Parameter List; Fault Codes - Siemens 6SE2101–1AA01 Operating Manual

6se21 series simovert p
Table of Contents

Advertisement

Available languages

Available languages

8.2 Parameter List

Parameter
Description
Only
P00
Frequency, output current or fault code
P01
Low frequency voltage boost
P02
Ramp–up time to maximum frequency
P03
Ramp–down time from maximum frequency
P04
Frequency control mode selection
P05
RUN/STOP mode
P06
Voltage to frequency curve selection
P07
Minimum frequency
P08
Maximum frequency
P09
Digital frequency set–point adjustment
P10
Analogue frequency set–point adjustment
P11
DC injection braking
P12
Jog
P13
Slip compensation
P14
Display status / Analogue output
P15
Voltage to frequency relationship: knee point
P16
Voltage to frequency relationship: curve type
P17
Current limit
P18
Overload limit
P19
Automatic boost
P20
Serial interface selection
P21
Serial interface address
P22
Serial interface parity and baud rate
P23
Digital input response speed
P24
Fixed frequency mode selection
P25
First fixed frequency
P26
Second fixed frequency
P27
Third fixed frequency
P28
Fourth fixed frequency
P29
Skip frequency
P30
Tachometer mode
P31
Tachometer scale factor
P32
Feedback compensation: proportional term (%)
P33
Feedback compensation: integral term (%)
P34
Feedback compensation: differential term (%)
P35
Tachometer slip limit (Hz)
P36
Tachometer sample rate
P37
Display tachometer frequency reading
P40
Switching frequency select
P41
Parameter default values
P42
Auto reset mode
P43
Ramp Smoothing
P44
Tachometer Interface Unit
P45
Clear Text Operator Panel Language
P48
Fault code
P49
Hardware type
P50
Software version
P51
Customer–specific Variants

8.3 Fault Codes

Code
Meaning
F00
Excessive load current or excessive link voltage. Low line voltage (6SE210*–3AA01 only).
F01
Excessive heatsink temperature.
F02
Corruption of parameterisation data in the non–volatile memory.
F03
Faulty operation of A–D converter or excessive tachometer feedback voltage.
F04
P07 set to a higher value than P08.
F05
P09 outside the limits set by P07 and P08.
F06
Fault on control board.
F07
Value of P25 > P08 setting or < P07 setting.
F08
Value of P26 > P08 setting or < P07 setting.
F09
Value of P27 > P08 setting or < P07 setting.
F10
Value of P28 > P08 setting or < P07 setting.
F11
Inverter tripped externally via X11.4 input.
8/2
Value Range
00.0 – 30.0%
00.0 – 400 s
00.0 – 400 s
000 – 009
000 – 009
000 – 006
00.0 – 399 Hz
00.1 – 400 Hz
00.0 – 400 Hz
080 – 240%
00.0 – 20.0%
00.1 – 400 Hz
00.0 – 20.0
000 – 003
00.1 – 400 Hz
000 or 001
00.1 – rated output 1.1 x
01.0 – 03.0
000 – 003
000 – 003
000 – 030
000 – 008
000 or 001
000 – 002
00.0 – 400
00.0 – 400
00.0 – 400
00.0 – 400
00.0 – 400
000 – 004
00.1 – 999
000 – 999
000 – 250
000 – 250
00.0 – 20.0
001 – 200
000 – 400
000 – 002
000 or 001
000 – 002
000 – 100
000 – 004
000 or 001
000 – 011
000 – 255
English
Default Settings
[
] – N. America
00.0
10.0
10.0
000
000
000
[001]
00.1
50.0
[60.0]
50.0
[60.0]
100
00.0
05.0
00.0
000
50.0
[60.0]
000
01.5
000
000
000
000
000
000
00.0
00.0
00.0
00.0
00.0
000
50.0
050
000
000
05.0
001
n/a
000 / 002
000
[001]
000
000
000
n/a
n/a
000

Hide quick links: