Technical Data - Panasonic 1828 Specification Sheet

Fire alarm systems external fire brigade panel

Advertisement

1828
External Fire Brigade Panel (S/W V1.2). 1828SE / 1828CC: Designation texts on
the front in Swedish / see below. NOTE! In Swedish convention (SBF): No
"General fault" presentation.
1582
External FBP interface board. (Required in EBL512 / 500 when SW mode 1826/28
– 1582 shall be used.)
1587
External FBP / DU interface board. (Required in EBL512 when SW mode 1826/28
– 1587 shall be used. EBL512 software V>2.3.2
2431
Connection board. (Required in EBL1000. SW mode 1826/28 – 1582 only.)
4552
RS485 Transceiver component / comm. module. (Required in EBL128. SW mode
1826/28 – 1587 only. EBL128 software V>1.0.5
1
Only required if the new function ("General fault" presentation) shall be used.
NOTE! The number of ext. FBPs that can be power supplied via the c.i.e. / board / external power
supply, is depending on all other units connected to the same c.i.e. / board / external power supply.
to 1200 m cable can be used.
1828CC is a unit with a neutral front where the designation texts by production are made separately and
put into a transparent "text slot" for the LED and push button respectively. CC=Country Code.
The ext. FBP 1828 can run in one of two different SW modes:
a) 1828 in SW mode 1826/28 – 1587 has the highest performance with regard to functionality, response
time, ability to store fire alarms, etc. and is an alternative to the ext. Presentation display 2428, the
Display unit 2236 and a compact size alternative to the ext. FBP 2426 but not as a spare part, since 1828,
in this SW mode, requires an Ext. FBP / DU interface board 1587 in the EBL512 c.i.e. and the look,
dimensions, etc. are not the same.
This mode is always used when the ext. FBP is connected to EBL128.
b) 1828 in SW mode 1826/28 - 1582 is an alternative to the ext. Presentation display 2428, the Display
unit 2236 and a compact size spare part to the ext. FBP 2426, i.e. the performance is the same
look, dimensions, etc. are not the same. 1828, in this SW mode, requires an Ext. FBP interface board
1582 in the EBL512 / EBL500 c.i.e.
Voltage (V DC)
rated
allowed
normal (in the system)
normal (in the system by battery back-up)
Current consumption at norm. volt. (mA)
Ext. FBP 1828
quiescent / active
Ambient temperature (°C)
operating
storage
Ambient humidity (% RH)
Ingress Protection rating (estimated)
Size W x H x D (mm)
Weight (g)
Colour (high impact ABS)
Approvals
2
On each 1582 board are up to eight addresses available and on each 1587 board up to sixteen addresses. In EBL128
are up to four addresses available.
3
Note! The alarm presentation will be as in the c.i.e. that ext. FBP is connected to, not as in 2425 / 2426. The 1828
front does not hold any LED "Zone/Detector not reset".
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet
MEW00336
Type numbers
1
required.)
1
required.)

Technical data

24
12-30
24
21-27
26 (at 24 V), 48 (at 12 V) / 49 (at 24 V), 88 (at 12 V)
0 to +40
-40 to +70
max. 90, non condensing
IP61 (with the "O" ring gasket)
220 x 145 x 50
750
Grey (RAL 7035)
CE; Conforms with EN54-2 and –4 whenever applicable.
Conforms with SS3654 edition 1.
Date of issue
2003-04-15
3
but the
Revision / Date of revision
4 / 2007-01-29