Download Print this page

Technical Data - Panasonic 1735 Specification Sheet

Fire alarm systems alert annunciation units
Hide thumbs Also See for 1735:

Advertisement

1735
Alert annunciation unit. Swedish designation texts.
1736
Alert annunciation unit. Designation texts in any language.
1587
External FBP / DU interface board in EBL512, for connection of the 1735 and
1736 units in system EBL512. (Software version > 2.2 is required.)
4552
RS485 transceiver component, for connection of up to four display units, e.g.
Alert Annunciation Units 1735 / 1736 in system EBL128.
NOTE! The number of units that can be power supplied via the c.i.e. (or an external power
supply) is depending on all other units connected to the same c.i.e. / external power supply. Up
to 1200 m cable can be used.
The 1736 unit has a neutral front where the designation texts, by production, are made
separately and put into a transparent "text slot" for the LED and push button respectively.
1735 succeeds the Display unit (with alert annunciation) 2235SE but not as a spare part, since
2235SE is connected to a COM loop and 1735 requires an Ext. FBP / DU interface board 1587
in the c.i.e.
(2235SE = Swedish designation texts.)
1736 succeeds the Display unit (with alert annunciation) 2235xx but not as a spare part, since
2235xx is connected to a COM loop and 1736 requires an Ext. FBP / DU interface board 1587
in the c.i.e.
(2235xx = Designation texts in another language than Swedish.)
The AA unit 1735 and AA unit 1736 shall run in SW mode 1735 – 1587 and SW mode 1736 –
1587 respectively.
Voltage (V DC)
rated
allowed
normal (in the system)
normal (in the system by battery back-up)
Current consumption at norm. volt. (mA)
AA unit 1735 / 1736
quiescent / active
Ambient temperature (°C)
operating
storage
Ambient humidity (% RH)
Ingress Protection rating (estimated)
Size W x H x D (mm)
Weight (g)
1735
1736
Colour (high impact ABS)
Approvals
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet
MEW00278
Type numbers

Technical data

24
12-30
24
21-27
26 (at 24 V), 48 (at 12 V) / 42 (at 24 V), 79 (at 12 V)
0 to +40
-40 to +70
max. 90, non condensing
IP61 (with the "O" ring gasket)
220 x 145 x 50
687
691
Grey (RAL 7035)
CE; Conforms with EN54-2 and –4 whenever applicable.
Conforms with SBF 110:6.
Date of issue
2003-04-16
Revision / Date of revision
3 / 2006-08-31

Advertisement

loading

This manual is also suitable for:

1736