1.3 Overview

The UPS provides two power paths between the utility source and the critical load.
Figure 1.1 shows the path for normal operation, with the load powered from the inverter.
Figure 1.2 shows the path for bypass operation, with the load supplied through the static
bypass line.
Figure 1.3 shows the path for battery operation, with the load supplied from the inverter.
A) Normal Operation.
FIGURE 1.1 Single Line Diagram - Normal Operation. Load powered by inverter
CB
AC Bypass
Input
CB
AC input
User
supplied
During normal operation, the path through the inverter is used to power the load.
Referring to Figure 1.1: Input AC power is converted to DC by the Converter. DC power is
utilized to charge the UPS battery and to provide power to the Inverter. The Inverter
converts the DC power to clean AC power to supply the critical load.
The conversion - inversion process eliminates any voltage transients or fluctuations
existing in the input power before it reaches the critical load.
* The AC Bypass Input circuit breaker (MCCB) for protection of the UPS and cables are field
supplied and field installed. (See WARNING 2 on page 1-2)
2033D SERIES UPS
OWNERS / TECHNICAL MANUAL
52RS
CONVERTER
52RC
FI
BATTERY
MITSUBISHI ELECTRIC 2033D SERIES UPS
Page Number:
Static Transfer
Switch
INVERTER
52C
FO
FB
72B
50kVA,
80kVA:
External Battery
1-5
Maintenance
Bypass
Switch
Output
52CS
Power Flow
Not in Use
UPS Module