Symptoms Of Incorrect Connection To Bc Controller Lev Board - Mitsubishi Electric PUHY-200YMF-C Service Handbook

Air conditioners city multi
Table of Contents

Advertisement

1 LEV
Note 1 :

Symptoms of incorrect connection to BC controller LEV board

LEV No.
1
3
1)
1
3
2)
3
1
Improper installation is the same for 1 and 2, so it is omitted here.
Note 2 : Method for checking LEV full open, full closed condition
1 Check LEV full opening (pulse) using the LED monitor display (outdoor controller board SW1).
Full opened: 2000 pulses
Full closed: 60 pulses (LEV 1 may be greater than 60 during full heating operation.)
2 With LEV full opened, check for pressure differential by measuring temperature of piping on both sides.
3 With LEV full closed, check for refrigerant noise.
Note 3 : Use the following table to determine opening due to LEV differential pressure control and superheat
control.
BC controller LEV basic operation characteristics
Region
Failure mode Operating mode
Small
LEV1
pulse
Large
Small
LEV3
pulse
Large
Cooling-only
Normal
Insufficient cooling
Insufficient cooling, insuf-
SH12 small,
ficient heating
SC11 small
SH12 small, SC11 small
SC16 small
SC16 large,
Branch piping SC small
Branch piping SC small
Heating-only
High pressure (PS1) - medium pressure (PS3) is large.
Heating-main
High pressure (PS1) - medium pressure (PS3) is small.
Cooling-main
Cooling-only
SH12 is large.
Cooling-main
Heating-only
High pressure (PS1) - mid pressure (PS3) is small.
Heating-main
Cooling-only
SC16 and SH12 are small.
Cooling-main
Heating-only
High pressure (PS1) - mid pressure (PS3) is large.
Heating-main
Cooling-main
Heating-only
Heating indoor SC small
PHM large
PHM large
Description
–109–
Heating-main
Insufficient cooling
Heating indoor SC small
PHM large
Normal range
2.0 ~ 3.5 kg/cm
2
G
(0.20~0.34MPa)
SH12<25
2.0 ~ 3.5 kg/cm
2
G
(0.20~0.34MPa)
SC16>6
SH12>5
2
2.0 ~ 3.5 kg/cm
G
(0.20~0.34MPa)