ABB Relion REB500 Product Manual

Hide thumbs Also See for Relion REB500:

Advertisement

Relion®
Distributed busbar protection REB500
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion REB500

  • Page 1 Relion® Distributed busbar protection REB500 Product Guide...
  • Page 2: Table Of Contents

    Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Contents 1. Main features ................4 8. REB500 Process bus configuration ........18 2. Application ................. 4 9. Hardware description .............. 19 3. Mode of installation ..............9 10.
  • Page 3 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. © Copyright 2016 ABB. All rights reserved.
  • Page 4: Main Features

    Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Application The main CTs supplying the currents to the busbar protection have to fulfill only modest performance requirements (see page 17). The protection operates REB500 discriminatively for all faults inside the zone of protection The numerical busbar protection REB500 is designed for and remains reliably stable for all faults outside the zone the high-speed (sub-cycle), selective protection of MV, HV...
  • Page 5 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 QB1 QB2 Figure 3. Triple busbar Figure 4. 1 ½ breaker system...
  • Page 6 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Functional overview Included functionalities (● standard, ○ optional) Table 1. Protection function Main functionality IEEE REB500 IEC 61850 ● Busbar protection PDIF ○ Busbar protection with neutral current 87BN PDIF ○...
  • Page 7 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Table 2 Bay protection functions of line variant L-V2 (optional) Bay protection function Main functionality IEEE REB500 IEC 61850 Distance protection DIST PDIS Definite time over and undercurrent protection OCDT PTOC Inverse time overcurrent protection...
  • Page 8 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Cyber security · Secure communication Main features · User Access Management · User Activity Logging Low-impedance busbar protection · Centralized account management · High functional reliability due to two independent ·...
  • Page 9: Mode Of Installation

    Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Centralized installation Mode of installation The central processing unit and the bay units are mounted in 19"racks (up to two bay units each rack), according to There are three versions of installing the numerical busbar the size of the busbar system in one or more cubicles (see protection REB500:...
  • Page 10: System Design

    Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Figure 6. Centralized installation After acquisition, the analog current and voltage signals are converted to numerical signals which are pre- System design processed and filtered. Zero-sequence voltage and zero- current signals are also calculated internally.
  • Page 11 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - MOSFET technology and offer an improved trip-time Central unit (500CU04) performance. The hardware structure is based on a closed, monolithic casing. A software logic enables the input and output channels to be assigned to the various functions.
  • Page 12: Functionality

    Functionality Busbar protection The protection algorithms are based on two well-proven where measuring principles which have been applied successfully in earlier ABB low-impedance busbar stabilizing factor protection systems: stabilization factor limit (typically 0.80) differential current pick-up value Stabilized differential current measurement...
  • Page 13 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Case 1: external faut = 139° Diagram of busbar = 139° Operating characteristic Case 2: internal fault = 40° 180° external fault = 74° 74° = 40° internal fault 0°...
  • Page 14 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Pole discrepancy Communication interface A pole discrepancy protection algorithm supervises that all Communication with the station automation system (SAS) three poles of a circuit-breaker open within a given time. is possible via the central unit.
  • Page 15 PCM600 Connectivity Package the aid of human machine interfaces at three levels. After installation and commissioning, PCM600 offers easy access to the installed base of ABB substation automation Local HMI products within the substation. The connectivity package The local display interface installed in the central unit and...
  • Page 16: Additional Features

    Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Additional features Table 4. Typical time synchronization accuracy Method Accuracy Self-supervision All the system functions are continuously monitored to no external time synchronization 1 min / ensure the maximum reliability and availability of the month protection.
  • Page 17 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Conversely, during the opening movement, the N/O possible for it to share protection cores with other contact must not open before the isolator main contact protection devices. gap exceeds its flashover point.
  • Page 18: Reb500 Process Bus Configuration

    Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - REB500 Process bus configuration Figure 12. REB500 Process bus configurations up to 60 Bay Units...
  • Page 19: Hardware Description

    Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Hardware description The following mounting alternatives are available (IP40 protection from the front): Bay Unit Central Unit · Flush mounting kit · 19” rack mounting kit ·...
  • Page 20 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Two rack mounted IEDs 224 mm + 12 mm with ring lug 25.5 mm 482.6 mm (19”) 265.9 mm (6U) 13 mm Figure 15. Two rack mounted Bay Units side by side Layout and dimensions Central Unit Rack mounted IED 224 mm + 12 mm with ring lug...
  • Page 21: Connection Diagrams

    Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - 10. Connection diagrams Rear view Bay Unit Rear view Central Unit X10 05 X331 X336 X10 01 X34 7 X10 02 X10 10 X334 X339 X10 09 X30 4 X34 9 X10 08...
  • Page 22 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Connection diagrams Bay Unit Binary outputs: Binary inputs: X304 X309 DC1- In Service Start BFP L1_1 Start BFP L2_1 X307 Start BFP L3_1 TRIP1+ DC1- TRIP CB L1_1 Start BFP L1L2L3_1 TRIP1+ Spare...
  • Page 23 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Precision binary outputs: Binary inputs: X326 (Option) X326 (Option) TRIP1+ Spare TRIP CB L1_1 TRIP1+ TRIP CB L2_1 Spare TRIP1+ Spare TRIP CB L3_1 TRIP2+ TRIP CB L1_2 X329 (Option) TRIP2+ TRIP CB L2_2...
  • Page 24 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Analogue inputs: Protection Function Measured value Currents X101 Current input L1 ● ● ● ● ● Phase current L1 Current input L1_0 (Line) Current input L2 ●...
  • Page 25 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Interfaces: Connection to a detached HMI (LHMI will be switch off if X0 is used.) Connection to REB500 Process bus (via Ethernet switch) X4 (not used) X9 (not used) Power Supply: X410...
  • Page 26 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Connection diagrams Central Unit Binary outputs: X349 X336 In Service Spare X347 Spare Protection blocked Spare Output relays blocked Spare Spare Isolator alarm Switch inhibit Spare Spare Differential current alarm Spare...
  • Page 27 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Binary inputs: X304 (Not used) X339 OC01 02 02 Spare OC02 Accept bus image alarm OC03 External reset OC04 Block all protection functions OC05 Block output relays OC06 Block busbar protection OC07...
  • Page 28 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Interfaces: X1000 (not used) Connection a detachedHMI (LHMI will be switch off if X0 is used.)) X1001 LAN0A Connection to REB500 Station bus connection 100BaseFx/LC process-bus IEC 61850-8-1 (via Ethernet switch) PRP Line A...
  • Page 29: Technical Data

    Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - 11. Technical Data Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified requirements Operative range The range of values of a given energizing quantity for which the equipment, under specified...
  • Page 30 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Table 7. Power supply Description PSM02 PSM03 100, 110, 120, 220, 240V AC 50/60Hz 48-125 V DC nominal 110, 125, 220, 250V DC 80...120% of Un (88...300 V DC) variation 80...120% of Un (38.4...150 V DC) 80...115% of Un (80...276 V AC)
  • Page 31 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Table 11. Power output relays Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 15 A Make and carry for 0.5 s 30 A Breaking capacity when the control-circuit time constant ≤1 A (48 V)
  • Page 32 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Table 15. IRIG-B interface Type Protocol Cable Tension clamp terminal IRIG-B Shielded twisted pair cable Recommended: CAT 5, Belden RS-485 (9841- 9844) or Alpha Wire (Alpha 6222-6230) Optical interface (X1010) IRIG-B MM 62,5/125 µm glass fiber core, ST connector...
  • Page 33 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Table 20. Environmental test Description Type test value Reference Cold tests IEC 60068-2-1/ANSI C37.90-2005 operation 96 h at -25ºC (chapter 4) 16 h at -40ºC storage 96 h at -40ºC IEC 60068-2-2/ANSI C37.90-2005 Dry heat tests...
  • Page 34 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Type Tests according to standards Table 21. Electromagnetic compatibility tests Description Type test value Reference 100 kHz and 1 MHz burst disturbance IEC 60255-26 test IEC 61000-4-18, level 3 ANSI C37.90.1-2002 Common mode 2.5 kV...
  • Page 35 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Description Type test value Reference Voltage dips and short interruptions on Dips: IEC 60255-26 DC power supply 40%/200 ms IEC 61000-4-29 70%/500 ms Interruptions: 0-50 ms: No restart 0...∞...
  • Page 36 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Table 23. Mechanical tests Description Reference Requirement Vibration response tests (sinusoidal) IEC 60255-21-1 Class 1 Vibration endurance test IEC 60255-21-1 Class 1 Shock response test IEC 60255-21-2 Class 1 Shock withstand test IEC 60255-21-2...
  • Page 37 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Station level functions (applicable for nominal frequencies of 50 and 60 Hz) Table 26. Busbar protection 87B (PDIF) Function/ Parameter Range/ Value Accuracy Min. fault current pick-up setting (I 200 to 6000 A in steps of 100 A ±5% of I at I...
  • Page 38 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Table 29. Overcurrent Protection 51 (PTOC) Function/ Parameter Range/ Value Accuracy Characteristic definite time ±5% of I at I < I Operate current 0.1 to 20 x I in steps of 0.1 x I ³...
  • Page 39 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Table 33. Check zone criterion 87CZ (PDIF) Function/ Parameter Range/ Value Accuracy Min. fault current pick-up setting (I ) neutral 500 to 6000 A in steps of 200 A ±5% of I at I <...
  • Page 40 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Station communication Table 37. Station communication protocols IEC 61850-8-1 IEC 61850-8-1 supports - Edition 1 and Edition 2 of the standard, configurable in HMI - Time synchronization via SNTP: typical accuracy ± 1 ms - Two independent time servers are supported.
  • Page 41 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Weight box 8 kg (<16.64 lbs) 10.5 kg (<23.15 lbs) Weight LHMI 1.3 kg (2.87 lbs) 1.3 kg (2.87 lbs) Mounting Table 41. Cubicle design Description Type Cubicle Standard type RESP97 (for details see 1MRB520159-BEN)
  • Page 42: Ordering For Customized Ied

    Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - 12. Ordering for customized IED Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions can only be ordered in combination with other functions and that some functions require specific hardware selections. Central Unit Order Code rules - Software option multiple selection is possible...
  • Page 43 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Ordering code Central Unit Example: REB500* 8.2 - CU04 - S10 A1A2- B1X0 - E K - SA A - F - A A - A C REB500* 8.2 -CU04 -S - B1X0- E - F - A...
  • Page 44 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Ordering code Central Unit (cont’d) Example: REB500* 8.2 - CU04 - S10 A1A2 - B1X0 - E K - SA A - F - A A - A C REB500* 8.2 -CU04 - S - B1X0 - E - F - A...
  • Page 45 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Ordering code Bay Unit Example: REB500* 8.2 - BU04- C1C2C5D1 - B1X0- C A -SA- A X0 -SA3- A - A REB500* 8.2 - BU04- - B1X0- C - A - A see cont’d Software...
  • Page 46 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Ordering code Bay Unit (cont’d) Example: REB500 * 8.10 - BU04 - C1C2C5D1 - B1X0- C A - SA - A X0 - SA3 - AX - A REB500 * 8.10 - BU04 - -A - A Human machine interface...
  • Page 47 Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Order code Switches/ Transceivers Switch AFS677: x 1MRK010500- Transceiver x 1MRK010501- AA System up to 10 BU +2 = n BU’s up to 24 BU +6 = n BU’s up to 38 BU +8 =...
  • Page 48: Manuals

    Distributed busbar protection REB500 1MRK 505 352-BEN Product version: 8.2 Issued: 2016-03-01 Revision: - Accessories Table 42. Available Accessories and engineering facilities Equipment Ordering no Rack mounting kit 6U 3/4x19" case 1KHL400527R0001 Rack mounting kit 6U 1/2x19" case 1KHL400239R0001 Flush mounting kit 6U 1/2x19" case 1KHL400228R0001 Wall mounting bracket 1KHL400317R0001...
  • Page 50 Contact us ABB AB Substation Automation Products SE-721 59 Västerås Sweden Telephone: +46 (0) 21 32 50 00 Facsimile: +46 (0) 21 14 69 18 http://www.abb.com/substationautomation...