5. SYSTEM PARAMETERS
Parameter
Number
P0305
motor current rating
Nominal motor current (A) from rating plate – see diagram P0304
Note:
This parameter can only be changed when P0010=1
Maximum value is defined as 2 * inverter rated current (r0207)
Minimum value is defined as 1/32 * inverter rated current (r0207)
P0307
Motor power rating
Nominal motor power (kW) from rating plate. If P0100 = 1, values will be in hp - see
diagram P0304
Note:
This parameter can only be changed when P0010=1
P0308
Motor cosPhi rating
Nominal motor power factor (cos φ) from rating plate - see diagram P0304
Note:
This parameter can only be changed when P0010=1
This parameter is only visible when P0100 = 0 or 2, i.e. when the motor power is entered in
kW.
Note:
A setting of 0 will cause the value to be calculated internally.
P0309
Motor efficiency rating
Nominal motor efficiency (%) from rating plate - see diagram P0304.
Note:
This parameter can only be changed when P0010=1
This parameter is only visible when P0100 = 1, i.e. when the motor power is entered in hp.
Note:
A setting of 0 will cause the value to be calculated internally.
P0310
Motor frequency rating
Nominal motor frequency (Hz) from rating plate - see diagram P0304
MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Parameter Name
International English
♦ ♦ ♦ ♦ P0003 User
Min
Access Level
Max
♦ ♦ ♦ ♦ P0004 Setting
[Default]
♦ ♦ ♦ ♦ Changeable
Units
♦ ♦ ♦ ♦ Status
0.12
1
10000
3
***
'
'
[
]
A
0.01
1
2000
3
***
'
'
[
]
-
0
2
1
3
[0]
'
'
-
0
2
100
3
[0]
'
'
%
12
1
650
3
[50]
'
'
Hz
55

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents