International English
Parameter
Number
P0771
Analog output function
Defines function of the 0 –20 mA analog output.
Possible settings:
These are the most common values:
21
24
25
26
27
Other values: See individual parameter descriptions
r0774
Analog output value
Shows the value of the analog output in mA.
P0777
Value X1 of analog output characteristics
Defines the x1 output characteristic.
The parameters P0777 – P0780 work as follows:
Points (x1, y1) , (x2,y2) can be chosen freely
P0778
Value Y1 of analog output characteristics
Defines y1 of output characteristic
P0779
Value X2 of analog output characteristics
Defines x2 of output characteristic
P0780
Value Y2 of analog output characteristics
Defines y2 of output characteristic
P0781
Analog output deadband
Sets the width of a dead-band in mA for the analog output.
64
Parameter Name
Actual frequency (scaled to P2000)
Output frequency (scaled to P2000)
Output voltage (scaled to 1000 V)
DC link voltage (scaled to 1000 V)
Output current (scaled to P2002 Level 3)
Output signal (mA)
20
P0780 Y2
P0778 Y1
0
(-100%)
P0777
X1
5. SYSTEM PARAMETERS
20 mA
100%
P0779
X2
MICROMASTER 420 Operating Instructions
♦ ♦ ♦ ♦ P0003 User
Min
Access Level
Max
♦ ♦ ♦ ♦ P0004 Setting
[Default]
♦ ♦ ♦ ♦ Changeable
Units
♦ ♦ ♦ ♦ Status
0
2
2248.0
8
[21]
'•'
-
-
2
-
8
[-]
%
-99999
2
99999
8
[0]
'•'
%
0
2
4
8
[0]
'•'
-
-99999
2
99999
8
[100]
'•'
%
0
2
20
8
[20]
'•'
-
0
2
20
8
[0]
'•'
-
6SE6400-5AA00-0BP0