interference. If gaseous refrigerant leaks and piles up around the unit, it may be ignited.
  • Page 6 Before installing the unit (moving and reinstalling the unit) and performing electrical work CAUTION Properly ground the unit. Periodically check the installation base for damage. Do not connect the grounding wire to a gas pipe, water pipe, If the unit is left on a damaged platform, it may fall and lightning rod, or grounding wire from a telephone pole.
  • Page 7 Before the test run CAUTION Turn on the unit at least 12 hours before the test run. Do not operate the unit without panels and safety guards. Keep the unit turned on throughout the season. If the unit is turned off in the middle of a season, it may result in malfunc- Rotating, high-temperature, or high-voltage parts on the unit tions.
  • Page 8: Table Of Contents

    CONTENTS I Read Before Servicing [1] Read Before Servicing......................3 [2] Necessary Tools and Materials ....................4 [3] Piping Materials ........................5 [4] Storage of Piping ........................7 [5] Pipe Processing........................7 [6] Brazing............................8 [7] Air Tightness Test........................9 [8] Vacuum Drying (Evacuation) ....................
  • Page 9 HWE10040...
  • Page 10: Read Before Servicing

    I Read Before Servicing [1] Read Before Servicing ....................... 3 [2] Necessary Tools and Materials..................4 [3] Piping Materials ......................... 5 [4] Storage of Piping ....................... 7 [5] Pipe Processing ......................... 7 [6] Brazing..........................8 [7] Air Tightness Test ......................9 [8] Vacuum Drying (Evacuation) ...................
  • Page 11 - 2 -...
  • Page 12: Read Before Servicing

    [ I Read Before Servicing ] I Read Before Servicing [1] Read Before Servicing 1. Check the type of refrigerant used in the system to be serviced. Refrigerant Type Multi air conditioner for building application CITY MULTI YJM-A series R410A 2.
  • Page 13: Necessary Tools And Materials

    [ I Read Before Servicing ] [2] Necessary Tools and Materials Prepare the following tools and materials necessary for installing and servicing the unit. Tools for use with R410A (Adaptability of tools that are for use with R22 or R407C) 1.
  • Page 14: Piping Materials

    [ I Read Before Servicing ] [3] Piping Materials Do not use the existing piping! 1. Copper pipe materials O-material (Annealed) Soft copper pipes (annealed copper pipes). They can easily be bent with hands. 1/2H-material (Drawn) Hard copper pipes (straight pipes). They are stronger than the O-material (Annealed) at the same radial thickness.
  • Page 15 [ I Read Before Servicing ] 4. Thickness and refrigerant type indicated on the piping materials Ask the pipe manufacturer for the symbols indicated on the piping material for new refrigerant. 5. Flare processing (O-material (Annealed) and OL-material only) The flare processing dimensions for the pipes that are used in the R410A system are larger than those in the R22 system. Flare processing dimensions (mm[in]) A dimension (mm) Pipe size (mm[in])
  • Page 16: Storage Of Piping

    [ I Read Before Servicing ] [4] Storage of Piping 1. Storage location Store the pipes to be used indoors. (Warehouse at site or owner's warehouse) If they are left outdoors, dust, dirt, or moisture may infiltrate and contaminate the pipe. 2.
  • Page 17: Brazing

    [ I Read Before Servicing ] [6] Brazing No changes have been made in the brazing procedures. Perform brazing with special care to keep foreign objects (such as oxide scale, water, and dust) out of the refrigerant system. Example: Inside the brazed connection Use of oxidized solder for brazing Use of non-oxidized solder for brazing 1.
  • Page 18: Air Tightness Test

    [ I Read Before Servicing ] [7] Air Tightness Test No changes have been made in the detection method. Note that a refrigerant leak detector for R22 will not detect an R410A leak. Halide torch R22 leakage detector 1. Items to be strictly observed Pressurize the equipment with nitrogen up to the design pressure (4.15MPa[601psi]), and then judge the equipment's air tight- ness, taking temperature variations into account.
  • Page 19: Vacuum Drying (Evacuation)

    [ I Read Before Servicing ] [8] Vacuum Drying (Evacuation) (Photo1) 15010H (Photo2) 14010 Recommended vacuum gauge: ROBINAIR 14010 Thermistor Vacuum Gauge 1. Vacuum pump with a reverse-flow check valve (Photo1) To prevent the vacuum pump oil from flowing into the refrigerant circuit during power OFF or power failure, use a vacuum pump with a reverse-flow check valve.
  • Page 20: Refrigerant Charging

    [ I Read Before Servicing ] [9] Refrigerant Charging Cylinder with a siphon Cylinder without a siphon Cylin- Cylin- Cylinder color R410A is pink. Refrigerant charging in the liquid state Valve Valve liquid liquid 1. Reasons R410A is a pseudo-azeotropic HFC blend (boiling point R32=-52°C[-62°F], R125=-49°C[-52°F]) and can almost be handled the same way as a single refrigerant, such as R22.
  • Page 21: Characteristics Of The Conventional And The New Refrigerants

    [ I Read Before Servicing ] [11] Characteristics of the Conventional and the New Refrigerants 1. Chemical property As with R22, the new refrigerant (R410A) is low in toxicity and chemically stable nonflammable refrigerant. However, because the specific gravity of vapor refrigerant is greater than that of air, leaked refrigerant in a closed room will accumulate at the bottom of the room and may cause hypoxia.
  • Page 22: Notes On Refrigerating Machine Oil

    [ I Read Before Servicing ] [12] Notes on Refrigerating Machine Oil 1. Refrigerating machine oil in the HFC refrigerant system HFC type refrigerants use a refrigerating machine oil different from that used in the R22 system. Note that the ester oil used in the system has properties that are different from commercially available ester oil. Refrigerant Refrigerating machine oil Mineral oil...
  • Page 23 [ I Read Before Servicing ] HWE10040 - 14 -...
  • Page 24: Ii Restrictions

    II Restrictions [1] System configuration ....................... 17 [2] Types and Maximum allowable Length of Cables ............19 [3] Switch Settings and Address Settings ................20 [4] Sample System Connection..................... 27 [5] An Example of a System to which an MA Remote Controller is connected..... 28 [6] An Example of a System to which an ME Remote Controller is connected.....
  • Page 25 - 16 -...
  • Page 26: System Configuration

    [ II Restrictions ] II Restrictions [1] System configuration 1. Table of compatible indoor units The table below summarizes the types of indoor units that are compatible with different types of outdoor units. (1) Standard combinations Outdoor units Composing units Maximum total ca- Maximum num- Types of connectable...
  • Page 27 [ II Restrictions ] (2) High COP combinations Outdoor units Composing units Maximum total ca- Maximum num- Types of connectable pacity of connect- ber of connect- indoor units able indoor units able indoor units EP200 YJM-A P15 - P200 models R410A series indoor units EP250 YJM-A...
  • Page 28: Types And Maximum Allowable Length Of Cables

    [ II Restrictions ] [2] Types and Maximum allowable Length of Cables 1. Wiring work (1) Notes 1) Have all electrical work performed by an authorized electrician according to the local regulations and instructions in this man- ual. 2) Install external transmission cables at least 5cm [1-31/32"] away from the power supply cable to avoid noise interference. (Do not put the control cable and power supply cable in the same conduit tube.) 3) Provide grounding for the outdoor unit as required.
  • Page 29: Switch Settings And Address Settings

    [ II Restrictions ] 2) Remote controller wiring MA remote controller ME remote controller Type Number of 2-core cable 2-core cable cores Cable type 2 *3 2 *3 0.3 to 1.25mm 0.3 to 1.25mm [AWG22 to 16] [AWG22 to 16] Cable size (0.75 to 1.25mm (0.75 to 1.25mm...
  • Page 30 [ II Restrictions ] 2. M-NET Address settings (1) Address settings table The need for address settings and the range of address setting depend on the configuration of the system. Unit or controller Address setting Setting method Facto- range ry set- ting CITY MULTI in- Main/sub unit...
  • Page 31 [ II Restrictions ] (2) Power supply switch connector connection on the outdoor unit (Factory setting: The male power supply switch connector is connected to CN41.) System configu- Connection to Power supply unit Group operation Power supply switch connector connection ration the system con- for transmission...
  • Page 32 [ II Restrictions ] (6) Miscellaneous settings Cooling-only setting for the indoor unit: Cooling only model (Factory setting: SW3-1 "OFF.") When using indoor unit as a cooling-only unit, set SW3-1 to ON. (7) Various types of control using input-output signal connector on the outdoor unit (various connection options) Terminal Type Usage...
  • Page 33 [ II Restrictions ] Example of wiring connection (1) CN51 (2) CN3S Outdoor unit Relay circuit Adapter 2 control board Distant control Relay circuit Adapter 1 board Outdoor unit CN3S control board CN51 Preparations in the field Maximum cable Preparations length is 10m Maximum cable in the field...
  • Page 34 [ II Restrictions ] 3. Demand control (1) General outline of control Demand control is performed by using the external signal input to the 1-2 and 1-3 pins of CN3D on the outdoor units (OC, OS1, and OS2). Between 2 and 12 steps of demand control is possible by setting DIP SW4-4 on the outdoor units (OC, OS1, and OS2). Table.1 DipSW4-4 Demand control switch...
  • Page 35 [ II Restrictions ] 3) 8-step demand control (When SW4-4 is set to ON on two outdoor units) Demand capacity is shown below. 8-step demand No.2 CN3D 1-2P Open Short-circuit No.1 CN3D 1-2P 1-3P Open Short-circuit Open Short-circuit Open Open 100% Short-circuit Short-circuit...
  • Page 36: Sample System Connection

    [ II Restrictions ] [4] Sample System Connection Examples of typical system connection are shown on pages [5] to [7]. Refer to the Installation Manual that came with each device or controller for details. (1) An example of a system to which an MA remote controller is connected System Address start up for in- Connection to the system controller...
  • Page 37: An Example Of A System To Which An Ma Remote Controller Is Connected

    [ II Restrictions ] [5] An Example of a System to which an MA Remote Controller is connected 1. System with one outdoor unit (automatic address setup for both indoor and outdoor units) (1) Sample control wiring Interlock operation with the ventilation unit Leave the male Leave the male...
  • Page 38 [ II Restrictions ] MA remote controller function selection or the installation (4) Wiring method manual for the MA remote controller for the setting meth- 1) Indoor/outdoor transmission line od.) Daisy-chain terminals M1 and M2 on the terminal block Group operation of indoor units for indoor-outdoor transmission line (TB3) on the outdoor To perform a group operation of indoor units (IC), daisy- units (OC, OS1, OS2) (Note), and terminals M1 and M2...
  • Page 39 [ II Restrictions ] 2. An example of a system with one outdoor unit to which 2 or more LOSSNAY units are connected (manual address setup for both indoor and outdoor units) (1) Sample control wiring Interlock operation with the ventilation unit Leave the male Leave the male Leave the male...
  • Page 40 [ II Restrictions ] 4) LOSSNAY connection (4) Wiring method Connect terminals M1 and M2 on the terminal block 1) Indoor/outdoor transmission line (TB5) on the indoor unit (IC) to the appropriate terminals Same as [5] 1. on the terminal block (TB5) on LOSSNAY (LC). (Non-po- Shielded cable connection larized two-wire) Same as [5] 1.
  • Page 41 [ II Restrictions ] 3. Group operation of units in a system with multiple outdoor units (1) Sample control wiring Interlock operation with the ventilation unit Move the male connector Leave the male Leave the male Group Group Group from CN41 to CN40. connector on connector on SW2-1 OFF...
  • Page 42 [ II Restrictions ] (If there is a problem with the outdoor unit whose power (4) Wiring method jumper was moved from CN41 to CN40, centralized con- 1) Indoor/outdoor transmission line trol is not possible, even if TB7's are daisy-chained). Same as [5] 1.
  • Page 43 [ II Restrictions ] 4. A system in which a system controller is connected to the transmission line for centralized control and which is pow- ered from an outdoor unit (1) Sample control wiring Interlock operation with the ventilation unit Move the male connector Leave the male Leave the male...
  • Page 44 [ II Restrictions ] a power failure, daisy-chain TB7 of OC, OS1, and OS2. (4) Wiring method (If there is a problem with the outdoor unit whose power 1) Indoor/outdoor transmission line jumper was moved from CN41 to CN40, centralized con- trol is not possible, even if TB7's are daisy-chained).
  • Page 45 [ II Restrictions ] 5. An example of a system in which a system controller is connected to the indoor-outdoor transmission line (except LM adapter) (1) Sample control wiring Interlock operation with the ventilation unit Move the male connector Leave the male Leave the male from CN41 to CN40.
  • Page 46 [ II Restrictions ] (4) Wiring method b) When not daisy-chaining TB7's on the outdoor units in the 1) Indoor/outdoor transmission line same refrigerant circuit, connect the transmission line for Daisy-chain terminals M1 and M2 on the terminal block centralized control to TB7 on the OC (Note a). To maintain centralized control even during an OC failure or a power fail- for indoor-outdoor transmission line (TB3) on the outdoor ure, daisy-chain TB7 of OC, OS1, and OS2.
  • Page 47: An Example Of A System To Which An Me Remote Controller Is Connected

    [ II Restrictions ] [6] An Example of a System to which an ME Remote Controller is connected (1) Sample control wiring Interlock operation with the ventilation unit Move the male connector Leave the male Leave the male from CN41 to CN40. connector on connector on SW2-1 OFF ON...
  • Page 48 [ II Restrictions ] When 2 remote controllers are connected to the sys- (4) Wiring method 1) Indoor/outdoor transmission line Refer to the section on Switch Setting. Same as [5] 1. Performing a group operation (including the group Shielded cable connection operation of units in different refrigerant circuits).
  • Page 49: An Example Of A System To Which Both Ma Remote Controller And Me Remote Controller Are Connected

    [ II Restrictions ] [7] An Example of a System to which both MA Remote Controller and ME Remote Controller are connected (1) Sample control wiring Leave the male Leave the male Move the male connector connector on connector on Group from CN41 to CN40.
  • Page 50 [ II Restrictions ] Same as [5] 1. (4) Wiring method Group operation of indoor units 1) Indoor/outdoor transmission line Same as [5] 1. Same as [5] 1. 4) ME remote controller wiring Shielded cable connection Same as [6] Same as [5] 1. When 2 remote controllers are connected to the sys- 2) Transmission line for centralized control Same as [5] 4.
  • Page 51: Restrictions On Pipe Length

    [ II Restrictions ] [8] Restrictions on Pipe Length (1) End branching P200 - P450 models Outdoor unit Branch header First branch (Branch joint) Indoor Indoor Indoor Branch joint Indoor Indoor Indoor Unit: m [ft] Allowable length of Operation Pipe sections pipes Length Total pipe length...
  • Page 52 [ II Restrictions ] P500 - P1250 models Provide a trap on the pipe (gas pipe only) within 2 m from the Note1 Install the pipe that connects the branch pipe and the outdoor units in joint pipe if the total length of the pipe that connects the joint the way that it has a downward inclination toward the branch pipe.
  • Page 53 [ II Restrictions ] 1. Refrigerant pipe size (1) Diameter of the refrigerant pipe between the outdoor unit and the first branch (outdoor unit pipe size) Outdoor unit set name Liquid pipe size (mm) [inch] Gas pipe size (mm) [inch] (total capacity) 200 model ø9.52 [3/8"]...
  • Page 54 [ II Restrictions ] (4) Size of the refrigerant pipe between the first distributor and the second distributor Liquid pipe size (mm) [inch] Gas pipe size (mm) [inch] ø19.05 [3/4"] ø34.93 [1-3/8"] (5) Size of the refrigerant pipe between the first distributor or the second distributor and outdoor units Liquid pipe size (mm) [inch] Gas pipe size (mm) [inch] 200 model ø9.52 [3/8"]...
  • Page 55 [ II Restrictions ] HWE10040 - 46 -...
  • Page 56: Iii Outdoor Unit Components

    III Outdoor Unit Components [1] Outdoor Unit Components and Refrigerant Circuit ............49 [2] Control Box of the Outdoor Unit..................53 [3] Outdoor Unit Circuit Board....................54 HWE10040 - 47 -...
  • Page 57 - 48 -...
  • Page 58: Outdoor Unit Components And Refrigerant Circuit

    [ III Outdoor Unit Components ] III Outdoor Unit Components [1] Outdoor Unit Components and Refrigerant Circuit 1. Front view of an outdoor unit (1) PUHY-P200, P250, P300, P350, P400YJM-A, PUHY-EP200, EP250YJM-A Fan guard Control Control Control Heat exchanger Heat exchanger...
  • Page 59 [ III Outdoor Unit Components ] (2) PUHY-P450YJM-A, PUHY-EP300YJM-A Fan guard Fan guard Fan guard Control Control Control Contactor Contactor Heat exchanger Heat exchanger Heat exchanger Front panel Front panel Front panel Fin guard Fin guard Fin guard HWE10040 - 50 -...
  • Page 60 [ III Outdoor Unit Components ] 2. Refrigerant circuit (1) PUHY-P200, P250, P300YJM-A, PUHY-EP200YJM-A Low-pressure sensor(63LS) High-pressure sensor(63HS1) Check valve High-pressure switch(63H1) 4-way valve(21S4b) Accumulator 4-way valve(21S4a) Low-pressure check joint High-pressure check joint Subcool coil Compressor cover Linear expansion valve...
  • Page 61 [ III Outdoor Unit Components ] (3) PUHY-P450YJM-A, PUHY-EP300YJM-A Low-pressure sensor(63LS) High-pressure sensor(63HS1) 2-way valve(SV5b) 4-way valve(21S4b) 4-way valve(21S4c) Linear expansion valve High-pressure switch(63H1) Check valve 4-way valve(21S4a) (LEV1) High-pressure Linear expansion valve check joint (LEV2) Solenoid valve (SV1a) Compressor cover 2-way valve(SV5c) Solenoid valve Accumulator...
  • Page 62: Control Box Of The Outdoor Unit

    [ III Outdoor Unit Components ] [2] Control Box of the Outdoor Unit <HIGH VOLTAGE WARNING> Control box houses high-voltage parts. When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.
  • Page 63: Outdoor Unit Circuit Board

    [ III Outdoor Unit Components ] [3] Outdoor Unit Circuit Board 1. Outdoor unit control board CN332 CNDC Serial communication signal input Output 18VDC CN801 Bus voltage input GND (INV board) Pressure switch Output 17VDC (Fan board) connection Serial communication signal output CNAC2 driving output LED1...
  • Page 64 [ III Outdoor Unit Components ] 2. M-NET board CNS2 CNIT Transmission line input/output for 12VDC input CN04 centralized control system CN102 Bus voltage input 5VDC input Power supply output for centralized control system Power supply detection output Indoor/outdoor transmission line input/output Power supply ON/OFF Grounding signal input...
  • Page 65 [ III Outdoor Unit Components ] 3. INV board SC-P1 Rectifier diode output (P) Open: No-load operation setting CN5V RSH1 SC-P2 Short-circuited: Normal setting LED1 Overcurrent detection Bus voltage Input(P) Lit: Inverter in normal operation 5VDC output resistor Blink: Inverter error GND(Fan Board) Serial communication signal output...
  • Page 66: Fan Board

    [ III Outdoor Unit Components ] 4. Fan board LED3 CN18V Lit during normal Input 18VDC Serial communication signal output CPU operation GND(Control board) Serial communication signal output CN21 Serial communication signal output GND(INV board) CNVDC Input 17VDC Bus voltage input CN22 GND(INV board) Input 5VDC...
  • Page 67 [ III Outdoor Unit Components ] 5. Noise Filter Output Output (Rectified L2-N current) (Rectified L2-N current) Surge absorber circuit Surge absorber circuit Short circuit Short circuit Grounding F1,F2,F3,F4 Fuse 250VAC 6.3A Output Grounding CN1A Input CN1B TB21 TB22 TB23 TB24 Input Input/output(L1)
  • Page 68: Iv Remote Controller

    IV Remote Controller [1] Functions and Specifications of MA and ME Remote Controllers ........61 [2] Group Settings and Interlock Settings via the ME Remote Controller ......62 [3] Interlock Settings via the MA Remote Controller ............. 66 [4] Using the built-in Temperature Sensor on the Remote Controller ........67 HWE10040 - 59 -...
  • Page 69 - 60 -...
  • Page 70: Functions And Specifications Of Ma And Me Remote Controllers

    [ IV Remote Controller ] IV Remote Controller [1] Functions and Specifications of MA and ME Remote Controllers There are two types of remote controllers: ME remote controller, which is connected on the indoor-outdoor transmission line, and MA remote controller, which is connected to each indoor unit. 1.
  • Page 71: Group Settings And Interlock Settings Via The Me Remote Controller

    [ IV Remote Controller ] [2] Group Settings and Interlock Settings via the ME Remote Controller 1. Group settings/interlock settings Make the following settings to perform a group operation of units that are connected to different outdoor units or to manually set up the indoor/outdoor unit address.
  • Page 72 [ IV Remote Controller ] Repeat steps in the previous page to interlock all the indoor units in a group with the LOSSNAY unit. (C) To return to the normal display When all the group settings and interlock settings are made, take the To go back to the normal display, To search for an address, follow step...
  • Page 73 [ IV Remote Controller ] (A) To delete group settings (B) To delete interlock settings <Successful completion of deletion> If deletion is successfully completed, will appear in the unit type display window. If the deletion fails, will (Displayed alternately) will be displayed in the room temperature display window. appear in the unit type display - If a transmission error occurs, the selected setting will not be window.
  • Page 74 [ IV Remote Controller ] [Operation Procedures] 1. Press the [ON/OFF] button on the remote controller to bring the unit to a stop. The display will appear as shown in the previous page (Normal display). 2. Press buttons [CHECK] and [ ] simultaneously for 2 seconds to go into the “Skip-Auto-Mode setting.”...
  • Page 75: Interlock Settings Via The Ma Remote Controller

    [ IV Remote Controller ] [3] Interlock Settings via the MA Remote Controller 1. LOSSNAY interlock setting (Make this setting only when necessary.) (1) MA Remote Controller (PAR-21MAA) * When the upper controller is connected, make the setting using the upper controller. NOTE: When using LOSSNAY units in conjunction, interlock the addresses of all indoor units within the group and address of LOSSNAY units.
  • Page 76: Using The Built-In Temperature Sensor On The Remote Controller

    [ IV Remote Controller ] < 2. Search Procedures > To search for the LOSSNAY unit that is interlocked with a particular indoor unit, enter the address of the indoor unit into the remote controller that is connected to it. <Indoor unit address>...
  • Page 77 [ IV Remote Controller ] HWE10040 - 68 -...
  • Page 78: V Electrical Wiring Diagram

    V Electrical Wiring Diagram [1] Electrical Wiring Diagram of the Outdoor Unit ..............71 [2] Electrical Wiring Diagram of Transmission Booster............73 HWE10040 - 69 -...
  • Page 79 - 70 -...
  • Page 80: Electrical Wiring Diagram Of The Outdoor Unit

    [ V Electrical Wiring Diagram ] V Electrical Wiring Diagram [1] Electrical Wiring Diagram of the Outdoor Unit 1. Electrical wiring diagram of the outdoor unit (1) PUHY-(E)P200, (E)P250, P300, P350, P400 models HWE10040 - 71 -...
  • Page 81 [ V Electrical Wiring Diagram ] (2) PUHY-P450, EP300 models HWE10040 - 72 -...
  • Page 82: Electrical Wiring Diagram Of Transmission Booster

    [ V Electrical Wiring Diagram ] [2] Electrical Wiring Diagram of Transmission Booster Terminal block for power supply (TB1) 250V 5A Red Red Red Black White White Green/Yellow AC220 - 240V Varistor Noise filter Black White White White White Varistor Green Black Stabilized power supply...
  • Page 83 [ V Electrical Wiring Diagram ] HWE10040 - 74 -...
  • Page 84: Vi Refrigerant Circuit

    VI Refrigerant Circuit [1] Refrigerant Circuit Diagram ..................... 77 [2] Principal Parts and Functions ..................79 HWE10040 - 75 -...
  • Page 85 - 76 -...
  • Page 86: Refrigerant Circuit Diagram

    [ VI Refrigerant Circuit ] VI Refrigerant Circuit [1] Refrigerant Circuit Diagram 1. Outdoor unit (1) PUHY-P200, P250, P300 models, EP200 model 21S4b 21S4a 63H1 63HS1 SV1a 63LS COMP SV5b LEV1 LEV2 SCC (HIC Circuit) (2) PUHY-P350, P400 models, EP250 model...
  • Page 87 [ VI Refrigerant Circuit ] (3) PUHY-P450 model, EP300 model 21S4c 21S4b FAN2 HEX2 (For HEX2) (Right side) 21S4a 63LS 63H1 63HS1 SV1a HEX1 (Left side) FAN1 (For HEX1) COMP SV5c SV5b LEV2 LEV1 SCC (HIC Circuit) HWE10040 - 78 -...
  • Page 88: Principal Parts And Functions

    [ VI Refrigerant Circuit ] [2] Principal Parts and Functions 1. Outdoor unit Part Symbols Notes Usage Specifications Check method name (functions) Com- Adjusts the amount of circulating P200 - 250 and EP200 mod- pressor (Comp1) refrigerant by adjusting the operat- ing frequency based on the oper- Low-pressure shell scroll ating pressure data...
  • Page 89 [ VI Refrigerant Circuit ] Part Symbols Notes Usage Specifications Check method name (functions) Thermis- 1) Detects discharge air temper- Degrees Celsius Resistance (Discharge) check ature = 7.465k = 4057 2) Provides high-pressure pro- 25/120 tection 7.465 4057 0°C[32°F] :698kohm 10°C[50°F] :413kohm 20°C[68°F] :250kohm 30°C[86°F] :160kohm...
  • Page 90 [ VI Refrigerant Circuit ] Part Symbols Notes Usage Specifications Check method name (functions) Sole- SV1a 1) High/low pressure bypass at AC220-240V Continuity noid Discharge-suc- Open while being powered/ check with a start-up and stopping, and valve tion closed while not being pow- tester capacity control during low- bypass...
  • Page 91 [ VI Refrigerant Circuit ] 2. Indoor Unit Part Symbol Notes Usage Specification Check method Name (functions) Linear 1) Adjusts superheat at the DC12V Refer to the section expan- Opening of stepping motor "Continuity Test with a indoor heat exchanger sion valve driving valve 0-(1400) puls- Tester".
  • Page 92: Vii Control

    VII Control [1] Functions and Factory Settings of the Dipswitches ............85 [2] Controlling the Outdoor Unit .................... 92 [3] Operation Flow Chart..................... 105 HWE10040 - 83 -...
  • Page 93 - 84 -...
  • Page 94: Functions And Factory Settings Of The Dipswitches

    [ VII Control ] VII Control [1] Functions and Factory Settings of the Dipswitches 1. Outdoor unit (1) Control board Units that re- quire switch Function according to switch setting Switch setting timing setting Switch Function Note.2 Unit address setting Set to 00 or 51-100 with the dial switch Before power on For self-diagnosis/...
  • Page 95 [ VII Control ] Units that re- quire switch Function according to switch setting Switch setting timing setting Switch Function Note.2 Test run mode: en- SW3-2 disabled SW3-2 enabled Anytime after power on abled/disabled Test run mode: ON/ Sends a test-run After power on and when Stops all ICs signal to all IC...
  • Page 96 [ VII Control ] 1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason. 2) A: Only the switch on either the OC or OS needs to be set for the setting to be effective on both units. B: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
  • Page 97 [ VII Control ] (2) INV board Functions are switched with the following connector. Function according to connec- Setting timing Connector Function Enabled Disabled Enabled Disabled CN6 short- Enabling/disabling the following error Error detec- Error detec- Anytime after power on circuit con- detection functions;...
  • Page 98 [ VII Control ] 2. Function of the switch (Indoor unit) (1) Dipswitches 1) SW1,3 Function according to switch setting Switch setting timing Switch Function Notes Set to ON (built-in sensor on the remote controller) Room temperature Built-in sensor on Indoor unit inlet on All Fresh (PEFY-VMH-F) model units detection position...
  • Page 99 [ VII Control ] (2) Address switch Actual indoor unit address setting varies in different systems. Refer to the installation manual for the outdoor unit for details on how to make the address setting. Each address is set with a combination of the settings for the 10's digit and 1's digit. (Example) When setting the address to "3", set the 1's digit to 3, and the 10's digit to 0.
  • Page 100 [ VII Control ] (2) ME remote controller (PAR-F27MEA) Set the address of the remote controller with the rotary switch. Rotary switch 10's digit 1's digit (left) (right) Remote controller unit Example: In case of address 108 Address setting range Setting method Main remote controller 101-150...
  • Page 101: Controlling The Outdoor Unit

    [ VII Control ] [2] Controlling the Outdoor Unit Outline of Control Method -1- Outline of Control Method The outdoor units are designated as OC, OS1 and OS2 in the order of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
  • Page 102 [ VII Control ] Bypass Control -5- Bypass Control Bypass solenoid valves (SV1a), which bypass the high- and low- pressure sides, perform the following functions. (1) Bypass solenoid valve (SV1a) (ON = Open), (SV9) (ON = Open) SV1a Operation When starting-up the compressor of each ON for 4 minutes.
  • Page 103 [ VII Control ] Compressor Frequency Control -6- Compressor Frequency Control Depending on the capacity required, the frequency of the compressor is controlled to keep constant evaporation temperature (0°C [32°F] = 0.71 MPa [103 psi]) during cooling operation, and condensing temperature (49°C [120°F] = 2.88 MPa [418 psi]) during heating operation.
  • Page 104 [ VII Control ] Defrost Operation Control -7- Defrost Operation Control (1) Starting the defrost operation The defrost cycle will start when all of the three conditions (outside temperature, cumulative compressor operation time, and pipe temperature) under <Condition 1>, <Condition 2>, or <Condition 3> are met. Condition 1 Condition 2 Condition 3...
  • Page 105 [ VII Control ] (3) Stopping the defrost operation The defrost cycle ends when 12 minutes have passed since the beginning of the cycle, or when the pipe temperature (TH3) has been continuously detected for 4 minutes (5 minutes on the P450 model)(when SW3-4 is set to OFF) or 2 minutes (when SW3-4 is set to ON) that exceeds the values in the table below.
  • Page 106 [ VII Control ] Refrigerant Recovery Control -8- Refrigerant Recovery Control Recovery of refrigerant is performed during heating operation to prevent the refrigerant from accumulating inside the unit while it is stopped (unit in fan mode), or inside the indoor unit that is in cooling mode or in heating mode with thermo off. It is also performed during cooling operation to prevent an excessive amount of refrigerant from accumulating in the outdoor heat ex- changer.
  • Page 107 [ VII Control ] Subcool Coil Control (Linear Expansion Valve <LEV1>) -10- Subcool Coil Control (Linear Expansion Valve <LEV1>) The OC, OS1, and OS2 controls the subcool coil individually. The LEV is controlled every 30 seconds to maintain constant the subcool at the outdoor unit heat exchanger outlet that is calculated from the values of high pressure (63HS1) and liquid piping temperature (TH3), or the superheat that is calculated from the values of low pressure (63LS) and the bypass outlet temperature (TH2) of the subcool coil.
  • Page 108 [ VII Control ] (2) P500, P550, P600, P650, P700, P750, P800, P850, P900 EP400, EP450, EP500, EP550, EP600 models Initial startup mode starts. The compressor on the OC starts up. 60Hz The total operating load of the indoor unit after 5 minutes of operation is P250 or above.
  • Page 109 [ VII Control ] (3) P950, P1000, P1050, P1100, P1150, P1200, P1250, EP650, EP700, EP750, EP800, EP850, EP900 models Initial startup mode starts. The compressor on the OC starts up. 60Hz The total operating load of the indoor unit after 5 minutes of operation is P250 or above. ( *1 The total operating load of the indoor unit after 5 minutes of operation is between P250 and P1000.
  • Page 110 [ VII Control ] Emergency Operation Mode -13- Emergency Operation Mode 1. Problems with the outdoor unit Emergency operation mode is a temporary operation mode in which the outdoor unit that is not in trouble operates when one of the outdoor units in the P500 through P900/EP400 through EP600 models is in trouble or when one or two of the outdoor units in the P950 through P1250/EP650 througt EP900 models are in trouble.
  • Page 111 [ VII Control ] (2) Ending the emergency operation 1) End conditions When one of the following conditions is met, emergency operation stops, and the unit makes an error stop. When the integrated operation time of compressor in cooling mode has reached four hours. When the integrated operation time of compressor in heating mode has reached two hours.
  • Page 112 [ VII Control ] Emergency operation pattern (2 outdoor units) OC failure OS failure pattern pattern Trouble Normal Normal Trouble Cooling Emergency Permitted Permitted operation Heating Permitted Permitted Capacity that matches Maximum total capacity the total capacity of the of indoor units (Note 1) operable outdoor units Emergency operation pattern (3 outdoor units) OC failure...
  • Page 113 [ VII Control ] DEMAND Control -15- DEMAND Control Cooling/heating operation can be prohibited (Thermo-OFF) by an external input to the indoor units. When DIP SW4-4 is set to ON, the 4-step DEMAND control is enabled. Eight-step demand control is possible in the system with two outdoor units. Twelve-step demand control is possible in the system with three outdoor units.
  • Page 114: Operation Flow Chart

    [ VII Control ] [3] Operation Flow Chart 1. Mode determination flowchart (1) Indoor unit (cooling, heating, dry, fan mode) Start Normal operation Error Breaker Unit in the stopped state turned on From outdoor unit Operation SW turned on 1. Protection function self-holding cancelled.
  • Page 115 [ VII Control ] (2) Outdoor unit (cooling and heating modes) Start Normal operation Error Breaker Unit in the stopped state turned on "HO" / "PLEASE WAIT" blinks on the remote controller *Note 1 Indoor units registered to the remote controller From indoor unit Operation command...
  • Page 116 [ VII Control ] 2. Operations in each mode (1) Cooling operation Cooling operation Normal operation During test run mode 4-way valve OFF Unit in the stopped state Indoor unit fan *Note 1 operation Test run mode Thermostat ON 3-minute restart prevention 1.
  • Page 117 [ VII Control ] (2) Heating operation Normal operation Defrost operation Heating operation Unit in the stopped state *Note 1,2 During test run mode Defrost operation 4-way valve ON 4-way valve OFF 1. Indoor unit fan stops 2. Inverter defrost frequency control Test run mode 3.
  • Page 118 [ VII Control ] (3) Dry operation Dry operation Normal operation Thermostat ON 4-way valve OFF Unit in the stopped state Test run mode *Note 2 Thermostat ON Suction temperature 18°C[64°F] *Note 1 1. Indoor unit fan stop 1. Outdoor unit (compressor) intermittent operation 2.
  • Page 119 [ VII Control ] HWE10040 - 110 -...
  • Page 120: Viii Test Run Mode

    VIII Test Run Mode [1] Items to be checked before a Test Run ................. 113 [2] Test Run Method ......................114 [3] Operating Characteristic and Refrigerant Amount ............115 [4] Adjusting the Refrigerant Amount .................. 115 [5] Refrigerant Amount Adjust Mode................... 118 [6] The following symptoms are normal.
  • Page 121 - 112 -...
  • Page 122: Items To Be Checked Before A Test Run

    [ VIII Test Run Mode ] VIII Test Run Mode [1] Items to be checked before a Test Run (1) Check for refrigerant leak and loose cables and connectors. (2) Measure the insulation resistance between the power supply terminal block and the ground with a 500V megger and make sure it reads at least 1.0Mohm.
  • Page 123: Test Run Method

    [ VIII Test Run Mode ] [2] Test Run Method The figure shows an MA remote controller (PAR-21MAA). ON/OFF button Set Temperature buttons Down Fan Speed button TIME SUN MON TUE WED THU FRI SAT TIMER AFTER AFTER ERROR CODE FUNCTION FILTER WEEKLY...
  • Page 124: Operating Characteristic And Refrigerant Amount

    [ VIII Test Run Mode ] [3] Operating Characteristic and Refrigerant Amount It is important to have a clear understanding of the characteristics of refrigerant and the operating characteristics of air conditioners before attempting to adjust the refrigerant amount in a given system. 1.
  • Page 125 [ VIII Test Run Mode ] 3. Amount of refrigerant to be added The amount of refrigerant that is shown in the table below is factory-charged to the outdoor units. The amount necessary for extended pipe (field piping) is not included and must be added on site. Outdoor unit model P200 P250...
  • Page 126 [ VIII Test Run Mode ] (2) Example: PUHY-P500YSJM-A 9.52 9.52 (3 m) (1 m) 9.52 (10 m) 15.88 (10 m) × Liquid separator 9.52 9.52 9.52 9.52 6.35 (10 m) (20 m) (10 m) (10 m) (10 m) 15.88 (30 m) model model model...
  • Page 127: Refrigerant Amount Adjust Mode

    [ VIII Test Run Mode ] [5] Refrigerant Amount Adjust Mode 1. Procedures Follow the procedures below to add or extract refrigerant as necessary depending on the operation mode. When the function switch (SW4-3) on the main board on the outdoor unit (OC only) is turned to ON, the unit goes into the refrigerant amount adjust mode, and the following sequence is followed.
  • Page 128 [ VIII Test Run Mode ] Start Turn on SW4-3 on the OC. Put all indoor units in the test run mode *Refer to the previous page for *Notes 1-4 in the chart. and run the units in cooling mode. Has the initial start-up mode been completed? Has it been at least...
  • Page 129: The Following Symptoms Are Normal

    [ VIII Test Run Mode ] [6] The following symptoms are normal. Remote controller Symptoms Cause display The indoor unit does not start "Cooling (heating)" The unit cannot perform a heating (cooling) operation when other indoor after starting cooling (heating) icon blinks on the units are performing a cooling (heating) operation.
  • Page 130: Standard Operation Data (Reference Data)

    [ VIII Test Run Mode ] [7] Standard Operation Data (Reference Data) 1. Single unit (1) Cooling operation Outdoor unit model Operation PUHY-P200YJM-A PUHY-P250YJM-A 27°C/ 19°C 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] 35°C/- [95°F/- ] No.
  • Page 131 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P300YJM-A PUHY-P350YJM-A 27°C/ 19°C 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 132 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P400YJM-A PUHY-P450YJM-A 27°C/ 19°C 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 133 [ VIII Test Run Mode ] (2) Heating operation Outdoor unit model Operation PUHY-P200YJM-A PUHY-P250YJM-A Indoor 20°C/- [68°F/- ] 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C 7°C/ 6°C Outdoor ture [45°F/ 43°F] [45°F/ 43°F] No. of connected units Unit Indoor No.
  • Page 134 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P300YJM-A PUHY-P350YJM-A Indoor 20°C/- [68°F/- ] 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C 7°C/ 6°C Outdoor ture [45°F/ 43°F] [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 135 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P400YJM-A PUHY-P450YJM-A Indoor 20°C/- [68°F/- ] 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C 7°C/ 6°C Outdoor ture [45°F/ 43°F] [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 136 [ VIII Test Run Mode ] 2. 2-unit combination (1) Cooling operation Outdoor unit model Operation PUHY-P500YSJM-A PUHY-P250YJM-A PUHY-P250YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 137 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P500YSJM-A1 PUHY-P200YJM-A PUHY-P300YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100...
  • Page 138 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P550YSJM-A PUHY-P250YJM-A PUHY-P300YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/50...
  • Page 139 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P600YSJM-A PUHY-P250YJM-A PUHY-P350YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100...
  • Page 140 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P600YSJM-A1 PUHY-P300YJM-A PUHY-P300YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100...
  • Page 141 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P650YSJM-A PUHY-P300YJM-A PUHY-P350YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100/50...
  • Page 142 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P700YSJM-A PUHY-P350YJM-A PUHY-P350YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100/100...
  • Page 143 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P700YSJM-A1 PUHY-P300YJM-A PUHY-P400YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100/100...
  • Page 144 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P750YSJM-A PUHY-P350YJM-A PUHY-P400YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100/100/50...
  • Page 145 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P800YSJM-A PUHY-P350YJM-A PUHY-P450YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100/100/100...
  • Page 146 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P800YSJM-A1 PUHY-P400YJM-A PUHY-P400YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100/100/100...
  • Page 147 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P850YSJM-A PUHY-P400YJM-A PUHY-P450YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100/100/100/50...
  • Page 148 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P900YSJM-A PUHY-P450YJM-A PUHY-P450YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100/100/100/100...
  • Page 149 [ VIII Test Run Mode ] (2) Heating operation Outdoor unit model Operation PUHY-P500YSJM-A PUHY-P250YJM-A PUHY-P250YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 150 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P500YSJM-A1 PUHY-P200YJM-A PUHY-P300YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100...
  • Page 151 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P550YSJM-A PUHY-P250YJM-A PUHY-P300YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/50...
  • Page 152 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P600YSJM-A PUHY-P250YJM-A PUHY-P350YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100...
  • Page 153 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P600YSJM-A1 PUHY-P300YJM-A PUHY-P300YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100...
  • Page 154 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P650YSJM-A PUHY-P300YJM-A PUHY-P350YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100/50...
  • Page 155 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P700YSJM-A PUHY-P350YJM-A PUHY-P350YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100/100...
  • Page 156 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P700YSJM-A1 PUHY-P300YJM-A PUHY-P400YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100/100...
  • Page 157 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P750YSJM-A PUHY-P350YJM-A PUHY-P400YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100/100/50...
  • Page 158 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P800YSJM-A PUHY-P350YJM-A PUHY-P450YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100/100/100...
  • Page 159 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P800YSJM-A1 PUHY-P400YJM-A PUHY-P400YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100/100/100...
  • Page 160 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P850YSJM-A PUHY-P400YJM-A PUHY-P450YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100/100/100/50...
  • Page 161 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-P900YSJM-A PUHY-P450YJM-A PUHY-P450YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100/100/100/100...
  • Page 162 [ VIII Test Run Mode ] 3. 3-unit combination (1) Cooling operation Outdoor unit model PUHY-P950YSJM-A Operation PUHY- PUHY- PUHY- P250YJM-A P300YJM-A P400YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No.
  • Page 163 [ VIII Test Run Mode ] Outdoor unit model PUHY-P1000YSJM-A Operation PUHY- PUHY- PUHY- P300YJM-A P300YJM-A P400YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 164 [ VIII Test Run Mode ] Outdoor unit model PUHY-P1050YSJM-A Operation PUHY- PUHY- PUHY- P300YJM-A P350YJM-A P400YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 165 [ VIII Test Run Mode ] Outdoor unit model PUHY-P1100YSJM-A Operation PUHY- PUHY- PUHY- P350YJM-A P350YJM-A P400YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 166 [ VIII Test Run Mode ] Outdoor unit model PUHY-P1150YSJM-A Operation PUHY- PUHY- PUHY- P350YJM-A P350YJM-A P450YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 167 [ VIII Test Run Mode ] Outdoor unit model PUHY-P1200YSJM-A Operation PUHY- PUHY- PUHY- P350YJM-A P400YJM-A P450YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 168 [ VIII Test Run Mode ] Outdoor unit model PUHY-P1250YSJM-A Operation PUHY- PUHY- PUHY- P350YJM-A P450YJM-A P450YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 169 [ VIII Test Run Mode ] (2) Heating operation Outdoor unit model PUHY-P950YSJM-A Operation PUHY- PUHY- PUHY- P250YJM-A P300YJM-A P400YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 170 [ VIII Test Run Mode ] Outdoor unit model PUHY-P1000YSJM-A Operation PUHY- PUHY- PUHY- P300YJM-A P300YJM-A P400YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 171 [ VIII Test Run Mode ] Outdoor unit model PUHY-P1050YSJM-A Operation PUHY- PUHY- PUHY- P300YJM-A P350YJM-A P400YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 172 [ VIII Test Run Mode ] Outdoor unit model PUHY-P1100YSJM-A Operation PUHY- PUHY- PUHY- P350YJM-A P350YJM-A P400YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 173 [ VIII Test Run Mode ] Outdoor unit model PUHY-P1150YSJM-A Operation PUHY- PUHY- PUHY- P350YJM-A P350YJM-A P450YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 174 [ VIII Test Run Mode ] Outdoor unit model PUHY-P1200YSJM-A Operation PUHY- PUHY- PUHY- P350YJM-A P400YJM-A P450YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 175 [ VIII Test Run Mode ] Outdoor unit model PUHY-P1250YSJM-A Operation PUHY- PUHY- PUHY- P350YJM-A P450YJM-A P450YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 176 [ VIII Test Run Mode ] 4. Single unit (High-COP) (1) Cooling operation Outdoor unit model Operation PUHY-EP200YJM-A PUHY-EP250YJM-A 27°C/ 19°C 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] 35°C/- [95°F/- ] No. of connected units Unit Indoor...
  • Page 177 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-EP300YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100 Main pipe 5 [17]...
  • Page 178 [ VIII Test Run Mode ] (2) Heating operation Outdoor unit model Operation PUHY-EP200YJM-A PUHY-EP250YJM-A Indoor 20°C/- [68°F/- ] 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C 7°C/ 6°C Outdoor ture [45°F/ 43°F] [45°F/ 43°F] No. of connected units Unit Indoor No.
  • Page 179 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-EP300YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100 Main pipe 5 [17]...
  • Page 180 [ VIII Test Run Mode ] 5. 2-unit combination (1) Cooling operation Outdoor unit model Operation PUHY-EP400YSJM-A PUHY-EP200YJM-A PUHY-EP200YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 181 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-EP450YSJM-A PUHY-EP200YJM-A PUHY-EP250YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/50...
  • Page 182 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-EP500YSJM-A PUHY-EP200YJM-A PUHY-EP300YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100...
  • Page 183 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-EP500YSJM-A1 PUHY-EP250YJM-A PUHY-EP250YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100...
  • Page 184 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-EP550YSJM-A PUHY-EP250YJM-A PUHY-EP300YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/50...
  • Page 185 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-EP600YSJM-A PUHY-EP300YJM-A PUHY-EP300YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100...
  • Page 186 [ VIII Test Run Mode ] (2) Heating operation Outdoor unit model Operation PUHY-EP400YSJM-A PUHY-EP200YJM-A PUHY-EP200YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 187 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-EP450YSJM-A PUHY-EP200YJM-A PUHY-EP250YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/50...
  • Page 188 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-EP500YSJM-A PUHY-EP200YJM-A PUHY-EP300YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100...
  • Page 189 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-EP500YSJM-A1 PUHY-EP250YJM-A PUHY-EP250YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100...
  • Page 190 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-EP550YSJM-A PUHY-EP250YJM-A PUHY-EP300YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/50...
  • Page 191 [ VIII Test Run Mode ] Outdoor unit model Operation PUHY-EP600YSJM-A PUHY-EP300YJM-A PUHY-EP300YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating conditions Model 100/100/100/100/100/100...
  • Page 192 [ VIII Test Run Mode ] 6. 3-unit combination (1) Cooling operation Outdoor unit model PUHY-EP650YSJM-A Operation PUHY- PUHY- PUHY- EP200YJM-A EP200YJM-A EP250YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No.
  • Page 193 [ VIII Test Run Mode ] Outdoor unit model PUHY-EP700YSJM-A Operation PUHY- PUHY- PUHY- EP200YJM-A EP200YJM-A EP300YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 194 [ VIII Test Run Mode ] Outdoor unit model PUHY-EP700YSJM-A1 Operation PUHY- PUHY- PUHY- EP200YJM-A EP250YJM-A EP250YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 195 [ VIII Test Run Mode ] Outdoor unit model PUHY-EP750YSJM-A Operation PUHY- PUHY- PUHY- EP200YJM-A EP250YJM-A EP300YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 196 [ VIII Test Run Mode ] Outdoor unit model PUHY-EP750YSJM-A1 Operation PUHY- PUHY- PUHY- EP250YJM-A EP250YJM-A EP250YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 197 [ VIII Test Run Mode ] Outdoor unit model PUHY-EP800YSJM-A Operation PUHY- PUHY- PUHY- EP200YJM-A EP300YJM-A EP300YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 198 [ VIII Test Run Mode ] Outdoor unit model PUHY-EP800YSJM-A1 Operation PUHY- PUHY- PUHY- EP250YJM-A EP250YJM-A EP300YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 199 [ VIII Test Run Mode ] Outdoor unit model PUHY-EP850YSJM-A Operation PUHY- PUHY- PUHY- EP250YJM-A EP300YJM-A EP300YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 200 [ VIII Test Run Mode ] Outdoor unit model PUHY-EP900YSJM-A Operation PUHY- PUHY- PUHY- EP300YJM-A EP300YJM-A EP300YJM-A 27°C/ 19°C Ambient Indoor tempera- DB/WB [81°F/ 66°F] ture Outdoor 35°C/- [95°F/- ] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 201 [ VIII Test Run Mode ] (2) Heating operation Outdoor unit model PUHY-EP650YSJM-A Operation PUHY- PUHY- PUHY- EP200YJM-A EP200YJM-A EP250YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 202 [ VIII Test Run Mode ] Outdoor unit model PUHY-EP700YSJM-A Operation PUHY- PUHY- PUHY- EP200YJM-A EP200YJM-A EP300YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 203 [ VIII Test Run Mode ] Outdoor unit model PUHY-EP700YSJM-A1 Operation PUHY- PUHY- PUHY- EP200YJM-A EP250YJM-A EP250YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 204 [ VIII Test Run Mode ] Outdoor unit model PUHY-EP750YSJM-A Operation PUHY- PUHY- PUHY- EP200YJM-A EP250YJM-A EP300YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 205 [ VIII Test Run Mode ] Outdoor unit model PUHY-EP750YSJM-A1 Operation PUHY- PUHY- PUHY- EP250YJM-A EP250YJM-A EP250YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 206 [ VIII Test Run Mode ] Outdoor unit model PUHY-EP800YSJM-A Operation PUHY- PUHY- PUHY- EP200YJM-A EP300YJM-A EP300YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 207 [ VIII Test Run Mode ] Outdoor unit model PUHY-EP800YSJM-A1 Operation PUHY- PUHY- PUHY- EP250YJM-A EP250YJM-A EP300YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 208 [ VIII Test Run Mode ] Outdoor unit model PUHY-EP850YSJM-A Operation PUHY- PUHY- PUHY- EP250YJM-A EP300YJM-A EP300YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 209 [ VIII Test Run Mode ] Outdoor unit model PUHY-EP900YSJM-A Operation PUHY- PUHY- PUHY- EP300YJM-A EP300YJM-A EP300YJM-A Indoor 20°C/- [68°F/- ] Ambient tempera- DB/WB 7°C/ 6°C Outdoor ture [45°F/ 43°F] No. of connected units Unit Indoor No. of units in opera- unit tion Operating...
  • Page 210: Ix Troubleshooting

    IX Troubleshooting [1] Error Code Lists ......................203 [2] Responding to Error Display on the Remote Controller..........206 [3] Investigation of Transmission Wave Shape/Noise............271 [4] Troubleshooting Principal Parts ..................274 [5] Refrigerant Leak ......................294 [6] Compressor Replacement Instructions................296 [7] Troubleshooting Using the Outdoor Unit LED Error Display..........
  • Page 211 - 202 -...
  • Page 212: Error Code Lists

    [ IX Troubleshooting ] IX Troubleshooting [1] Error Code Lists Searched unit Error Prelimi- (prelim- Error nary inary) Error code definition Notes Code error detail code code 4300 0403 Serial communication error 4305 (Note) 0900 Test run 1102 1202 Discharge temperature fault 1301 Low pressure fault 1302...
  • Page 213 [ IX Troubleshooting ] Searched unit Error Prelimi- (prelim- Error nary inary) Error code definition Notes Code error detail code code Indoor unit pipe tempera- ture (TH22) Temperature sensor OA processing unit pipe 5102 1217 fault temperature (TH2) HIC bypass circuit outlet temperature (TH2) Indoor unit gas-side pipe temperature (TH23)
  • Page 214 [ IX Troubleshooting ] Searched unit Error Prelimi- (prelim- Error nary inary) Error code definition Notes Code error detail code code 6608 No response error MA controller signal reception error (No signal re- 6831 ception) MA remote controller signal transmission error 6832 (Synchronization error) MA remote controller signal transmission error...
  • Page 215: Responding To Error Display On The Remote Controller

    [ IX Troubleshooting ] [2] Responding to Error Display on the Remote Controller 0403 1. Error Code 0403 Serial communication error 2. Error definition and error detection method Serial communication error between the control board and the INV board on the compressor, and between the control board and the Fan board Detail code 01: Between the control board and the INV board Detail code 05: Between the control board and the Fan board...
  • Page 216 [ IX Troubleshooting ] 1102 1. Error Code 1102 Discharge temperature fault 2. Error definition and error detection method 1) If the discharge temperature of 120 °C [248°F] or more is detected during the above operation (the first detection), the outdoor unit stops once, turns to anti-restart mode for 3 minutes, and restarts after 3 minutes automatically.
  • Page 217 [ IX Troubleshooting ] 1301 1. Error Code 1301 Low pressure fault 2. Error definition and error detection method When starting the compressor from Stop Mode for the first time if low pressure reads 0.098MPa [14psi] immediately before start-up, the operation immediately stops. 3.
  • Page 218 [ IX Troubleshooting ] 1302 1. Error Code 1302 High pressure fault 1 (Outdoor unit) 2. Error definition and error detection method 1) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor during operation (the first detection), the out- door stops once, turns to antirestart mode for 3 minutes, and restarts after 3 minutes automatically.
  • Page 219 [ IX Troubleshooting ] 1. Error Code 1302 High pressure fault 2 (Outdoor unit) 2. Error definition and error detection method If the pressure of 0.098MPa [14psi] or lower is registered on the pressure sensor immediately before start-up, it will trigger an abnormal stop, and error code "1302"...
  • Page 220 [ IX Troubleshooting ] 2500 1. Error Code 2500 Drain sensor submergence (Models with a drain sensor) 2. Error definition and error detection method 1) If an immersion of the drain sensor in the water is detected while the unit is in any mode other than the Cool/Dry mode and when the drain pump goes from OFF to ON, this condition is considered preliminary water leakage.
  • Page 221 [ IX Troubleshooting ] 1. Error Code 2500 Drain sensor submergence (Models with a float switch) 2. Error definition and error detection method 1) If an immersion of the float switch in the water is detected while the unit is in any mode other than the Cool/Dry mode and when the drain pump goes from OFF to ON, this condition is considered preliminary water leakage.
  • Page 222 [ IX Troubleshooting ] 2502 1. Error Code 2502 Drain pump fault (Models with a drain sensor) 2. Error definition and error detection method 1) Make the drain sensor thermistor self-heat. If the temperature rise is small, it is interpreted that the sensor is immersed in water.
  • Page 223 [ IX Troubleshooting ] 1. Error Code 2502 Drain pump fault (Models with a float switch) 2. Error definition and error detection method 1) The immersion of sensor tip in water is detected by the ON/OFF signal from the float switch. ∗Submergence of the sensor When it is detected that the float switch has been ON for 15 seconds, it is interpreted that the sensor tip is immersed in water.
  • Page 224 [ IX Troubleshooting ] 2503 1. Error Code 2503 Drain sensor (Thd) fault 2. Error definition and error detection method If the open or short circuit of the thermistor has been detected for 30 seconds, this condition is considered to be a preliminary error, and the unit goes into the 3-minute restart delay mode.
  • Page 225 [ IX Troubleshooting ] 2600 1. Error Code 2600 Water leakage 2. Cause, check method and remedy Check that water does not leak from the pipes in such as the humidifier. 2601 1. Error Code 2601 Water supply cutoff 2. Cause, check method and remedy Cause Check method and remedy The water tank of the humidifier is empty.
  • Page 226 [ IX Troubleshooting ] 3121 1. Error Code 3121 Out-of-range outside air temperature 2. Error definition and error detection method When the thermistor temperature of -28°C[-18°F] or below has continuously been detected for 3 minutes during heating op- eration (during compressor operation), the unit makes an error stop and "3121" appears on the display. (Use the OC therm- istor temperature to determine when two outdoor units are in operation.) The compressor restarts when the thermistor temperature is -26°C[-15°F] or above (both OC and OS) during error stop.
  • Page 227 [ IX Troubleshooting ] 4102 1. Error Code 4102 Open phase 2. Error definition and error detection method An open phase of the power supply (L1 phase, N phase) was detected at power on. The L3 phase current is outside of the specified range. The open phase of the power supply may not always be detected if a power voltage from another circuit is applied.
  • Page 228 [ IX Troubleshooting ] 4106 1. Error Code 4106 <Transmission power supply fault Error detail code FF (Outdoor unit)> 2. Error definition and error detection method Transmission power output failure 3. Cause 1) Wiring failure 2) Transmission power supply cannot output voltage because overcurrent was detected. 3) Voltage cannot be output due to transmission power supply problem.
  • Page 229 [ IX Troubleshooting ] 4115 1. Error Code 4115 Power supply signal sync error 2. Error definition and error detection method The frequency cannot be determined when the power is switched on. 3. Cause, check method and remedy Cause Check method and remedy Power supply error Check the voltage of the power supply terminal block (TB1).
  • Page 230 [ IX Troubleshooting ] 4220?4225 1. Error Code 4220 4225 Abnormal bus voltage drop (Detail code 108) 2. Error definition and error detection method If Vdc 289V or less is detected during Inverter operation. (S/W detection) 3. Cause, check method and remedy (1) Power supply environment Check whether the unit makes an instantaneous stop when the detection result is abnormal or a power failure occurs.
  • Page 231 [ IX Troubleshooting ] 1. Error Code 4220 4225 Abnormal bus voltage rise (Detail code 109) 2. Error definition and error detection method If Vdc 830V is detected during inverter operation. 3. Cause, check method and remedy (1) Different voltage connection Check the power supply voltage on the power supply terminal block (TB1).
  • Page 232 [ IX Troubleshooting ] 1. Error Code 4220 4225 Low bus voltage at startup (Detail code 131) 2. Error definition and error detection method When Vdc 160 V is detected just before the inverter operation. 3. Cause, check method and remedy (1) Inverter main circuit failure Same as detail code 108 of 4220 error Refer to section -6- "Inverter"...
  • Page 233 [ IX Troubleshooting ] 4240 1. Error Code 4240 Overload protection 2. Error definition and error detection method If the output current of "(Iac) >Imax (Arms)" or "THHS > 100°C [212°F] " is continuously detected for 10 minutes or more during inverter operation.
  • Page 234 [ IX Troubleshooting ] 4250?4250 4255 1. Error Code 4250 4255 IPM error (Detail code 101) 2. Error definition and error detection method In the case of 4250 Overcurrent is detected by the overcurrent detection resistor (RSH) on the INV board. In the case of 4255 IPM error signal is detected.
  • Page 235 [ IX Troubleshooting ] 1. Error Code 4250 Instantaneous overcurrent (Detail code 106) Overcurrent (Detail code 107) 2. Error definition and error detection method P200, P250, and EP200 models Overcurrent 94 Apeak or 22 Arms and above is detected by the current sensor. P300 - P450, EP250, and EP300 models Overcurrent 94 Apeak or 35 Arms and above is detected by the current sensor.
  • Page 236 [ IX Troubleshooting ] 1. Error Code 4250 4255 Overcurrent error due to short-circuited motor (Detail code 105) 2. Error definition and error detection method When a short is detected on the load side just before starting the inverter operation. 3.
  • Page 237 [ IX Troubleshooting ] 5101,5102,5103,5104 1. Error Code 5101 Return air temperature sensor (TH21) fault (Indoor unit) Return air temperature sensor (TH4) fault (OA processing unit) 5102 Pipe temperature sensor (TH22) fault (Indoor unit) Pipe temperature sensor (TH2) fault (OA processing unit) 5103 Gas-side pipe temperature sensor (TH23) fault (Indoor unit) Gas-side pipe temperature sensor (TH3) fault (OA processing unit)
  • Page 238 [ IX Troubleshooting ] 5102,5103,5104,5105,5106,5107?5103,5104,5105,5106,5107 1. Error Code 5102 HIC bypass circuit outlet temperature sensor (TH2) fault (Outdoor unit) 5103 Heat exchanger outlet temperature sensor (TH3) fault (Outdoor unit) 5104 Discharge temperature sensor (TH4) fault (Outdoor unit) 5105 Accumulator inlet temperature sensor (TH5) fault (Outdoor unit) 5106 HIC circuit outlet temperature sensor (TH6) fault (Outdoor unit) 5107...
  • Page 239 [ IX Troubleshooting ] 5110 1. Error Code 5110 Heatsink temperature sensor (THHS) fault (Detail code 01) 2. Error definition and error detection method When a short or an open of THHS is detected just before or during the inverter operation. 3.
  • Page 240 [ IX Troubleshooting ] 5301 1. Error Code 5301 ACCT sensor fault (Detail code 115) 2. Error definition and error detection method When the formula "output current < 1.5 Arms" remains satisfied for 10 seconds while the inverter is in operation. 3.
  • Page 241 [ IX Troubleshooting ] 1. Error Code 5301 Open-circuited IPM/Loose ACCT connector (Detail code 119) 2. Error definition and error detection method Presence of enough current cannot be detected during the self-diagnostic operation immediately before inverter startup. 3. Cause, check method and remedy Cause Check method and remedy Inverter output wiring problem...
  • Page 242 [ IX Troubleshooting ] 5701 1. Error Code 5701 Loose float switch connector 2. Error definition and error detection method Detection of the disconnected float switch (open-phase condition) during operation 3. Cause, check method and remedy (1) CN4F disconnection or contact failure Check for disconnection of the connector (CN4F) on the indoor unit control board.
  • Page 243 [ IX Troubleshooting ] 6600 1. Error Code 6600 Address overlap 2. Error definition and error detection method An error in which signals from more than one indoor units with the same address are received The address and attribute that appear on the remote controller indicate the controller that detected the error. 3.
  • Page 244 [ IX Troubleshooting ] 6602 1. Error Code 6602 Transmission processor hardware error 2. Error definition and error detection method Although "0" was surely transmitted by the transmission processor, "1" is displayed on the transmission line. The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.
  • Page 245 [ IX Troubleshooting ] 6603 1. Error Code 6603 Transmission line bus busy error 2. Error definition and error detection method Generated error when the command cannot be transmitted for 4-10 minutes in a row due to bus-busy Generated error when the command cannot be transmitted to the transmission line for 4-10 minutes in a row due to noise The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.
  • Page 246 [ IX Troubleshooting ] 6607 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
  • Page 247 [ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
  • Page 248 [ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
  • Page 249 [ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
  • Page 250 [ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
  • Page 251 [ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
  • Page 252 [ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
  • Page 253 [ IX Troubleshooting ] 1. Error Code 6607 No ACK error 2. Error definition and error detection method The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans- mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.) The address/attribute appeared on the display on the remote controller indicates the controller which did not provide the response (ACK).
  • Page 254 [ IX Troubleshooting ] 6608 1. Error Code 6608 No response error 2. Error definition and error detection method When no response command is returned although acknowledgement (ACK) is received after transmission, an error is detect- When the data is transmitted 10 times in a row with 3 seconds interval, an error is detected on the transmission side. The address/attribute appeared on the display on the remote controller indicates the controller where an error oc- curred.
  • Page 255 [ IX Troubleshooting ] 6831 1. Error Code 6831 MA controller signal reception error (No signal reception) 2. Error definition and error detection method Communication between the MA remote controller and the indoor unit is not done properly. No proper data has been received for 3 minutes. 3.
  • Page 256 [ IX Troubleshooting ] 6832 1. Error Code 6832 MA remote controller signal transmission error (Synchronization error) 2. Error definition and error detection method MA remote controller and the indoor unit is not done properly. Failure to detect opening in the transmission path and unable to send signals ∗Indoor unit : 3 minutes ∗Remote controller : 6 seconds 3.
  • Page 257 [ IX Troubleshooting ] 6833 1. Error Code 6833 MA remote controller signal transmission error (Hardware error) 2. Error definition and error detection method Communication between the MA remote controller and the indoor unit is not done properly. An error occurs when the transmitted data and the received data differ for 30 times in a row. 3.
  • Page 258 [ IX Troubleshooting ] 6834 1. Error Code 6834 MA controller signal reception error (Start bit detection error) 2. Error definition and error detection method Communication between the MA remote controller and the indoor unit is not done properly. No proper data has been received for 2 minutes. 3.
  • Page 259 [ IX Troubleshooting ] 7100 1. Error Code 7100 Total capacity error 2. Error definition and error detection method The model total of indoor units in the system with one outdoor unit exceeds limitations. 3. Error source, cause, check method and remedy, Error source Cause Check method and remedy...
  • Page 260 [ IX Troubleshooting ] 7101 1. Error Code 7101 Capacity code setting error 2. Error definition and error detection method Connection of incompatible (wrong capacity code) indoor unit or outdoor unit 3. Error source, cause, check method and remedy Error source Cause Check method and remedy Outdoor unit...
  • Page 261 [ IX Troubleshooting ] 7102 1. Error Code 7102 Wrong number of connected units 2. Error definition and error detection method The number of connected indoor units is "0" or exceeds the allowable value. 3. Error source, cause, check method and remedy Error source Cause Check method and remedy...
  • Page 262 [ IX Troubleshooting ] 7105 1. Error Code 7105 Address setting error 2. Error definition and error detection method Erroneous setting of OC unit address 3. Cause, check method and remedy Error source Cause Check method and remedy Outdoor unit Erroneous setting of OC unit address Check that the address of OC unit is set to 51- The address of outdoor unit is not being set to 51 -...
  • Page 263 [ IX Troubleshooting ] 7110 1. Error Code 7110 Connection information signal transmission/reception error 2. Error definition and error detection method The given indoor unit is inoperable because it is not properly connected to the outdoor unit in the same system. 3.
  • Page 264 [ IX Troubleshooting ] 7113 1. Error Code 7113 Function setting error (incorrect resistor connection) 2. Error source, cause, check method and remedy Error source Cause Check method and remedy Outdoor unit Wiring fault (Detail code 15) Loose connectors, short-circuit, con- Check the connector CNTYP5 on the control board for tact failure proper connection.
  • Page 265 [ IX Troubleshooting ] 7117 1. Error Code 7117 Model setting error 2. Error source, cause, check method and remedy Error source Cause Check method and remedy Outdoor unit Wiring fault (Detail code 15) Loose connectors, short-circuit, con- Check the connector CNTYP5 on the control board for tact failure proper connection.
  • Page 266 [ IX Troubleshooting ] 7130 1. Error Code 7130 Incompatible unit combination 2. Error definition and error detection method The check code will appear when the indoor units with different refrigerant systems are connected. 3. Error source, cause, check method and remedy Error source Cause Check method and remedy...
  • Page 267 [ IX Troubleshooting ] Troubleshooting according to the remote controller malfunction or the external input error In the case of MA remote controller -1- Troubleshooting according to the remote controller malfunction or the external input error In the case of MA remote controller 1.
  • Page 268 [ IX Troubleshooting ] In the case of MA remote controller 2. Phenomena When the remote controller operation SW is turned on, the operation status briefly appears on the display, then it goes off, and the display lights out immediately, and the unit stops. (1) Cause 1) The power for the M-NET transmission line is not supplied from the outdoor unit.
  • Page 269 [ IX Troubleshooting ] In the case of MA remote controller 3. Phenomena "HO" or "PLEASE WAIT" display on the remote controller does not disappear, and no operation is performed even if the button is pressed. ("HO" or "PLEASE WAIT" display will normally turn off 5 minutes later after the power on.) (1) Cause 1) The power for the M-NET transmission line is not supplied from the outdoor unit.
  • Page 270 [ IX Troubleshooting ] Flow chart Even if the operation button on the remote controller is pressed, the indoor and the outdoor units do not start running. HWE10040 - 261 -...
  • Page 271 [ IX Troubleshooting ] Troubleshooting according to the remote controller malfunction or the external input error In case of ME remote controller In case of ME remote controller 1. Phenomena Even if the operation button on the remote controller is pressed, the display remains unlit and the unit does not start running. (Power indicator does not appear on the screen.) (1) Cause...
  • Page 272 [ IX Troubleshooting ] In case of ME remote controller 2. Phenomena When the remote controller operation SW is turned on, a temporary operation display is indicated, and the display lights out immediately. (1) Cause 1) The power is not supplied to the indoor unit. The main power of the indoor unit (AC220V) is not on.
  • Page 273 [ IX Troubleshooting ] In case of ME remote controller 3. Phenomena "HO" display on the remote controller does not disappear, and no operation is performed even if the button is pressed. (1) Cause Without using MELANS 1) Outdoor unit address is set to "00" 2) A wrong address is set.
  • Page 274 [ IX Troubleshooting ] In case of ME remote controller 4. Phenomena "88" appears on the remote controller when the address is registered or confirmed. (1) Cause, check method and remedy Cause Check method and remedy An error occurs when the address is registered or con- firmed.
  • Page 275 [ IX Troubleshooting ] Troubleshooting according to the remote controller malfunction or the external input error Both for MA remote controller and ME remote controller Both for MA remote controller and ME remote controller 1. Phenomena Although cooling operation starts with the normal remote controller display, the capacity is not enough (1) Cause, check method and remedy Cause Check method and remedy...
  • Page 276 [ IX Troubleshooting ] Cause Check method and remedy Long piping length Check the piping length to determine if it is contrib- The cooling capacity varies greatly depending on the uting to performance loss. pressure loss. (When the pressure loss is large, the Piping pressure loss can be estimated from the cooling capacity drops.) temperature difference between the indoor unit...
  • Page 277 [ IX Troubleshooting ] 2. Phenomena Although heating operation starts with the normal remote controller display, the capacity is not enough. (1) Cause, check method and remedy Cause Check method and remedy Compressor frequency does not rise sufficiently. Check pressure difference between the detected pressure by the pressure sensor and the actual Faulty detection of pressure sensor.
  • Page 278 [ IX Troubleshooting ] Cause Check method and remedy Indoor unit LEV malfunction Refer to the page of LEV troubleshooting ([4] -5- Insufficient refrigerant flows due to LEV malfunction ).(page 279) (not enough opening). Temperature reading error on the indoor unit piping Check the thermistor.
  • Page 279 [ IX Troubleshooting ] 3. Phenomena Outdoor unit stops at times during operation. (1) Cause, check method and remedy Cause Check method and remedy The first stop is not considered as an error, as the Check the mode operated in the past by displaying unit turns to anti-restart mode for 3 minutes as a pre- preliminary error history on LED display with SW1.
  • Page 280: Investigation Of Transmission Wave Shape/Noise

    [ IX Troubleshooting ] [3] Investigation of Transmission Wave Shape/Noise 1. M-NET transmission Control is performed by exchanging signals between the outdoor unit and the indoor unit (ME remote controller) through M- NET transmission. Noise interference on the transmission line will interrupt the normal transmission, leading to erroneous op- eration.
  • Page 281 [ IX Troubleshooting ] (3) Check method and remedy 1) Measures against noise Check the followings when noise exists on the wave or the errors described in (1) occur. Error code definition Remedy Check that the wiring 1. The transmission line and Isolate the transmission line from the power line (5cm [1-31/32"] or work is performed ac- the power line are not...
  • Page 282 [ IX Troubleshooting ] 2. MA remote controller transmission The communication between the MA remote controller and the indoor unit is performed with current tone burst. (1) Symptoms caused by noise interference on the transmission line If noise is generated on the transmission line, and the communication between the MA remote controller and the indoor unit is interrupted for 3 minutes in a row, MA transmission error (6831) will occur.
  • Page 283: Troubleshooting Principal Parts

    [ IX Troubleshooting ] [4] Troubleshooting Principal Parts High-Pressure Sensor -1- High-Pressure Sensor (63HS1) 1. Compare the pressure that is detected by the high pressure sensor, and the high-pressure gauge pressure to check for failure. By configuring the digital display setting switch (SW1) as shown in the figure below, the pressure as measured by the high- pressure sensor appears on the LED1 on the control board.
  • Page 284 [ IX Troubleshooting ] Low-Pressure Sensor -2- Low-Pressure Sensor (63LS) 1. Compare the pressure that is detected by the low pressure sensor, and the low pressure gauge pressure to check for failure. By configuring the digital display setting switch (SW1) as shown in the figure below, the pressure as measured by the low- pressure sensor appears on the LED1 on the control board.
  • Page 285 [ IX Troubleshooting ] Solenoid Valve -3- Solenoid Valve Check whether the output signal from the control board and the operation of the solenoid valve match. Setting the self-diagnosis switch (SW1) as shown in the figure below causes the ON signal of each relay to be output to the LED's. Each LED shows whether the relays for the following parts are ON or OFF.
  • Page 286 [ IX Troubleshooting ] (3) In case of SV1a (Bypass valve) This solenoid valve opens when powered (Relay ON). 1) At compressor start-up, the SV1a turns on for 4 minutes, and the operation can be checked by the self-diagnosis LED display and the closing sound.
  • Page 287 [ IX Troubleshooting ] Is the wiring between the Correct the wiring according to the wiring FAN board, 52F, and fan motor connected correctly? diagram. Does 52F operate on the Replace 52F. coil voltage (206-252V)? Is a voltage of between 188V and 253V (TJMU) or between 414V and 506V (YJMU) applied to the power supply input? Correct the wiring according to the...
  • Page 288 [ IX Troubleshooting ] -5- LEV LEV operation LEV (Indoor unit: Linear expansion valve), LEV2 (Outdoor unit: Linear expansion valve) are stepping-motor-driven valves that operate by receiving the pulse signals from the indoor and outdoor unit control boards. (1) Indoor LEV and Outdoor LEV (LEV2a, LEV2b) The valve opening changes according to the number of pulses.
  • Page 289 [ IX Troubleshooting ] 4) LEV closing and opening operation *Upon power on, the indoor unit circuit board sends a 2200 pulse signal to the indoor unit LEV and a 3200 pulse signal to the outdoor unit LEV to determine the valve position and always brings the valve to the position as indicated by "...
  • Page 290 [ IX Troubleshooting ] (2) Outdoor LEV (LEV1) The valve opening changes according to the number of pulses. 1) Connections between the outdoor control board and LEV1 (outdoor expansion valve) Outdoor control board DC 12V Brown Drive circuit Blue Orange Yellow White 2) Pulse signal output and valve operation...
  • Page 291 [ IX Troubleshooting ] (3) Judgment methods and possible failure mode The specifications of the outdoor unit (outdoor LEV) and the indoor unit (indoor LEV) differ.Therefore, remedies for each failure may vary. Check the remedy specified for the appropriate LEV as indicated in the right column. Malfunction Judgment method Remedy...
  • Page 292 [ IX Troubleshooting ] (4) Outdoor unit LEV (LEV1) coil removal procedure 1) LEV component As shown in the figure, the outdoor LEV is made in such a way that the coils and the body can be separated. Body Coils Stopper Lead wire 2) Removing the coils...
  • Page 293 [ IX Troubleshooting ] (5) Removal procedure of outdoor unit LEV2 coil 1) Components The outdoor unit LEV consists of a coil and a valve body that can be separated from each other. Body Stopper Coil Lead wire 2) Removing the coil Securely hold the LEV at the bottom (as indicated by A in the figure), and turn the coil.
  • Page 294 [ IX Troubleshooting ] Inverter -6- Inverter Replace only the compressor if only the compressor is found to be defective. Replace only the fan motor if only the fan motor is found to be defective. Replace the defective components if the inverter is found to be defective. If both the compressor and the inverter are found to be defective, replace the defective component(s) of both devices.
  • Page 295 [ IX Troubleshooting ] Error display/failure condition Measure/inspection item Inverter related errors Check the details of the inverter error in the error log at X LED Monitor 4250, 4255, 4220, 4225, 4230, 4240,4260, 5301, 0403 Display on the Outdoor Unit Board. Take appropriate measures to the error code and the error details in ac- cordance with IX [2] Responding to Error Display on the Remote Con- troller.
  • Page 296 [ IX Troubleshooting ] (2) Inverter output related troubles Items to be checked Phenomena Remedy Disconnect the invert- Overcurrent error Replace the INV board. Check the er output wire from (4250 Detail code No. 101, 104, 105, 106, and 107) INV board er- the terminals of the ror detection...
  • Page 297 [ IX Troubleshooting ] Items to be checked Phenomena Remedy Put the outdoor unit into oper- Overcurrent-related problems oc- a. Check items [1] through [3] Check whether ation. cur immediately after compressor for problems. the inverter is Check the inverter output volt- startup.
  • Page 298 [ IX Troubleshooting ] (3) Trouble treatment when the main power breaker is tripped Items to be checked Phenomena Remedy Check the breaker capacity. Use of a non-specified break- Replace it with a specified breaker. Perform Meg check between the Zero to several ohm, or Meg Check each part and wiring.
  • Page 299 [ IX Troubleshooting ] (5) Simple checking procedure for individual components of main inverter circuit Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less. Part name Judgment method IGBT module...
  • Page 300 [ IX Troubleshooting ] Judgment value (reference) Black ( + ) SC-P1 FT-N SC-L1 SC-L2 SC-L3 SC-P1 5 - 200 ohm 5 - 200 ohm 5 - 200 ohm FT-N Red (-) SC-L1 5 - 200 ohm SC-L2 5 - 200 ohm SC-L3 5 - 200 ohm Black ( + )
  • Page 301: Indoor Unit

    [ IX Troubleshooting ] Control Circuit -7- Control Circuit (1) Control power source function block Power source system (AC 380 / 415 V) Control system (DC 5 ~ 30 V) INV board Noise filter Compressor Rectifier Smoothing capacitor Inverter Noise filter AC 380/ 415V Fuse Terminal block for...
  • Page 302 [ IX Troubleshooting ] (2) Troubleshooting transmission power circuit of outdoor unit Check the voltage at the indoor/outdoor transmission terminal block (TB3) of outdoor unit. DC 24 ~ 30 V Check whether the transmission line is disconnected, check for contact failure, and repair the problem. Check the voltage at TB3 after removing transmission line from TB3.
  • Page 303: Refrigerant Leak

    [ IX Troubleshooting ] [5] Refrigerant Leak 1. Leak spot: In the case of extension pipe for indoor unit (Cooling season) 1) Mount a pressure gauge on the service check joint (CJ2) on the low-pressure side. 2) Stop all the indoor units, and close the liquid service valve (BV2) inside the outdoor unit while the compressor is being stopped. 3) Stop all the indoor units;...
  • Page 304 [ IX Troubleshooting ] 2) Therefore, if the power source is turned off within 30 minutes, the lev remains fully closed and the refrigerant remains sealed. When only the power for the indoor unit is turned off, the indoor unit LEV turns from faintly open to fully closed. 3) In the cooling cycle, the section between "21S4b, c"...
  • Page 305: Compressor Replacement Instructions

    [ IX Troubleshooting ] [6] Compressor Replacement Instructions [Compressor replacement procedures] Follow the procedures below (Steps 1 through 6) to remove the compressor components and replace the compressor. Reassemble them in the reverse order after replacing the compressor. 1. Remove both the top and bottom service panels 2.
  • Page 306 [ IX Troubleshooting ] Compressor covers (right and left) (The inside of the compressor cover is lined with sound insulation material.) Compressor cover (top) Belt heater 4. Remove the compressor cover (top). 5. Remove the compressor wires, compressor covers (right and left), and belt heater. Protection for the sealing material Suction piping...
  • Page 307: Troubleshooting Using The Outdoor Unit Led Error Display

    [ IX Troubleshooting ] [7] Troubleshooting Using the Outdoor Unit LED Error Display If the LED error display appear as follows while all the SW1 switches are set to OFF, check the items under the applicable item numbers below. 1. Error code appears on the LED display. Refer to IX [2] Responding to Error Display on the Remote Controller.(page 206) 2.
  • Page 308: X Led Monitor Display On The Outdoor Unit Board

    X LED Monitor Display on the Outdoor Unit Board [1] How to Read the LED on the Service Monitor ............... 301 HWE10040 - 299 -...
  • Page 309 - 300 -...
  • Page 310: How To Read The Led On The Service Monitor

    [ X LED Monitor Display on the Outdoor Unit Board ] X LED Monitor Display on the Outdoor Unit Board [1] How to Read the LED on the Service Monitor 1. How to read the LED By setting the DIP SW 1-1 through 1-10 (Switch number 10 is represented by 0), the operating condition of the unit can be monitored on the service monitor.
  • Page 311 [ X LED Monitor Display on the Outdoor Unit Board ] 3. Time data storage function The outdoor unit has a simple clock function that enables the unit to calculate the current time with an internal timer by receiv- ing the time set by the system controller, such as G(B)-50A. If an error (including a preliminary error) occurs, the error history data and the error detection time are stored into the service memory.
  • Page 312 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 303 -...
  • Page 313 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 304 -...
  • Page 314 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 305 -...
  • Page 315 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 306 -...
  • Page 316 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 307 -...
  • Page 317 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 308 -...
  • Page 318 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 309 -...
  • Page 319 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 310 -...
  • Page 320 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 311 -...
  • Page 321 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 312 -...
  • Page 322 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 313 -...
  • Page 323 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 314 -...
  • Page 324 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 315 -...
  • Page 325 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 316 -...
  • Page 326 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 317 -...
  • Page 327 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 318 -...
  • Page 328 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 319 -...
  • Page 329 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 320 -...
  • Page 330 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 321 -...
  • Page 331 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 322 -...
  • Page 332 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 323 -...
  • Page 333 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 324 -...
  • Page 334 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 325 -...
  • Page 335 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 326 -...
  • Page 336 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 327 -...
  • Page 337 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 328 -...
  • Page 338 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 329 -...
  • Page 339 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 330 -...
  • Page 340 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 331 -...
  • Page 341 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 332 -...
  • Page 342 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 333 -...
  • Page 343 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 334 -...
  • Page 344 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 335 -...
  • Page 345 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 336 -...
  • Page 346 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 337 -...
  • Page 347 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 338 -...
  • Page 348 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 339 -...
  • Page 349 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 340 -...
  • Page 350 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 341 -...
  • Page 351 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 342 -...
  • Page 352 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 343 -...
  • Page 353 [ X LED Monitor Display on the Outdoor Unit Board ] HWE10040 - 344 -...
  • Page 354 Service Handbook Service Handbook Model PUHY-P200, P250, P300, P350, P400, P450YJM-A PUHY-P500, P550, P600, P650, P700, P750, P800, P850, P900YSJM-A(1) PUHY-P950, P1000, P1050, P1100, P1150, P1200, P1250YSJM-A PUHY-EP200, EP250, EP300YJM-A PUHY-EP400, EP450, EP500, EP550, EP600YSJM-A(1) PUHY-EP650, EP700, EP750, EP800, EP850, EP900YSJM-A(1) http://Global.MitsubishiElectric.com...

Table of Contents