ABB REC650 Product Manual
ABB REC650 Product Manual

ABB REC650 Product Manual

Bay control
Hide thumbs Also See for REC650:

Advertisement

®
Relion
650 series
Bay control REC650
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB REC650

  • Page 1 ® Relion 650 series Bay control REC650 Product Guide...
  • Page 2: Table Of Contents

    18. Ordering............75 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB. ABB AB assumes no responsibility for any errors that may appear in this document. © Copyright 2011 ABB AB.
  • Page 3: Series Overview

    2. Application • Single breaker for double busbar (A02) • Bus coupler for double busbar (A07) REC650 is used for the control, protection The packages are configured and ready for and monitoring of different types of bays in direct use. Analog and control circuits have power networks.
  • Page 4 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 132 kV Bus REC650-A01 – Single Busbar Single breaker 10AI (4I+1I+5U) Control Control Control 132kV/110V S CILO S CSWI S XSWI Meter. V MMXU Control Control Control...
  • Page 5 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 REC650-A02 – Double Busbar Single breaker 10AI (4I+1I+5U) 132 kV Bus Control Control Control S CILO S CSWI S XSWI Control Control Control 132kV/ S CILO S CSWI...
  • Page 6 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 QC11 QC21 REC650-A07 – Bus Coupler single breaker 10AI (6I+4U) 132 kV Bus Control Control Control S CILO S CSWI S XSWI Control Control Control 132kV/ S CILO...
  • Page 7: Available Functions

    Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 3. Available functions...
  • Page 8: Scswi

    Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Control and monitoring functions IEC 61850/ ANSI Function description Function block name Control SESRSYN Synchrocheck, energizing check, and synchronizing SMBRREC Autorecloser SCILO Logical node for interlocking BB_ES...
  • Page 9 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 IEC 61850/ ANSI Function description Function block name QCBAY Bay control LOCREM Handling of LR-switch positions LOCREMCTRL LHMI control of Permitted Source To Operate (PSTO) SLGGIO Logic Rotating Switch for function...
  • Page 10 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 IEC 61850/ ANSI Function description Function block name Configurable logic blocks, OR gate INVERTER Configurable logic blocks, Inverter gate PULSETIMER Configurable logic blocks, Pulse timer GATE Configurable logic blocks,...
  • Page 11 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 IEC 61850/ ANSI Function description Function block name TIMERSETQT Configurable logic Q/T, timer function block with quality and time PULSETIMERQT Configurable logic Q/T, pulse timer with quality and time...
  • Page 12 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 IEC 61850/ ANSI Function description Function block name DRPRDRE Disturbance report AxRADR Analog input signals BxRBDR Binary input signals SPGGIO IEC 61850 generic communication I/ O functions...
  • Page 13 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 IEC 61850/ ANSI Function description Function block name Metering PCGGIO Pulse counter logic ETPMMTR Function for energy calculation and demand handling...
  • Page 14 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Back-up protection functions IEC 61850/ ANSI Function description Function block name Current protection PHPIOC Instantaneous phase overcurrent protection OC4PTOC 51/67 Four step directional phase overcurrent protection EFPIOC...
  • Page 15 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 IEC 61850/ ANSI Function description Function block name Frequency protection SAPTUF Underfrequency function SAPTOF Overfrequency function SAPFRC Rate-of-change frequency protection...
  • Page 16 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Designed to communicate IEC 61850/ ANSI Function description Function block name Station communication IEC 61850 communication protocol, LAN1 DNP3.0 for TCP/IP communication protocol, LAN1 IEC61870-5-103 IEC60870-5-103 serial...
  • Page 17 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Basic IED functions IEC 61850/ Function description Function block name Basic functions included in all products INTERRSIG Self supervision with internal event list SELFSUPEVLST Self supervision with internal event list...
  • Page 18: Control

    Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 place selection and external or internal 4. Control blockings. Apparatus control features: Synchrocheck, energizing check, • Select-Execute principle to give high and synchronizing SESRSYN reliability The Synchronizing function allows closing of •...
  • Page 19 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Interlocking The interlocking functionality blocks the possibility to operate high-voltage switching devices, for instance when a disconnector is under load, in order to prevent material damage and/or accidental human injury.
  • Page 20: Current Protection

    Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 separately. Step 2 and 3 are always definite IEC 61850 generic communication time delayed. I/O functions DPGGIO All IEC and ANSI time delayed characteristics The IEC 61850 generic communication I/O are available.
  • Page 21 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Directional operation can be combined A current check with extremely short reset together with corresponding communication time is used as check criterion to achieve a logic in permissive or blocking teleprotection high security against unnecessary operation.
  • Page 22: Voltage Protection

    Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 The pole discordance function operates based forward, reverse or non-directional on information from the circuit breaker logic independently for each step. with additional criteria from unsymmetrical DNSPTOC protects against all unbalanced phase currents when required.
  • Page 23: Frequency Protection

    Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 transformers or measures it from a single Rate-of-change frequency voltage input transformer fed from an open protection SAPFRC delta or neutral point voltage transformer. Rate-of-change frequency protection function...
  • Page 24: Logic

    Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 transformer and the IED in order to avoid The function operates after a predefined unwanted operations that otherwise might operating time and resets when the fault occur.
  • Page 25 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 • LOOPDELAY function block used to delay • XORQT function block. The function also the output signal one execution cycle. propagates timestamp and quality of input signals.
  • Page 26: Monitoring

    Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 output changes, the Event bit in the state 10. Monitoring part is toggled. The function also propagates timestamp and quality of input signals. Measurements CVMMXN, CMMXU, VNMMXU, VMMXU, CMSQI, VMSQI •...
  • Page 27 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 blocks, which are set to trigger the example corrective actions) and in the long disturbance recorder. All signals from start of term (for example functional analysis). pre-fault time to the end of post-fault time The event recorder logs all selected binary will be included in the recording.
  • Page 28: Metering

    Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 The function is characterized by great Insulation gas monitoring function flexibility and is not dependent on the SSIMG operation of protection functions. It can record disturbances not detected by Insulation gas monitoring function (SSIMG) is protection functions.
  • Page 29: Human Machine Interface

    Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 scaled service value is available over the resolution of 320x240 pixels. The character station bus. size may vary depending on selected language. The amount of characters and rows...
  • Page 30: Station Communication

    Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Time-tagging of internal events and Change lock function CHNGLCK disturbances are an excellent help when evaluating faults. Without time Change lock function (CHNGLCK) is used to synchronization, only the events within the block further changes to the IED IED can be compared to one another.
  • Page 31 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 according to GOOSE is part of the standard. Table 1. Supported communication Disturbance files uploading is provided. interface and protocol alternatives Disturbance files are accessed using the IEC...
  • Page 32: Hardware Description

    Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 15. Hardware description Layout and dimensions Mounting alternatives The following mounting alternatives are available (IP40 protection from the front): • 19” rack mounting kit • Wall mounting kit •...
  • Page 33 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 IEC09000677.ai IEC09000677 V1 EN Figure 10. Two rack mounted IEDs side by side 224 mm + 12 mm with ring-lug connector 25.5 mm 482.6 mm (19") GUID-5C185EAC-13D0-40BD-8511-58CA53EFF7DE V1 EN Figure 12.
  • Page 34: Connection Diagrams

    Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 16. Connection diagrams Module Slot Rear Position pCOM X0, X1, X4, X9,X304 pPSM X307, X309, X410 X101, X102 X321, X324 X326, X329 X331, X334 X336, X339 1MRK006501-BB 2 PG 1.1 IEC V1 EN Figure 13.
  • Page 35 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Connection diagrams for REC650 A01 1MRK006501-DB 5 PG 1.1 IEC V1 EN Figure 16. Power supply module (PSM), 110-250V DC 1MRK006501-DB 3 PG 1.1 IEC V1 EN Figure 14.
  • Page 36 1MRK006501-DB 9 PG 1.1 IEC V1 EN (Terminal X321, X324) Figure 20. Binary input/output (BIO) option (Terminal X331, 334) Connection diagrams for REC650 A02 1MRK006501-DB 8 PG 1.1 IEC V1 EN Figure 19. Binary input/output (BIO) option (Terminal X326, 329) 1MRK006501-CB 3 PG 1.1 IEC V1 EN...
  • Page 37 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 1MRK006501-CB 4 PG 1.1 IEC V1 EN Figure 22. Power supply module (PSM) 48-125V DC 1MRK006501-CB 6 PG 1.1 IEC V1 EN Figure 24. Transformer module (TRM) 1MRK006501-CB 5 PG 1.1 IEC V1 EN...
  • Page 38 Figure 26. Binary input/output (BIO) option Figure 28. Binary input/output (BIO) option (Terminal X326, X329) (X336, X339) Connection diagrams for REC650 A07 1MRK006501-CB 9 PG 1.1 IEC V1 EN Figure 27. Binary input/output (BIO) option (Terminal X331, X334) 1MRK006501-BB 3 PG 1.1 IEC V1 EN...
  • Page 39 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 1MRK006501-BB 4 PG 1.1 IEC V1 EN Figure 30. Power supply module (PSM) 48-125V DC 1MRK006501-BB 6 PG 1.1 IEC V1 EN Figure 32. Transformer module (TRM) 1MRK006501-BB 5 PG 1.1 IEC V1 EN...
  • Page 40 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 1MRK006501-BB 10 PG 1.1 IEC V1 EN 1MRK006501-BB 8 PG 1.1 IEC V1 EN Figure 36. Binary input/output (BIO) option Figure 34. Binary input/output (BIO) option (Terminal X336, X339) (Terminal X326, X329) 1MRK006501-BB 9 PG 1.1 IEC V1 EN...
  • Page 41: Technical Data

    Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 17. Technical data General Definitions Reference The specified value of an influencing factor to which are referred the value characteristics of the equipment Nominal The range of values of an influencing quantity (factor) within which, under...
  • Page 42 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Analog inputs Table 2. Energizing inputs Description Value Rated frequency 50/60 Hz Operating range Rated frequency ± 5 Hz Current inputs Rated current, I 0.1/0.5 A 1/5 A...
  • Page 43 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Auxiliary DC voltage Table 3. Power supply Description Type 1 Type 2 nominal 100, 110, 120, 220, 240 V 48, 60, 110, 125 V DC AC, 50 and 60 Hz...
  • Page 44 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 5. Signal output and IRF output IRF relay change over - type signal output relay Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 10 A Make and carry 0.5 s...
  • Page 45 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 8. Ethernet interfaces Ethernet interface Protocol Cable Data transfer rate CAT 6 S/FTP or better 100 MBits/s LAN/HMI port (X0) LAN1 (X1) TCP/IP protocol Fibre-optic cable...
  • Page 46 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 14. Environmental conditions Description Value Operating temperature range -25...+55ºC (continuous) Short-time service temperature range -40...+70ºC (<16h) Note: Degradation in MTBF and HMI performance outside the temperature range of -25...+55ºC...
  • Page 47 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Type tests according to standards Table 16. Electromagnetic compatibility tests Description Type test value Reference 100 kHz and 1 MHz burst IEC 61000-4-18 disturbance test IEC 60255-22-1, level 3 •...
  • Page 48 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 16. Electromagnetic compatibility tests, continued Description Type test value Reference Power frequency immunity IEC 60255-22-7, class A test 300 V rms IEC 61000-4-16 • Common mode 150 V rms •...
  • Page 49 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 17. Insulation tests Description Type test value Reference Dielectric tests: IEC 60255-5 • Test voltage 2 kV, 50 Hz, 1 min 1 kV, 50 Hz, 1 min,...
  • Page 50 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 EMC compliance Table 20. EMC compliance Description Reference EMC directive 2004/108/EC Standard EN 50263 (2000) EN 60255-26 (2007) Current protection Table 21. Instantaneous phase overcurrent protection PHPIOC...
  • Page 51 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 22. Four step phase overcurrent protection OC4PTOC Function Setting range Accuracy ± 1.0% of I Operate current (5-2500)% of lBase at I ≤ I ± 1.0% of I at I > I Reset ratio >...
  • Page 52 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 23. Instantaneous residual overcurrent protection EFPIOC Function Range or value Accuracy ± 1.0% of I at I £ I Operate current (1-2500)% of lBase ± 1.0% of I at I > I Reset ratio >...
  • Page 53 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 24. Four step residual overcurrent protection EF4PTOC Function Range or value Accuracy ± 1.0% of I at I £ I Operate current (1-2500)% of lBase ± 1.0% of I at I > I Reset ratio >...
  • Page 54 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 25. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy ± 1.0% of I at I £ I (0.25-200.00)% of lBase Operate level for 3I ·cosj...
  • Page 55 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 25. Sensitive directional residual overcurrent and power protection SDEPSDE, continued Function Range or value Accuracy Operate time, non- 80 ms typically at 0.5 to 2 x I...
  • Page 56 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 26. Thermal overload protection, one time constant LPTTR Function Range or value Accuracy ± 1.0% of I Reference current (0-400)% of IBase ± 1.0°C Reference temperature (0-600)°C...
  • Page 57 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 28. Stub protection STBPTOC Function Range or value Accuracy ± 1.0% of I at I £ I Operating current (1-2500)% of IBase ± 1.0% of I at I > I Reset ratio >...
  • Page 58 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 31. Directional over/underpower protection GOPPDOP, GUPPDUP Function Range or value Accuracy Power level (0.0–500.0)% of SBase ± 1.0% of S at S < S ± 1.0% of S at S > S (1.0-2.0)% of SBase...
  • Page 59 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Voltage protection Table 33. Two step undervoltage protection UV2PTUV Function Range or value Accuracy Operate voltage, low and (1–100)% of UBase ± 0.5% of U high step Reset ratio <105%...
  • Page 60 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 35. Two step residual overvoltage protection ROV2PTOV Function Range or value Accuracy Operate voltage, step 1 (1-200)% of UBase ± 0.5% of U at U < U ±...
  • Page 61 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Frequency protection Table 37. Under frequency protection SAPTUF Function Range or value Accuracy Operate value, start function (35.00-75.00) Hz ± 2.0 mHz Operate value, restore frequency (45 - 65) Hz ±...
  • Page 62: Ccsrdif

    Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 39. Rate-of-change frequency protection SAPFRC Function Range or value Accuracy Operate value, start function (-10.00-10.00) Hz/s ± 10.0 mHz/s Operate value, restore enable (45.00 - 65.00) Hz ±...
  • Page 63 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 42. Breaker close/trip circuit monitoring TCSSCBR Function Range or value Accuracy Operate time delay (0.020 - 300.000) s ± 0,5% ± 110 ms Control Table 43. Synchronizing, synchrocheck and energizing check SESRSYN...
  • Page 64: Smpptrc

    Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 44. Autorecloser SMBRREC Function Range or value Accuracy Number of autoreclosing shots 1 - 5 Autoreclosing open time: shot 1 - t1 3Ph (0.000-60.000) s ± 0.5% ± 25 ms shot 2 - t2 3Ph (0.00-6000.00) s...
  • Page 65 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 46. Configurable logic blocks Logic block Quantity with cycle time Range or value Accuracy 5 ms 20 ms 100 ms INVERTER SRMEMORY RSMEMORY GATE PULSETIMER (0.000–90000.000) s ±...
  • Page 66 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Monitoring Table 48. Measurements CVMMXN Function Range or value Accuracy ± 0.5% of U Voltage (0.1-1.5) ×U at U£U ± 0.5% of U at U > U ±...
  • Page 67 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 50. Disturbance report DRPRDRE Function Range or value Accuracy Current recording ± 1,0% of I at I ≤ I ± 1,0% of I at I > Ir Voltage recording ±...
  • Page 68 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 51. Event list DRPRDRE Function Value Buffer capacity Maximum number of events in 1000 the list Resolution 1 ms Accuracy Depending on time synchronizing Table 52. Indications DRPRDRE...
  • Page 69 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 55. Disturbance recorder DRPRDRE Function Value Buffer capacity Maximum number of analog inputs Maximum number of binary inputs Maximum number of disturbance reports 100 Maximum total recording time (3.4 s recording time and...
  • Page 70 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 59. Circuit breaker condition monitoring SSCBR Function Range or value Accuracy Alarm levels for open and (0-200) ms ± 0.5% ± 25 ms close travel time...
  • Page 71 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Dimensions Table 64. Dimensions Description Value Width 220 mm Height 265.9 mm (6U) Depth 249.5 mm Weight box <10 kg (6U) Weight LHMI 1.3 kg (6U) Inverse time characteristics Table 65.
  • Page 72 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 66. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: k = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷...
  • Page 73 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 68. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of Class 5 +40 ms 0.01 unless otherwise stated æ...
  • Page 74 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 69. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of Class 5 +40 ms 0.01 unless otherwise stated æ...
  • Page 75 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Table 70. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in Class 5 +40 ms steps of 0.01 æ...
  • Page 76: Ordering

    Please refer to the available functions table for included application functions. To obtain the complete ordering code, please combine code from the tables, as given in the example below. Exemple code: REC650*1.1-A01X00-X00-B1A5-B-A-SA-AB1-RA3-AAAA-E. Using the code of each position #1-11 specified as REC650*1-2 2-3-4 4-5-6-7 7-8-9 9-10 10 10 10-11...
  • Page 77 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Casing Notes and Rules Rack casing, 6 U 1/2 x 19" Selection for position #5. Mounting details with IP40 of protection from the front Notes and Rules No mounting kit included Rack mounting kit for 6 U 1/2 x 19"...
  • Page 78 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Connection type for Analog modules Notes and Rules Compression terminals Ringlug terminals Analog system Slot position: Transformer module, 6I + 4U 1/5A, 100/220V Only for A07 Transformer module, 4I, 1/5A+1I, 0.1/0.5A+5U,...
  • Page 79 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Manuals Note: One (1) IED Connect CD containing user documentation (Operation manual, Technical manual, Installation manual, Commissioning manual, Application manual, Communication protocol manual, DNP, Communication protocol manual, IEC61850, Communication protocol manual, IEC60870-5-103, Type test certificate, Engineering manual and Point list manual, DNP3, Connectivity packages and LED label template is always included for each IED.
  • Page 80 Bay control REC650 1MRK 511 249-BEN - Product version: 1.1 Issued: February 2011 Related documents Documents related to REC650 Identity number Application manual 1MRK 511 246-UEN Technical manual 1MRK 511 247-UEN Commissioning manual 1MRK 511 248-UEN Product Guide 1MRK 511 249-BEN...
  • Page 82 Contact us ABB AB Substation Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 +46 (0) 21 14 69 18 www.abb.com/substationautomation...

Table of Contents