Paluse train input function

1.11 Paluse train input function

Pulse train (the number of sampling pulses) from terminal JOG is stored to D9236.
When the sampling pulses overflow, make adjustment with the setting of Pr. 416 and
Pr. 417.
The number of sampling pulses
= the number of input pulses per count cycle x Pre-scale setting value (Pr. 417) x
increments scaling factor (Pr. 416)
Parameter
Pulse train input
291
selection
Pre-scale function
416
selection
Pre-scale setting
417
Device No.
Pulse train input sampling
D9236
pulse
Pulse train input cumulative
D9237
count value L
Pulse train input cumulative
D9238
count value H
Reset request of pulse train
D9239
input count
Count start of the pulse train
D9240
input
40
Initial
Name
Value
0
0
1
value
Name
Setting
Range
0, 10,20
Terminal JOG
1,11,21,100 Pulse train input
Pre-scale function selection
(increments scaling factor)
0: No function
1: ×1
0 to 5
2: ×0.1
3: ×0.01
4: ×0.001
5: ×0.0001
Set the pre-scale value to calcute the
0 to 32767
number of sampling pulse when
inputting the pulse train.
Setting
Range
The number of pulses counted in
0 to 32767
count cycle is stored.
0 to
The cumulative value of the number
99999999
of sampling pulses is stored.
0
Not clear
1
Count clear
0
Stop counting
1
Start counting