5.8 INPUTS/OUTPUTS
c) LOCAL DEVICES: DEVICE ID FOR TRANSMITTING GSSE MESSAGES
In a L90 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each
GOOSE message is programmed in the
GSSE/GOOSE CONFIGURATION
Likewise, the device ID that represents the IEC 61850 GSSE application ID name string sent as part of each GSSE mes-
sage is programmed in the
CONFIGURATION
TRANSMISSION
In L90 releases previous to 5.0x, these name strings were represented by the

PATH: SETTINGS
INPUTS/OUTPUTS
 REMOTE INPUT 1
5
Remote Inputs that create FlexLogic operands at the receiving relay are extracted from GSSE/GOOSE messages originat-
ing in remote devices. Each remote input can be selected from a list consisting of: DNA-1 through DNA-32, UserSt-1
through UserSt-32, and Dataset Item 1 through Dataset Item 32. The function of DNA inputs is defined in the IEC 61850
specification and is presented in the IEC 61850 DNA Assignments table in the Remote outputs section. The function of
UserSt inputs is defined by the user selection of the FlexLogic operand whose state is represented in the GSSE/GOOSE
message. A user must program a DNA point from the appropriate FlexLogic operand.
Remote input 1 must be programmed to replicate the logic state of a specific signal from a specific remote device for local
use. This programming is performed via the three settings shown above.
The
REMOTE INPUT 1 ID
selects the remote device which originates the required signal, as previously assigned to the remote device via the setting
REMOTE DEVICE (16) ID
GSSE/GOOSE message required.
The
REMOTE IN 1 DEFAULT STATE
the remote device sending the point is declared to be non-communicating. The following choices are available:
Setting
REMOTE IN 1 DEFAULT STATE
Setting
REMOTE IN 1 DEFAULT STATE
Setting
REMOTE IN 1 DEFAULT STATE
not known, such as after relay power-up but before the first communication exchange, the input will default to logic 1.
When communication resumes, the input becomes fully operational.
Setting
REMOTE IN 1 DEFAULT STATE
not known, such as after relay power-up but before the first communication exchange, the input will default to logic 0.
When communication resumes, the input becomes fully operational.
For additional information on GSSE/GOOOSE messaging, refer to the Remote Devices section in this chapter.
NOTE
5-328
SETTINGS

TRANSMISSION
FIXED GOOSE
SETTINGS
PRODUCT SETUP


GSSE
GSSE ID


REMOTE INPUTS

REMOTE INPUT
Remote Ip
REMOTE IN
MESSAGE
Remote Device
REMOTE IN
MESSAGE
None
REMOTE IN
MESSAGE
STATE: Off
REMOTE IN
MESSAGE
EVENTS: Disabled
setting allows the user to assign descriptive text to the remote input. The
(see the Remote devices section). The
setting selects the logic state for this point if the local relay has just completed startup or
to "On" value defaults the input to logic 1.
to "Off" value defaults the input to logic 0.
to "Latest/On" freezes the input in case of lost communications. If the latest state is
to "Latest/Off" freezes the input in case of lost communications. If the latest state is
L90 Line Current Differential System

PRODUCT SETUP
COMMUNICATIONS

setting.
GOOSE ID


COMMUNICATIONS
setting.
RELAY NAME
REMOTE INPUT 1(32)
Range: up to 12 alphanumeric characters
1 ID:
1
Range: Remote Device 1 to Remote device 16
1 DEVICE:
1
Range: None, DNA-1 to DNA-32, UserSt-1 to UserSt-32,
1 ITEM:
Config Item 1 to Config Item 32
Range: On, Off, Latest/On, Latest/Off
1 DEFAULT
Range: Disabled, Enabled
1
setting selects the specific bits of the
REMOTE IN 1 ITEM
5 SETTINGS

IEC 61850 PROTOCOL
IEC 61850 PROTOCOL
GSSE/GOOSE
setting.
5.8.6 REMOTE INPUTS
REMOTE IN 1 DEVICE
GE Multilin
setting