Siemens Simatic S7-1500 Manual page 40

Simatic s7-1500/et 200mp digital input module f-di 16x24vdc
Hide thumbs Also See for Simatic S7-1500:
Table of Contents

Advertisement

Applications of the F-I/O module
5.4 Application 3: Safety mode SIL3/Cat.4/PLe
Parameter assignment
Assign the following parameters for the corresponding channel:
Table 5- 4
Parameter
Sensor evaluation
Supplied channels
Short-circuit test activated
Fault detection
The following table presents fault detection according to the sensor supply and the
parameter assignment for the short-circuit test:
Table 5- 5
Fault
Short-circuit within the channel
pair
Short-circuit with other channels
or other sensor supplies
Short-circuit with L+ to DI
Short-circuit with M to DI
Discrepancy error
Short-circuit with L+ to U
Short-circuit with M to U
fective
*) Fault detection only if signals are corrupted. That is, the read signal differs from the sensor signal
(discrepancy error). If there is no signal corruption with respect to the sensor signal, fault detection
is not possible and is not required from a safety standpoint.
See also
Connecting (Page 15)
40
Parameter assignment
Channel with internal sensor supply
1oo2 evaluation, equivalent
Channels [x...y]
Disable
Fault detection
Internal sensor supply and
short-circuit test deactivated
n
n
Sn
or de-
Sn
Channel with external sensor
supply
None
Fault detection
No
Yes*
Yes*
Yes*
Yes
No
Yes
Digital input module F-DI 16x24VDC (6ES7526-1BH00-0AB0)
Manual, 01/2016, A5E03858068-AA
External sensor supply
No
Yes
Yes*
Yes*
Yes
No

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents