External Input/Output; External Signal Input Function - Mitsubishi Electric GB-50ADA-A Installation Instructions Manual

Hide thumbs Also See for GB-50ADA-A:
Table of Contents

Advertisement

10 External input/output

10-1. External signal input function

* To use the external signal input, a separately-sold external input/output adapter (PAC-YG10HA) and external power supply
are required.
10-1-1. External input signal function setting (to be set from the web browser for Initial settings)
External contact signal (12VDC or 24VDC) can be used to send signals indicating the following status of all air conditioning units
that are controlled by the controller: Emergency stop/Normal, Run/Stop, and local remote controller operation Prohibit/Permit.
No.
External input signal function
External input signal will not be used.
1
(factory setting)
Emergency stop/Normal (level signal)
2
Run/Stop (level signal)
3
Run/Stop, Prohibit/Permit (pulse signal)
4
* DIDO controller (PAC-YG66DCA) cannot be collectively run or stopped by using the external input function. But when
[Emergency stop/Normal (Level signal)] is selected, DIDO controller (PAC-YG66DCA) can be collectively stopped by setting
the appropriate switches on the DIDO controller.
10-1-2. Level signals and pulse signals
(A) Level signals
Contact ON
Contact OFF
Stop
Contact ON
Contact OFF
Normal
10-1-3. External input specifications
Lead wire
CN5
(PAC-YG10HA)
Orange
No. 5
No. 6
Yellow
Blue
No. 7
Gray
No. 8
No. 9
Red
(A) Level signals
1 If "Emergency stop/Normal operation signal" is selected, the unit will come to an emergency stop when the contact
turns on, and the unit will resume normal operation when the contact turns off. When emergency stop is reset, all units
will remain stopped, including the ones that were operating before the emergency stop signal input was received. To
return to the previous operation status, these units need to be manually restarted.
2 If "Run/Stop signal input" is selected, the unit will go into operation when external input signal contact turns ON, and the
unit will stop when the contact signal turns OFF.
MODEL :
Serial number :
Run
Stop
Emergency
Normal
stop
Emergency stop/Normal
(level signal)
Emergency stop/Normal
signal input
Not used
Not used
Not used
External power supply 12VDC or 24VDC
External input/output terminal (CN5)
During the emergency stop, the Run/Stop mode cannot be changed from the
local remote controller, and the Run/Stop mode and Prohibit/Permit settings
cannot be changed from the GB-50ADA. Timer setting will be ignored.
The Run/Stop mode cannot be changed from the local remote controller,
and the Run/Stop mode and Prohibit/Permit settings cannot be changed
from the GB-50ADA. Timer setting will be ignored.
The pulse width (contact ON) should be between 0.5 and 1 second.
(B) Pulse signal
(Example) Run/Stop
Signal 1 (Run)
Signal 2 (Stop)
* Same with the Prohibit/Permit signal input.
Run/Stop
(level signal)
Run/Stop signal input
Not used
Not used
Not used
- 24 -
Notes
0.5 - 1 second
Contact ON
Contact OFF
Contact ON
Contact OFF
Stop
Emergency stop
Run/Stop, Prohibit/Permit
(pulse signal)
Operation signal input
Stop signal input
Local remote controller operation
prohibit signal input
Local remote controller operation
permit signal input
0.5 - 1 second
Stop