Way Alarm Codes - Panasonic U-8MF2E8 Service Manual

3-way vrf system
Table of Contents

Advertisement

4. 3WAY Alarm Codes

With types 8HP and 10HP, the INV compressor is compressor 1.
With types 12HP, 14HP and 16HP, the INV compressor is compressor 1, and the constant-speed
compressors (AC1) are compressors 2.
Alarm code
E06
Outdoor unit failed to receive serial communication signals from indoor unit.
E12
Automatic address setting start is prohibited.
E15
Automatic address setting alarm (too few units)
E16
Automatic address setting alarm (too many units)
E20
No indoor units at automatic address setting.
E24
Outdoor unit failed to receive communications from another outdoor unit.
E25
Outdoor unit address setting failure (duplication)
E26
Mismatch in outdoor unit quantity
E29
Outdoor unit failed to receive communication from outdoor unit (main)
E31
Communication error between the microcomputers
F04
Compressor 1 discharge temperature sensor trouble
F05
Compressor 2 discharge temperature sensor trouble
F06
Gas temperature sensor trouble at outdoor heat exchanger 1 (In)
F07
Liquid temperature sensor trouble at outdoor heat exchanger 1 (Out)
F08
Outdoor air temperature sensor trouble
F12
Compressor intake temperature sensor trouble (SCT)
F14
Temp. sensor at refrigerant gas outlet of dual-tube (SCG)
F16
High pressure sensor failure. High pressure trouble.
F17
Low-pressure sensor trouble
F23
Gas temperature sensor trouble at outdoor heat exchanger 2 (In)
F24
Liquid temperature sensor trouble at outdoor heat exchanger 2 (Out)
F31
Outdoor unit non-volatile memory (EEPROM) trouble
H01
Compressor 1 current trouble
H11
Constant speed compressor 2 overcurrent alarm
H12
Constant speed compressor 2 lock current alarm
H03
Compressor 1 CT sensor disconnected or short-circuit
H05
Compressor 1 discharge temperature sensor disconnected
H06
Low-pressure switch activated
H08
Compressor 1 oil detection sensor (connection) trouble
H13
Compressor 2 CT sensor disconnected or short-circuit
H15
Compressor 2 discharge temperature sensor disconnected
H27
Compressor 2 oil detection sensor (connection) trouble
H31
HIC trouble alarm
L04
Outdoor system address duplication
L10
Outdoor unit capacity not set
L11
Incorrect wiring of remote group control wiring (in case of shared solenoid valve kit)
L17
Outdoor unit model mismatch
P02
Compressor thermal protector is activated. (trip only and no alarm)
P03
Compressor 1 discharge temperature trouble
P04
High-pressure switch activated
P05
Reverse phase (or missing phase) detected
P14
O
sensor (detects low oxygen level) activated
2
P16
Compressor 1 (INV) overcurrent
P17
Compressor 2 discharge temperature trouble
P22
Fan motor trouble
P29
Inverter compressor missing phase or lock alarm
Blinking Inspection Display on the remote
controller
Alarm meaning
CHECK blinking (1)
CHECK blinking (2)
5 - 7
3WAY SYSTEM
Trouble Diagnosis
Page
5-8
5-8
5-8
5-9
5-9
5-9
5-10
5-10
5-10
5-10
5-11
5-11
5
-12
5-12
5-13
5-13
5-13
5-14
5-15
5-12
5-12
5-15
5-15
5-16
5-16
5-17
5-17
5-18
5
5-19
5-17
5-17
5-19
5-19
5-19
5-20
5-20
5-21
5-21
5-22
5-23
5-23
5-24
5-24
5-22
5-25
5-25
5-26
5-27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents