13.2 General Technical Data

Mains supply (L1, L2, L3)
Supply voltage
Supply voltage
Mains voltage low / mains drop-out:
During low mains voltage or a mains drop-out, the drive continues until the intermediate circuit voltage drops below the
minimum stop level, which corresponds typically to 15% below the drive's lowest rated supply voltage. Power-up and full torque
cannot be expected at mains voltage lower than 10% below the drive's lowest rated supply voltage.
Supply frequency
Max. imbalance temporary between mains phases
True Power Factor (λ)
Displacement Power Factor (cosφ) near unity
Switching on input supply L1, L2, L3 (power-ups)
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100 k RMS symmetrical Amperes, 480/600 V
maximum.
Motor output (U, V, W)
Output voltage
Output frequency
Switching on output
Accel/Decel Times
Torque characteristics
Starting torque (Constant torque)
Starting torque
Overload torque (Constant torque)
*Percentage relates to AF-600 FP Drive's nominal torque.
Cable lengths and cross sections for control cables
Max. motor cable length, screened
Max. motor cable length, unscreened
Maximum cross section to control terminals, flexible/ rigid wire without cable end sleeves
Maximum cross section to control terminals, flexible wire with cable end sleeves
Maximum cross section to control terminals, flexible wire with cable end sleeves with collar
Minimum cross section to control terminals
Digital inputs
Programmable digital inputs
3
13
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Input resistance, R
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
100
AF-600 FP
i
TM
Design and Installation Guide
overvoltage category III/pollution degree 2
DET-768b
380-480 V ±10%
525-600 V ±10%
50/60 Hz ±5%
3.0 % of rated supply voltage
≥ 0.9 nominal at rated load
(> 0.98)
maximum once/2 min.
0-100% of supply voltage
0-590 Hz
Unlimited
1-3600 s
*
maximum 110% for 1 min.
*
maximum 135% up to 0.5 s
*
maximum 110% for 1 min.
150 m
300 m
2
1.5mm
/16 AWG
2
1mm
/18 AWG
2
0.5mm
/20 AWG
2
0.25mm
/ 24AWG
4 (6)
1)
18, 19, 27
, 29, 32, 33,
PNP or NPN
0-24 V DC
<5 V DC
>10 V DC
>19 V DC
<14 V DC
28 V DC
approx. 4 kΩ