C.3

Representation of analog values in the current output ranges

The tables below list the decimal and hexadecimal values (codes) of the possible current
output ranges.
Table C- 7
Values
>117.589%
117.589%
100%
75%
0.003617%
0%
-75%
-100%
-117.593%
<-117.593%
Table C- 8
Values
>117.589%
117.589%
100%
75%
0.003617%
0%
<0%
Analog output module AQ 4xU/I ST (6ES7532-5HD00-0AB0)
Manual, 09/2016, A5E03484696-AD
C.3 Representation of analog values in the current output ranges
Current output range ±20 mA
dec
hex
>32511
>7EFF
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-20736
AF00
-27648
9400
-27649
93FF
-32512
8100
<-32512
<8100
Current output range 0 mA to 20 mA
dec
hex
>32511
>7EFF
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
<0
<0
Representation of analog values
Current output range
±20 mA
23.52 mA
23.52 mA
20 mA
15 mA
723.4 nA
0 mA
-723.4 nA
-15 mA
-20 mA
-23.52 mA
-23.52 mA
Current output range
0 mA to 20 mA
23.52 mA
23.52 mA
20 mA
15 mA
723.4 nA
0 mA
0 mA
Range
Maximum output value
Overshoot range
Rated range
Undershoot range
Minimum output value
Range
Maximum output value
Overshoot range
Rated range
Minimum output value
39