This UPS does not include a Bypass input circuit breaker (MCCB) to
protect bypass circuit. The Bypass input circuit breaker (MCCB) is to be
field
supplied
Specifications are as follows:
TABLE 1.2
Rating of Bypass Input Circuit Breaker
Capacity (kVA) Bypass Voltage (Vac) Bypass Rating (Aac)
100
150
225
300
375
500
750
AC input and AC output overcurrent protection and disconnect devices shall be field
supplied and installed. The DC output breaker (MCCB) shall be field supplied and
installed. The overcurrent protection device should be installed in the Battery cabinet
and rated as indicated in TABLE 1.6.
MITSUBISHI ELECTRIC 9800A SERIES UPS
9800A SERIES UPS
OWNERS / TECHNICAL MANUAL
WARNING 4
and
installed.
Recommended
480
600
480
600
480
600
480
600
480
600
480
600
480
600
Page Number:
1-4
Breaker
(MCCB)'s
Breaker (A)
120
150
96
125
180
225
144
200
271
350
217
300
361
500
289
400
451
600
361
500
602
800
482
600
902
1200
722
900