5.2 PRODUCT SETUP
5.2PRODUCT SETUP
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
SECURITY
CyberSentry or basic security applies, depending on purchase. This section outlines password access. See the next sec-
tion and the Security chapter for information on setting up user accounts and CyberSentry security.
Two levels of password security are provided via the
is not available and intended for factory use only.
The following operations are under command password supervision:
•
Operating the breakers via faceplate keypad
5
•
Changing the state of virtual inputs
•
Clearing the event records
•
Clearing the oscillography records
•
Clearing fault reports
•
Changing the date and time
•
Clearing the breaker arcing current
•
Clearing energy records
•
Clearing the data logger
•
Clearing the user-programmable pushbutton states
The following operations are under setting password supervision:
•
Changing any setting
•
Test mode operation
The command and setting passwords are defaulted to "0" when the relay is shipped from the factory. When a password is
set to "0", the password security feature is disabled.
The L90 supports password entry from a local or remote connection.
Local access is defined as any access to settings or commands via the faceplate interface. This includes both keypad entry
and the through the faceplate RS232 port. Remote access is defined as any access to settings or commands via any rear
communications port. This includes both Ethernet and RS485 connections. Any changes to the local or remote passwords
enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond-
ing connection password. If the connection is to the back of the L90, the remote password must be used. If the connection
is to the RS232 port of the faceplate, the local password must be used.
The
PASSWORD ACCESS EVENTS
5-8
SECURITY
ACCESS LEVEL:
Restricted
CHANGE LOCAL
MESSAGE
PASSWORDS
ACCESS
MESSAGE
SUPERVISION
DUAL PERMISSION
MESSAGE
SECURITY ACCESS
PASSWORD ACCESS
MESSAGE
EVENTS: Disabled
settings allows recording of password access events in the event recorder.
L90 Line Current Differential System
Range: Restricted, Command, Setting,
Factory Service (for factory use only)
See page 5–9.
See page 5–10.
See page 5–11.
Range: Disabled, Enabled
setting: command and setting. The factory service level
ACCESS LEVEL
5 SETTINGS
5.2.1 SECURITY
GE Multilin