6.2.1 Modbus TCP

EN-40 MODBUS TCP Status
Range:
[0]
[1]
Bit
Description
0
Link Status port
1
1
Link Status port
2
2
Link speed
3
Link Duplex
4
Port 502 com-
6
munication
5
UNUSED
6
Valid IP address No
7
Modbus time-
out (30 s)
8
Duplicate IP
9
Register 7 error No
10
FTP server
11
HTTP server
12
SMTP service
13
Cable diagnosis Disabled
14
Auto crossover Disabled
15
IGMP snooping Disabled
EN-41 Slave Message Count
Option:
EN-42 Slave Exception
Option:
EN-80 FTP Server
Option:
[0] *
Disable
[1]
Enable
EN-81 HTTP Server
Option:
[0] *
Disable
[1]
Enable
40
Function:
Read only. Displays the Modbus TCP- specific 16-bit Status word.
Bit = [0]
Bit =[1]
Disconnected
Connected
Disconnected
Connected
0/10 Mbps
100 Mbps
Half
Full
No
Yes
-
-
Yes
No
Yes
No
Yes
Yes
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Enabled
Enabled
Enabled
Function:
Read only.
Displays the number of Modbus messages received and processed by the slave.
Function:
Read only.
Displays the number of Modbus messages for which the slave has sent an exception response.
Function:
Disables the built-in FTP server.
Enables the built-in FTP server.
Function:
Disables the build-in HTTP (web) server.
Enables the build-in HTTP (web) server.