Dismantling Tab And Cap; Mechanical Control - ABB Emax E1 Installation And Service Instructions Manual

Low voltage air circuit-breakers emax series
Table of Contents

Advertisement

8.3.4.

Dismantling tab and cap

- The tab (1) of the release by rotating the screws (2) as shown in fi gure 33.
- Remove the front cap (3) by loosening the four screws (4).
2
1
4
Fig. 33
- If there is a minimum release, remove the coils support and release the control springs, closing and opening the switch.
Fig. 34
8.3.5.

Mechanical control

- Clean at the points indicated in fi gure 35. For excessive deposits, a laminated dilutant such as Henkel 273471 or the equivalent
can be used.
- Lubricate, at the points indicated in fi g. 35, the opening-closing shafts and hooks with MOBILGREASE 28 (EXXON MOBIL).
- Check that the opening and closing shafts are free to rotate.
Fig. 35
Model
L6555
2
1
3
3
4
Apparatus
Doc. No
1SDH000460R0002
Scale
Emax
Page No
21/74