Parameter Setting - ABB COM600 Product Manual

Grid automation controller
Hide thumbs Also See for COM600:
Table of Contents

Advertisement

ABB
Grid Automation Controller
COM600
Product version: 4.0
LOCAL
HMI
OPC Server
Ethernet switch
PLC
PLC
PLC
Fig. 3 Overview of an industrial system using Grid Automation Controller COM600
The single line diagram can be configured
to include an indication for the local/remote
selection switch. Alarm symbols and generic
symbols can be placed in the SLD to give
an even better overview of the status. In
addition, generic control buttons can be
added to control objects. A separate control
dialog is used for controlling the switching
device. It provides information on switching
device identification, reservation status and
interlocking conditions. The select-before-
execute logic is used to prevent unintended
operation. By reserving the switching device
for a single user the risk of controlling
the device from two different locations is
eliminated. Further, COM600 supports the tap
changer function.
Connection examples:
COM600 has by default four serial ports. The
number of serial ports can be increased using
the optional serial card. The four serial ports
enable the connection and combination of
different serial protocols. For example 3 SPA
+ 1 IEC 101 protocol or 2 SPA + 1 IEC 103 +1
IEC 101 protocol.
Electrical
SCADA
Ethernet switch
REF615
REF615
REF615
COM600 can be equipped with an optional
Ethernet interface. The number of Ethernet
interfaces can be increased by choosing the
optional Ethernet extension card.

3. Parameter setting

The parameter setting tool (PST) is used for
viewing and/or setting parameters in IEDs
supporting transparent SPA, Modbus or
IEC 61850 parameterization. The PST enables
activation of the parameter setting function
for the chosen IEDs. In addition, it enables
that only selected parameters are shown in
the web HMI of COM600 limiting the number
of visible parameters to the ones that are con-
sidered important for the user. Changes in the
settings require that the user has engineering
or administrator rights in COM600.
1MRS756764 D
DISTRIBUTION
CONTROL
SYSTEM
OPC Client / Server
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents