Pulse Input Command (Speed Command Selection) - Toshiba TOSVERT VF-AS3 Instruction Manual

Hide thumbs Also See for TOSVERT VF-AS3:
Table of Contents

Advertisement

3. 2
Pulse input command
(speed command selection)
It is possible to input inverter operation frequency command by PG pulse signals.
This command cannot be used when vector control operation with sensor is effective.
• Inverter output frequency can be controlled in ratio with the pulse output signal from the pulse oscillator.
• By inputting two-phase pulse with 90 degrees phase difference, it is possible to input forward and
reverse rotation commands.
See 2.2.3 for detail connection
3. 2. 1
Pulse input setting parameter
■ Set frequency command selection
Table 3-5. Parameter for frequency command selection
Title
FMOd
Frequency command select 1
F200
Frequency command priority select
F207
Frequency command select 2
F208
Frequency command switching frequency
■ Set frequency point setting
Table 3-6. Parameter for frequency point setting
Title
F234
RP/high speed pulse input point 1 setting
RP/high speed pulse input point 1
F235
frequency
F236
RP/high speed pulse input point 2 setting
RP/high speed pulse input point 2
F237
frequency
* Calculation of the reference frequency
The input pulse frequency is calculated to the percent base data. The calculated percent data is
converted to the frequency in accordance with 2 point setting (from [F234] to [F237]). Refer to the
below figure. By inputting two-phase pulse with 90 degrees phase difference, it is possible to input
forward and reverse rotation commands.
Function Name
Function Name
3-7
Adjustment Range
17: High resolution pulse train (option)
0: [FMOd]/[F207] (switched by TB)
1: [FMOd]/[F207] (switched by [F208])
Same as [FMOd] (1 - 23)
0.1 – [FH] Hz
Adjustment Range
-100 – 100%
0.0 – [FH] Hz
-100 – 100%
0.0 – [FH] Hz
E6582148
Setting at
Shipment
1
0
3
0.1
10
Setting at
Shipment
0
0.0
100
80.0
3. Functional Description