13.2 General Technical Data

Mains supply
Supply voltage
Supply voltage
Supply voltage
Supply voltage
Mains voltage low/mains drop-out:
During low mains voltage or a mains drop-out, the AF-650 GP drive continues until the DC-link voltage drops below the
minimum stop level, which corresponds typically to 15% below the frequency converter's lowest rated supply voltage. Power-up
and full torque cannot be expected at mains voltage lower than 10% below the frequency converter's lowest rated supply
voltage.
Supply frequency
Maximum imbalance temporary between mains phases
True Power Factor (λ)
Displacement Power Factor (cos ϕ)
Switching on input supply L1, L2, L3 (power-ups) ≤ 7.5 kW (10 hp)
Switching on input supply L1, L2, L3 (power-ups) 11–75kW/15–100 hp
Switching on input supply L1, L2, L3 (power-ups) ≥ 90 kW (125 hp)
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100 kAIC RMS symmetrical Amperes,
240/500/600/690 V maximum.
Motor output (U, V, W
Output voltage
Output frequency
Switching on output
Ramp times
Torque characteristics
Starting torque (constant torque)
Starting/overload torque (variable torque)
Torque rise time in Flux Vector Vector Control (for 5 kHz fsw)
Torque rise time in Advanced Vector Control (independent of fsw)
1) Percentage relates to the nominal torque.
2) The torque response time depends on application and load but as a rule, the torque step from 0 to reference is 4–5 x torque
rise time.
Digital inputs
3
13
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic 0 PNP
Voltage level, logic 1 PNP
Voltage level, logic 0 NPN
Voltage level, logic 1 NPN
Maximum voltage on input
Pulse frequency range
(Duty cycle) minimum pulse width
Input resistance, R
STO terminal 37
Voltage level
Voltage level, logic 0 PNP
Voltage level, logic 1 PNP
Maximum voltage on input
128
1)
)
2)
2)
i
2)
(terminal 37 is fixed PNP logic)
DET-767c All rights reserved.
380–500 V ±10%
525–600 V ±10%
525–690 V ±10%
3.0% of rated supply voltage
≥ 0.9 nominal at rated load
near unity (> 0.98)
maximum 2 times/minute
maximum 1 time/minute
maximum 1 time/2 min.
overvoltage category III/pollution degree 2
0–100% of supply voltage
1)
maximum 150% for 60 s
once in 10 minutes
1)
maximum 110% for 60 s
once in 10 minutes
18, 19, 27
approximately 4 kΩ
200–240 V ±
50/60 Hz ±5%
0–590 Hz
Unlimited
0.01–3600 s
1 ms
10 ms
1)
4 (6)
1)
1)
, 29
, 32, 33
PNP or NPN
0–24 V DC
<5 V DC
>10 V DC
>19 V DC
<14 V DC
28 V DC
0–110 kHz
4.5 ms
0–24 V DC
<4 V DC
>20 V DC
28 V DC
MG35M402